1 trong số 3

Allen-Bradley 1771-OB PLC-5 Digital DC Output Module

Allen-Bradley 1771-OB PLC-5 Digital DC Output Module

Only 8 item(s) left in stock
  • Manufacturer: Allen-Bradley

  • Product No.: 1771-OB

  • Country of origin:Hoa Kỳ

  • Product Type: Digital Output Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 900g

  • Dimensions: 3.5cm x 13cm x 14.5cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Số lượng
Xem toàn bộ chi tiết

The 1771-OB is an 8-channel digital solid-state electronic device engineered for the PLC-5 / 1771 I/O Platform to drive low-voltage direct current industrial control hardware. It provides electrical switching paths for various field components, including DC motor drivers, status indicators, and industrial solenoid valves. The internal control micro-logic is energized via the local I/O chassis backplane rail, drawing a maximum current of 165 mA to maintain structural optoelectronic isolation between high-level plant field elements and core processor busses. System integration is established through the standard 1771-WA wiring arm connector assembly, permitting physical hot-swapping or card replacement sequences without disturbing landed field terminal connections.

Features

  • High-Density Output Distribution: Integrates eight independent solid-state DC switching circuits within a single-slot chassis package.
  • Dedicated Short-Circuit Protection: Individual 2 A, 8AG protective fuses mounted per channel safeguard the module against severe field overcurrent hazards.
  • Visual Status Array: Equipped with nine front-panel diagnostic LEDs providing localized visualization of blown-fuse status and specific channel conduction states.
  • Direct Input Interlocking: Supports zero-potential ground reference looping to directly drive discrete DC input modules, such as the 1771-IB receiver block.
  • Optoelectronic Backplane Protection: Incorporates continuous 1500 Vca (rms) galvanic isolation to prevent destructive external voltage transients from damaging backplane control logic.
  • Mechanical Slot Keying: Backplane socket keying fields restrict module slot alignment, ensuring only matched electrical module types sit within defined wiring nests.

Applications

  • Distributed control of factory floor solenoid-actuated pneumatic manifolds.
  • Direct activation of low-current DC motor speed control enable drives.
  • Remote instrumentation control panels and pilot lamp illumination matrix lines.
  • Inter-rack logic interlocking with low-voltage input hardware sub-assemblies.

Hardware Specifications

Parameter Specification
Manufacturer Allen-Bradley / Rockwell Automation
Model 1771-OB
Product Series PLC-5 / 1771 I/O
Module Type Digital DC Output Driver Module
Outputs Per Module 8
Chassis Compatibility 1771 I/O Chassis
Input Operational Voltage Range 10 Vdc to 27 Vdc
Output Current Capacity 1.5 A per individual output (not to exceed 8 A total per module)
Maximum Current Surge 4 A for 1 ms, repeatable at 1 s intervals
Off-State Leakage Current 1 mA maximum per output
On-State Voltage Drop 2 Vdc maximum
Signal Transmission Delay 10 ms (On to Off and Off to On states)
Power Dissipation 0.9 Watts minimum, 16.9 Watts maximum
Thermal Dissipation 3.0 BTU/h minimum, 57.6 BTU/h maximum
Backplane Logic Current Demand 165 mA @ 5 Vdc plus/minus 5%
Optoelectric Isolation 1500 Vca (rms)
Operating Temperature Range 0 degC to 60 degC
Storage Temperature Range -40 degC to 85 degC
Relative Ambient Humidity 5% to 95% (non-condensing)
Field Wiring Specifications Flexible cable with 1.5 mm2 nominal cross-section
Backplane Plastic Keying Slots Between positions 4 and 6, and between positions 18 and 20
Internal Fusing 2 A, 8AG rating (one individual fuse per output path)
Terminal Connection Block 1771-WA Wiring Arm

Connections/Interfaces

Connector Terminal Pin Function
Terminal A +DC Voltage Supply Input Reference
Terminal 0 Digital Output Channel 0 Signal Line
Terminal 1 Digital Output Channel 1 Signal Line
Terminal 2 Digital Output Channel 2 Signal Line
Terminal 3 Digital Output Channel 3 Signal Line
Terminal 4 Digital Output Channel 4 Signal Line
Terminal 5 Digital Output Channel 5 Signal Line
Terminal 6 Digital Output Channel 6 Signal Line
Terminal 7 Digital Output Channel 7 Signal Line
Terminal B DC Common Ground Return Reference

Engineering Notes

  • Terminal to Bit Discrepancy: The terminal channel designations etched on the physical 1771-WA wiring arm hardware do not directly map to software internal image register data bits. Refer strictly to the system allocation table when building control code.
  • Potential Equalization: When cross-linking an output channel directly into an input processing unit (such as a 1771-IB), a common power supply loop must feed both blocks to tie all reference grounds to an identical voltage potential.
  • Polarity Critical Warning: Correct structural polarity must be maintained on all direct current power terminals. Applying alternating current (AC) power configurations or cross-wiring polarity rails will result in critical module hardware destruction.
  • Backplane Power Balancing: The 165 mA backplane current consumption must be calculated into the aggregate power supply capacity budget of the specific 1771 chassis rack to avoid thermal overloading or backplane dip errors.

Field Guidelines

  • Electrostatic Grounding Procedures: Operators must latch an approved ESD wrist grounding strap to a structural physical ground point or discharge local potentials by touching an earth-grounded steel frame before touching card edges.
  • Plastic Keying Installation: Ensure the chassis backplane keying pegs are properly seated at the factory positions (between pins 4/6 and pins 18/20) to prevent the accidental insertion of mismatched voltage cards.
  • Chassis De-energization: Complete chassis rack power downcycles are required prior to sliding the driver module out of its physical slot to protect operators and prevent inductive backplane transients.
  • Fuse Extraction Protocol: To safely swap a compromised fuse assembly, release the front mechanical swing arm latch, withdraw the board housing, undo the two case retention screws, and replace the spent 2 A, 8AG component inside.

Technical & Procurement FAQ

Q: What specific fuse replacement specification must be used if a channel drops out? A: Each individual output switch is paired with a standard 2 A, 8AG form-factor fuse accessible underneath the card side cover.

Q: Can this DC driver module be safely slotted into the leftmost slot of a 1771 chassis? A: No, the far-left slot of the 1771 chassis configuration is structurally reserved for the master processor module or remote I/O network adapter head.

Q: Does the module display indicators on the front face for individual circuit diagnostics? A: Yes, it features one dedicated red LED for blown fuse notification alongside eight individual red status LEDs that light up when an output channel is actively energized.

Vận chuyển nhanh toàn cầu

  • Giao hàng tiêu chuẩn: 4-6 ngày làm việc qua DHL, FedEx và UPS.
  • Giao hàng nhanh: Giao hàng trong ngày cho đơn đặt hàng có sẵn trong kho trước 2:00 chiều (GMT+8).
  • Phủ sóng toàn cầu: Phục vụ hơn 150 quốc gia, bao gồm giao hàng nhanh đến Saudi Arabia và UAE.

Trả hàng & Bảo hành

  • Đảm bảo 30 ngày: Chấp nhận trả hàng cho sản phẩm có sẵn trong kho với bao bì nguyên bản, niêm phong từ nhà máy.
  • Bảo hành 12 tháng: Mỗi linh kiện công nghiệp đều được bảo hành kỹ thuật chuyên nghiệp.

Đơn hàng được xử lý và giao từ thứ Hai đến thứ Sáu (không bao gồm ngày lễ).


Để biết đầy đủ điều kiện, phí lưu kho và chi tiết trả hàng quốc tế, vui lòng xem trang chính thức của chúng tôi Chính sách Hoàn tiền & Trả hàng .

TECHNICAL SPECIFICATIONS

Color pattern
Đen
Country of origin
Hoa Kỳ
Power source
Nguồn điện DC

Sản phẩm đã xem gần đây

Kiến thức kỹ thuật

Bộ truyền động điện được thiết kế để thay thế hệ thống thủy lực: Hướng dẫn tự động hóa công nghiệp thực tiễn

Bài viết này giải thích cách các bộ truyền động điện tích hợp, như dòng e-Actuator của SMC, đang thay đổi điều khiển chuyển động công nghiệp bằng cách thay thế các hệ thống khí nén và thủy lực truyền...

Các phép toán toán học sử dụng OpenPLC cho các ứng dụng tự động hóa công nghiệp

Bài viết này giải thích cách các hệ thống PLC thực hiện các phép toán cơ bản như cộng, trừ, nhân, chia, modulo và lũy thừa trong tự động hóa công nghiệp. Nó trình bày cách các khối chức năng này...

Logic Boolean Nâng Cao với Lập Trình PLC FBD: Ứng Dụng Công Nghiệp Thực Tiễn Vượt Xa Logic Cơ Bản

Bài viết giải thích một số hàm logic Boolean nâng cao được sử dụng trong lập trình PLC ngoài các phép toán cơ bản AND, OR và NOT. Nó trình bày cách các công cụ như bảng chân trị, bộ chọn đa kênh, bộ...

Logic Boolean trong Lập trình PLC: Hiểu về Cổng Logic FBD

Logic Boolean là nền tảng của mọi chương trình PLC. Từ các điều khiển máy đơn giản đến các hệ thống tự động hóa công nghiệp phức tạp, các cổng logic quyết định cách các bộ điều khiển phản ứng với các...

Hướng Dẫn Chi Tiết Về Tường Lửa Công Nghiệp và Phân Vùng Mạng OT

Tường lửa công nghiệp đóng vai trò quan trọng trong an ninh mạng OT, bảo vệ các mạng PLC, DCS và SCADA thông qua phân đoạn, kiểm soát truy nhập/ra vào và tích hợp IDS/IPS phù hợp với các nguyên tắc...

Hướng dẫn về Càng Robot: Từ Xử lý Nhẹ Nhàng đến Tự động Hóa Công Suất Nặng

Các bộ kẹp robot hiện đại đang phát triển vượt ra ngoài các hàm cơ học truyền thống. Từ hệ thống dính lấy cảm hứng từ tắc kè, bộ kẹp mềm đạt chuẩn thực phẩm đến các công cụ kho hàng được trang bị trí...