1 из 1

Omron CJ1W-AD041-V1 CJ Series Analog Input Unit

Omron CJ1W-AD041-V1 CJ Series Analog Input Unit

Остался только 8 товар(ы) на складе
  • Производитель: Omron

  • Номер продукта: ÿCJ1W-AD041-V1

  • Страна происхождения:Япония

  • Тип продукта: Analog Output Modules

  • Оплата: Т/Т, Western Union

  • Вес: 1500г

  • Размеры: 125 x 105 x 35 mm

  • Порт отгрузки: Сямынь

  • Гарантия: 12 месяцев

Количество
Просмотреть полные детали

Description

Integrating seamlessly into Omron Sysmac CJ-series PLCs, the Omron CJ1W-AD041-V1 provides high-density, precise analog-to-digital conversion across four physical input channels. This module processes voltage and current field transmitter signals, translating physical variables into highly accurate digital data blocks. Its backplane-driven processor supports advanced signal scaling, peak-hold execution, and customized input filtration algorithms directly inside the memory allocation table, eliminating the need for complex ladder-logic averaging routines.

Features

  • Four Selectable Channels: Individual configuration per channel for current (4 to 20 mA) or voltage (1 to 5 V, 0 to 5 V, 0 to 10 V, -10 to +10 V) inputs.
  • High-Speed A/D Conversion: Configurable conversion speeds reaching up to 250 microseconds per point in high-speed mode.
  • Selectable Resolution Modes: Offers standard 1/4000 resolution or high-resolution 1/8000 mode for ultra-precise process variable tracking.
  • Detachable Terminal Block: Features an 18-point detachable M3 screw terminal block, enabling swift module replacements without re-wiring.
  • Built-In Diagnostics: Real-time detection of input wire disconnection, over-range levels, and internal hardware faults.

Applications

  • Chemical processing and multi-loop temperature tracking via 4-20 mA transmitters.
  • Water and wastewater monitoring involving volumetric flow and pressure transmitters.
  • Variable frequency drive (VFD) speed-feedback control systems.
  • Precise packaging and tension-control systems utilizing load cells and signal conditioners.

Technical Specifications

Parameter Specification Values
Manufacturer Omron Industrial Automation
Model Number CJ1W-AD041-V1
Product Series CJ Series (CJ1G, CJ1H, CJ1M, CJ2M, CJ2H)
Number of Analog Inputs 4 Channels
Input Voltage Ranges 0 to 5 V, 1 to 5 V, 0 to 10 V, -10 to +10 V
Input Current Ranges 4 to 20 mA
Resolution Options 1/4000 (Standard), 1/8000 (High-Resolution Mode)
Conversion Time 1.0 ms/point max. (Standard), 250 microsec/point max. (High-Speed)
Accuracy (25 degC) Voltage: +/-0.2% of FS; Current: +/-0.4% of FS
Channel-to-Channel Isolation None (Common ground plane)
Backplane Bus Isolation Photocoupler isolated between input terminals and CPU internal logic
Internal Current Consumption 0.42 A at 5 VDC (Backplane rail)
External Wiring Terminal 18-point detachable terminal block (M3 screws)
Standards & Approvals CE, UL (Class I Div 2), NK, Lloyd's
Country of Origin Japan
Shipping Weight (Calculated) 0.32 kg
Package Dimensions (Calculated) 125 x 105 x 35 mm

Connections and Interfaces

Terminal No. Signal Label Description
1 V IN 1 Voltage Input Terminal, Channel 1
2 I IN 1 Current Input Terminal, Channel 1
3 COM 1 Common Terminal, Channel 1
4 V IN 2 Voltage Input Terminal, Channel 2
5 I IN 2 Current Input Terminal, Channel 2
6 COM 2 Common Terminal, Channel 2
7 V IN 3 Voltage Input Terminal, Channel 3
8 I IN 3 Current Input Terminal, Channel 3
9 COM 3 Common Terminal, Channel 3
10 V IN 4 Voltage Input Terminal, Channel 4
11 I IN 4 Current Input Terminal, Channel 4
12 COM 4 Common Terminal, Channel 4
13 to 17 NC No Connection (Do not wire)
18 SLD Shield Terminal (Internal system ground)

Empirical Engineering Insights

Alternative Models & Compatibility

The "V1" suffix indicates critical updates over the legacy non-V1 module. It introduces the high-resolution mode (1/8000 conversion) and reduces overall conversion times down to 250 microseconds per channel. The module is fully backward compatible; however, if you are upgrading from an older version in a system that utilized specific unit settings, you must reconfirm the I/O allocation mapping in CX-Programmer to ensure the CPU can register the newer features.

Application Pitfalls & Engineering Notes

This unit features non-isolated input channels, meaning all four channels share a common internal ground plane. If you feed analog signals from devices powered by different external DC supplies, ground-loop offset voltages will distort the analog readings or potentially trigger hardware faults on the module. For isolated channels, choose the CJ1W-AD042 or add signal isolators externally on each loop.

Commissioning & Wiring Tips

Always route the analog signal cabling away from high-voltage motor power cables to mitigate EMI noise coupling. Connect the shield line of the twisted-pair cable exclusively to the SLD terminal (Pin 18) on the module's terminal block. Unused channels must be explicitly disabled in the software configuration; otherwise, they will float and cause the PLC's internal error flags to cycle unexpectedly.

Installation Guidelines

CRITICAL WARNING

Do not insert or remove the CJ1W-AD041-V1 module from the PLC backplane while the rack is powered. De-energize the main control supply completely and allow all internal bus charges to bleed down to zero before handling. Live insertion will damage the backplane interface ASIC and corrupt the memory tables within the CPU module.

1
Align the structural hook on the upper section of the module with the slot on the PLC backplane. Rotate the module downwards until it seats flush.
2
Secure the unit by locking the yellow slider mechanisms at both the top and bottom of the module casing. Ensure they click completely into place.
3
Wire current loops using the I IN and COM terminals; wire voltage loops via the V IN and COM terminals. Tighten terminal block screws to a maximum torque of 0.5 N-m.
Loading product navigation…

Can I mix voltage and current signals on the same CJ1W-AD041-V1 module?

Yes. Each of the four channels can be configured independently for either voltage or current signals in the software settings, using the dedicated terminal assignments for each channel.

What is the consequence of not isolating signals on this card?

Since there is no channel-to-channel isolation, sharing different ground loops across channels can inject ground currents, offset voltages, and noise, potentially skewing signals or damaging input circuitry.

How do I configure the module for high-resolution 1/8000 mode?

Resolution is adjusted by accessing the DM area settings corresponding to the unit's allocated memory words within CX-Programmer, and setting the resolution flag high prior to PLC initialization.

Do I need external shunt resistors to measure current inputs?

No, the card features built-in current measurement circuitry. You wire the current source loop directly to the designated I IN and COM terminals of the respective channel.

Глобальная экспресс-доставка

  • Стандартная доставка: 4-6 рабочих дней через DHL, FedEx и UPS.
  • Экспресс-отправка: Отправка в тот же день для заказов со склада, сделанных до 14:00 (GMT+8).
  • Мировое покрытие: Обслуживаем более 150 стран, включая быструю доставку в Саудовскую Аравию и ОАЭ.

Возвраты и гарантия

  • 30-дневная гарантия: Принимаются возвраты товаров со склада в оригинальной, заводской запечатанной упаковке.
  • 12-месячная гарантия: Каждый промышленный компонент поддерживается нашей профессиональной технической гарантией.

Заказы обрабатываются и доставляются с понедельника по пятницу (кроме государственных праздников).


Для полной информации о праве на возврат, сборах за пополнение запасов и международных возвратах, пожалуйста, ознакомьтесь с нашим официальным Политика возврата и возврата средств .

TECHNICAL SPECIFICATIONS

Country of origin
Япония

Недавно просмотренные товары

Технические знания

Продвинутая булева логика в программировании ПЛК с использованием FBD: практические промышленные применения за пределами базовой логики

В статье объясняются несколько продвинутых функций булевой логики, используемых в программировании ПЛК, помимо базовых операций AND, OR и NOT. Рассматривается, как такие инструменты, как таблицы...

Булева логика в программировании ПЛК: понимание логических элементов FBD

Булева логика является основой каждой программы ПЛК. От простого управления машинами до сложных систем промышленной автоматизации, логические элементы определяют, как контроллеры реагируют на...

Подробное руководство по промышленным файрволам и сегментации сетей ОТ

Промышленные межсетевые экраны играют ключевую роль в кибербезопасности операционных технологий (OT), защищая сети ПЛК, ДСК и SCADA посредством сегментации, контроля входящего и исходящего трафика, а...

Руководство по роботизированным захватам: от деликатного обращения до тяжелой автоматизации

Современные роботизированные захваты развиваются дальше традиционных механических челюстей. От клеевых систем, вдохновленных гекконами, и мягких захватов пищевого класса до инструментов на базе ИИ...

Воспоминание: как ранние электродвигатели изменили подземную добычу полезных ископаемых

От компрессоров с приводом от каната до аккумуляторных вагонеток — ранние горные работы стали поворотным моментом в индустриальной электрификации. В этой статье рассматривается, как электродвигатели...

Factory I/O: современный инструмент моделирования ПЛК для обучения промышленной автоматизации

Factory I/O меняет обучение ПЛК, предоставляя погружающие 3D промышленные симуляции для студентов, инженеров и команд технического обслуживания. Платформа сокращает разрыв между теорией и практикой...