1 of 1

Beckhoff BX9000 Bus Terminal Controller

Beckhoff BX9000 Bus Terminal Controller

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: BX9000

  • Country of origin:Germany

  • Product Type: Bus Terminal Controllers

  • Payment: T/T, Western Union

  • Weight: 250g

  • Dimensions: 81 mm x 100 mm x 90 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

Designed as an autonomous, high-performance PLC with an integrated Ethernet port, the Beckhoff BX9000 Bus Terminal Controller bridges decentralized I/O systems and higher-level networks. This compact controller executes complex control programs locally while processing communication tasks independently. Programmed using the standardized TwinCAT system in accordance with IEC 61131-3, the module ensures flexible, modular architecture for a broad range of industrial Automation setups.

The unit features extensive local memory capacities, including 256 kB of program memory and 256 kB of data memory, with additional remanent and persistent data allocation. Up to 64 local Bus Terminals connect directly to the system block, with expansion up to 255 terminals possible via the integrated K-bus extension. For diagnostic operations, it provides an illuminated FSTN display, status LEDs, and a mechanical joystick switch for localized menu navigation and system diagnostics.

Features

  • Versatile Programming: Configurable via TwinCAT over the network Ethernet interface or the dedicated serial programming connection.
  • Multi-Language Execution: Fully compliant with IEC 61131-3 standards (IL, LD, FBD, SFC, ST).
  • Robust Connectivity: Equipped with an RJ45 Ethernet interface (10/100 Mbit/s auto-baud rate), dual serial ports (RS232 and RS485), and an integrated CANopen-based Smart System Bus (SSB).
  • Local HMI Interface: Integrated 2 x 16 character backlit FSTN display paired with a navigational joystick for real-time local parameters.
  • Flexible Expansion: Seamlessly manages up to 255 individual Bus Terminals using K-bus extension accessories.
  • Time Tracking: Contains an onboard battery-backed real-time clock for system-wide time-stamping.

Applications

  • Distributed plant automation and localized process control systems.
  • Substation diagnostic nodes and monitoring stations in utility networks.
  • Machine-level PLC control with upstream Ethernet TCP/IP supervisory communication.

Technical Specifications

Manufacturer Beckhoff
Part Number / Model BX9000
Program Memory 256 kbytes
Data Memory 256 kbytes
Remanent / Persistent Data 2 kbytes / 1 kbyte
Cycle Time Approx. 1 ms for 1,000 instructions (excluding I/O cycle)
Bus Terminals Supported 64 (up to 255 with K-bus extension)
Data Transfer Rates 10/100 Mbit/s with automatic recognition
Bus Interface RJ45
Serial Interfaces COM1: 1 x RS232, COM2: 1 x RS232 or RS485
Sub-bus System SSB (CANopen-based subsidiary bus)
Power Supply Voltage 24 V DC (-15 % / +20 %)
Input Current 140 mA + (total K-bus current)/4, max. 500 mA
Starting Current 2.5 x continuous current
K-bus Current Supply 1450 mA
Power Contacts Capacity Max. 24 V DC / max. 10 A
Electrical Isolation 500 V (power contact / supply voltage)
Diagnostics / Display Illuminated 2 x 16 character FSTN display, 2 x Power LEDs, 2 x K-bus LEDs
Operating Temperature 0 to +55 Celsius
Storage Temperature -25 to +85 Celsius
Relative Humidity 95 %, non-condensing
Protection Rating IP20
Dimensions (W x H x D) 81 mm x 100 mm x 90 mm
Weight Approx. 250 g

Connections and Interfaces

Interface Type Specification / Compatibility
Ethernet Port RJ45 connection, 10/100 Base-T
COM1 Interface RS232 serial connection for programming and diagnostic data
COM2 Interface RS232 or RS485 configuration for peripheral device attachment
K-Bus Direct connection backplane interface for local Bus Terminals
Wiring Type Solid wire (s), stranded wire (st), or ferrule (f) connection using spring actuation
Solid Wire Cross-Section (s) 0.08 to 2.5 mm²
Stranded Wire Cross-Section (st) 0.08 to 2.5 mm²
Ferrule Cross-Section (f) 0.14 to 1.5 mm²
Stripping Length 8 to 9 mm

Installation Guidelines

  • Mounting: Mount directly on a standard 35 mm DIN rail conforming to EN 60715 using the integrated lock mechanism.
  • Positioning: Variable mounting orientation is acceptable. Utilize the built-in double slot and key connection for reliable side-by-side terminal mounting.
  • Terminal Wiring: To insert or remove connection wires, actuate the terminal springs by applying pressure with a standard screwdriver.
  • Thermal Considerations: Maintain free air convection clearance inside the electrical cabinet to keep operating conditions below the +55 Celsius threshold.

Compliance and Certifications

  • CE
  • UL

Which programming environments are compatible with the Beckhoff BX9000?

The BX9000 is programmed using the TwinCAT configuration and PLC programming system over its integrated Ethernet TCP/IP interface or the serial programming port.

What is the maximum I/O expansion capacity of the BX9000?

The controller supports up to 64 local Bus Terminals directly on the assembly block. With a K-bus extension module, it can be expanded to connect up to 255 Bus Terminals.

What serial interfaces are built into the BX9000 system?

The controller features two serial interfaces: COM1 is configured as 1 x RS232, and COM2 can operate as either 1 x RS232 or 1 x RS485.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Recently Viewed Products

Technical knowledge

Modernizing Bailey INFI 90 Symphony HMIs Running on OpenVMS Alpha

A practical guide to replacing aging Bailey Symphony operator stations running on OpenVMS Alpha. It compares Alpha emulation, OpenVMS x86 migration, OPC re-platforming, and phased ABB modernization.

Why Maintenance Data Is Essential for Industrial Reliability

Maintenance data connects work orders, sensor signals, asset history, costs, and technician knowledge. Used well, it improves planning, reliability, predictive maintenance, spare-parts control, and...

Suyuqlik quvvat tizimlarini almashtirish uchun mo‘ljallangan elektr aktuatorlar: Amaliy sanoat avtomatizatsiyasi qo‘llanmasi

Ushbu maqola SMCning e-Actuator seriyasi kabi integratsiyalashgan elektr aktuatorlarining sanoat harakatini boshqarishda an’anaviy pnevmatik va gidravlik tizimlarni qanday almashtirayotganini...

Sanoat avtomatlashtirish ilovalari uchun OpenPLC yordamida matematik amallar bajarish

Ushbu maqola PLC tizimlari sanoat avtomatlashtirishida qo‘shish, ayirish, ko‘paytirish, bo‘lish, modulo va darajaga ko‘tarish kabi asosiy matematik amallarni qanday bajarishini tushuntiradi. Unda...

FBD PLC dasturlashda ilg‘or Boolean mantiqi: asosiy mantiqdan tashqari amaliy sanoat ilovalari

Maqola PLC dasturlashda asosiy AND, OR va NOT amallaridan tashqari bir nechta ilg‘or Boolean mantiq funksiyalarini tushuntiradi. Unda haqiqat jadvallari, multiplexerlar, impuls generatorlari va...

PLC dasturlashda Boolean mantiqi: FBD mantiq eshiklarini tushunish

Boolean mantiq har bir PLC dasturining asosidir. Oddiy mashina boshqaruvlaridan tortib murakkab sanoat avtomatlashtirish tizmlarigacha, mantiqiy eshiklar boshqaruvchilarning o‘zgaruvchan kirishlar va...