1 จาก 1

BECKHOFF EL9222-9664 2-Channel 24 VDC Overcurrent Protection Terminal

BECKHOFF EL9222-9664 2-Channel 24 VDC Overcurrent Protection Terminal

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: EL9222-9664

  • Country of origin:เยอรมนี

  • Product Type: Overcurrent protection terminal

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 12 mm x 100 mm x 68 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

ปริมาณ
ดูรายละเอียดทั้งหมด

Product Overview

The EL9222-9664 (EL92229664) is a high-performance 2-channel electronic overcurrent protection terminal designed to safeguard 24 VDC system components within the EtherCAT I/O ecosystem. Unlike traditional thermal-magnetic circuit breakers, the EL9222-9664 provides precise, fast-acting electronic monitoring and shutdown capabilities for two independent channels with asymmetrical rated currents (6 A and 4 A). This module is essential in complex automation environments—such as high-speed assembly lines, semiconductor tools, and robotic cells—where selective protection is required to isolate faulty branch circuits without collapsing the entire control voltage rail. By integrating advanced diagnostics, including a 90% load advance warning, it enables predictive maintenance and significantly reduces troubleshooting time in mission-critical industrial applications.

Technical Configuration

The EL9222-9664 is engineered for versatility and reliability, featuring two protected outputs: Output 1 is rated at 6 A and Output 2 at 4 A. A unique hardware feature of this specific model is that Output 1 is routed additionally via the power contact, allowing for streamlined power distribution across the terminal bus. The module incorporates an "Advance Warning" function that triggers at 90% of the rated current, providing a proactive signal before a shutdown occurs. For ultimate safety, it includes integrated fail-safe elements (10 A Fast / 6 A Time-lag) and an overvoltage power-off threshold of ≥ 32 V DC. The interface is user-friendly, featuring LED buttons for local reset and status indication, while maintaining a slim 12 mm profile to maximize DIN rail density.

Technical Specifications

Feature Specification
Model EL9222-9664
Brand BECKHOFF
Technology 2-Channel Overcurrent Protection
Nominal Voltage 24 VDC
Rated Current 6 A (CH1) / 4 A (CH2)
Input Current Max. 10 A
E-bus Consumption typ. 80 mA
Overvoltage Protection ≥ 32 VDC (Automatic Power-off)
Isolation 500 V (E-bus / signal voltage)
Hold Time (Post-off) ≥ 10 s
Operating Temp 0 to +55 deg C
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Shipping Weight 2.0 kg

Technical FAQs

How does the 90% advance warning benefit my control system?

The 90% warning allows the PLC to monitor if a specific branch is approaching its limit. This is critical for detecting aging actuators or increased friction in mechanical systems before they cause a full trip, allowing for scheduled maintenance instead of emergency downtime.

Can I reset the channel remotely via EtherCAT?

Yes, while the EL9222-9664 features a physical LED button for local manual intervention, the status and control (reset/switch-off) can be fully integrated into the EtherCAT process data for remote management via TwinCAT or other controllers.

What happens if the input voltage exceeds 32 VDC?

The terminal features an integrated overvoltage power-off mechanism. If the supply voltage hits 32 VDC or higher, the module will automatically disconnect the outputs to protect downstream sensitive electronics from voltage spikes or power supply failures.

What is the purpose of the integrated fail-safe fuse?

The integrated fuse (10 A / 6 A) acts as a secondary hardware protection layer. In the extremely rare event of an electronic component failure within the terminal itself, the mechanical fuse ensures the circuit is safely interrupted, conforming to global safety standards.


Engineering & Installation Guide

  • Selective Protection Logic: When designing your power distribution, ensure that the total sum of the downstream loads does not exceed the individual channel ratings (6 A or 4 A). For inductive loads with high inrush currents (e.g., large DC motors), verify that the starting peak does not trigger the electronic trip curve prematurely.

  • Wiring and Termination: Use the spring-actuation mechanism with a standard flat-head screwdriver. For high-vibration environments, flexible conductors (f) with ferrules are recommended to ensure a gas-tight connection. The stripping length must be strictly 8 to 9 mm; insufficient stripping can lead to high-resistance contact and localized overheating at the 10 A max input point.

  • Power Contact Continuity: Note that Output 1 utilizes the power contact. When mounting multiple EL9222-9664 terminals side-by-side, ensure the power contact bus (up to 10 A max) is correctly sized for the cumulative current of the entire terminal block to prevent thermal overloading of the backplane.

 

การจัดส่งด่วนทั่วโลก

  • การจัดส่งมาตรฐาน: 4-6 วันทำการ ผ่าน DHL, FedEx และ UPS
  • จัดส่งด่วน: จัดส่งในวันเดียวกันสำหรับคำสั่งซื้อที่มีในสต็อกและสั่งก่อนเวลา 14:00 น. (GMT+8)
  • ครอบคลุมทั่วโลก: ให้บริการมากกว่า 150 ประเทศ รวมถึงการจัดส่งด่วนไปยังซาอุดีอาระเบียและสหรัฐอาหรับเอมิเรตส์

การคืนสินค้าและการรับประกัน

  • การรับประกัน 30 วัน: รับคืนสินค้าที่มีในสต็อกในบรรจุภัณฑ์เดิมที่ปิดผนึกจากโรงงาน
  • การรับประกัน 12 เดือน: อะไหล่อุตสาหกรรมทุกชิ้นได้รับการรับประกันทางเทคนิคจากผู้เชี่ยวชาญของเรา

คำสั่งซื้อจะถูกดำเนินการและจัดส่งในวันจันทร์ถึงวันศุกร์ (ไม่รวมวันหยุดราชการ)


สำหรับคุณสมบัติครบถ้วน ค่าธรรมเนียมการเติมสินค้าใหม่ และรายละเอียดการคืนสินค้าระหว่างประเทศ กรุณาดูที่เว็บไซต์อย่างเป็นทางการของเรา นโยบายการคืนเงินและการคืนสินค้า .

TECHNICAL SPECIFICATIONS

Color pattern
สีขาวอมเทา
Country of origin
เยอรมนี

สินค้าที่ดูล่าสุด

ความรู้ทางเทคนิค

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...