1 trong số 1

Bently Nevada 125712-01 4-Channel Relay Module

Bently Nevada 125712-01 4-Channel Relay Module

Only 8 item(s) left in stock
  • Manufacturer: Bently Nevada

  • Product No.: 125712-01

  • Country of origin:Hoa Kỳ

  • Product Type: Relay Modules

  • Payment: T/T, Western Union

  • Weight: 400g

  • Dimensions: 241 mm x 24.4 mm x 99.1 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Số lượng
Xem toàn bộ chi tiết

Description

The 125712-01 is a full-height spare component designed to provide four independent relay outputs within the 3500 Series Machinery Protection System. This module functions by executing highly customizable voting logic directly driven by machine alerts and danger levels across the system enclosure. Each output terminal incorporates specialized Alarm Drive Logic, which can be custom configured with complex AND or OR Boolean expressions using the 3500 Rack Configuration Software to manage specific automated trip signals. It operates reliably when located to the right of the main Rack Interface Module, delivering discrete contact outputs for field control links, emergency stop systems, or external industrial annunciators.

Features

  • Four fully programmable, independent relay outputs supporting complex localized system voting logic.
  • Configurable Alarm Drive Logic utilizing combinational AND/OR gate selections for flexible machine-state actions.
  • Multi-channel compatibility accepting alert and danger alarm inputs from any active monitor card in the local rack.
  • Front-panel visual diagnostics including dedicated LEDs for Module OK, active TX/RX communications, and individual relay state indicators.
  • High-integrity epoxy-sealed relay hardware utilizing pairs of single-pole double-throw (SPDT) relays in a unified double-pole double-throw (DPDT) physical arrangement.
  • Hardware switch-selectable functionality for setting channels to either Normally Energized (NE) or Normally De-energized (NDE) operation.

Applications

  • Mechanical trip systems and emergency shutdown integration.
  • Automated industrial voting logic and alarming systems for large rotating assets.
  • Critical turbomachinery and industrial compressor protective interlocking networks.

Ordering Information

Part Number / Option Description
3500/32-A01-B00 4-Channel Relay Module with I/O Module, No Agency Approvals 
3500/32-A01-B01 4-Channel Relay Module with I/O Module, CSA/NRTL/C Approval 
125712-01 Spare 4-Channel Relay Module (Main Board) 
125720-01 Spare 4-Channel Relay I/O Module 
00580436 Connector Header, Internal Termination, 6-position, Green 

Technical Specifications

Category Specification Data
Electrical Power Consumption 6 watts typical 
  Relay Type Two SPDT relays connected in a DPDT configuration 
  Environmental Sealing Epoxy-sealed 
  Arc Suppressor 250 Vrms, installed as standard 
Contact Ratings Max Switched Current 5 A 
  Max Switched Voltage (dc) 30 Vdc 
  Max Switched Voltage (ac) 250 Vac 
  Max Switched Power (dc) 120 W 
  Max Switched Power (ac) 600 VA 
  Minimum Switched Current 10 mA @ 5 Vdc 
  Contact Life 100,000 cycles @ 5 A, 24 Vdc or 120 Vac 
Environmental Operating Temperature -30 degC to +65 degC (-22 °F to +150 °F) 
  Storage Temperature -40 degC to +85 degC (-40 °F to +185 °F) 
  Humidity 95%, non-condensing 
Mechanical Main Module Dimensions (H x W x D) 241 mm x 24.4 mm x 242 mm (9.50 in x 0.96 in x 9.52 in) 
  Main Module Weight 0.7 kg (1.6 lb.) 
  Rack Space (Main Module) 1 full-height front slot 
  Rack Space (I/O Module) 1 full-height rear slot 
  Manufacturer Bently Nevada 

Connections/Interfaces

Terminal Designation Function
NC Normally Closed contact connection terminal for external equipment loops 
ARM Armature (Common) contact interface terminal for external field wiring 
NO Normally Open contact connection terminal for external equipment loops 
RELAY MODE (Switch) Hardware selector switches for Normally De-energized (NDE) or Normally Energized (NE) mode 

Installation Guidelines

  • Slot Allocation: Position the module in any available full-height slot directly to the right of the 3500 Rack Interface Module.
  • Relay Mode Configuration: Before commissioning, configure individual channel hardware switches located on the module to specify either Normally De-energized (NDE) or Normally Energized (NE) operation based on the field device type.
  • Software Configuration: Use the 3500 Rack Configuration Software to map specific combinations of alert or danger alarms across monitor channels into the module's localized Alarm Drive Logic.

Compliance and Certifications

  • EMC Emissions: EN 55011 Class A (Radiated and Conducted Emissions).
  • EMC Immunity: IEC61000-6-2, EN 61000-4-2 (Electrostatic Discharge Criteria B), ENV 50140 (Radiated Susceptibility Criteria A), ENV 50141 (Conducted Susceptibility Criteria A), EN 61000-4-4 (Electrical Fast Transient Criteria B), EN 61000-4-5 (Surge Capability Criteria B), 61000-4-8 (Magnetic Field Criteria A), EN 61000-4-11 (Voltage Dip Criteria B), ENV 50204 (Radio Telephone Criteria B).
  • Safety Requirements: EN 61010-1 Low Voltage Directives.
  • Hazardous Area Approvals: CSA/NRTL/C; Class I, Div 2, Groups A, B, C, D; T4 @ Ta = -20 degC to +65 condition. Certification Number: CSA 150268-1002151 (LR 26744).

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Bently Nevada 125712-01 4-Channel Relay Module

Can this relay module be used in Triple Modular Redundant configurations?

No. Triple Modular Redundant (TMR) applications require the use of the 3500/34 TMR Relay Module instead of this standard 4-channel version.

What are the contact ratings for resistive loads on these relays?

The maximum ratings are 5 A with a maximum switched voltage of 30 Vdc or 250 Vac. The maximum switched power is 120 W for DC or 600 VA for AC.

How do you program the voting and driving logic for each channel?

The voting logic is configured by setting up AND and OR gates using the 3500 Rack Configuration Software, which pulls alert and danger states from monitor channels.

What do the front-panel TX/RX LEDs indicate?

The TX/RX LED flashes to indicate active and proper communications between this relay module and other modules within the 3500 rack framework.

Vận chuyển nhanh toàn cầu

  • Giao hàng tiêu chuẩn: 4-6 ngày làm việc qua DHL, FedEx và UPS.
  • Giao hàng nhanh: Giao hàng trong ngày cho đơn đặt hàng có sẵn trong kho trước 2:00 chiều (GMT+8).
  • Phủ sóng toàn cầu: Phục vụ hơn 150 quốc gia, bao gồm giao hàng nhanh đến Saudi Arabia và UAE.

Trả hàng & Bảo hành

  • Đảm bảo 30 ngày: Chấp nhận trả hàng cho sản phẩm có sẵn trong kho với bao bì nguyên bản, niêm phong từ nhà máy.
  • Bảo hành 12 tháng: Mỗi linh kiện công nghiệp đều được bảo hành kỹ thuật chuyên nghiệp.

Đơn hàng được xử lý và giao từ thứ Hai đến thứ Sáu (không bao gồm ngày lễ).


Để biết đầy đủ điều kiện, phí lưu kho và chi tiết trả hàng quốc tế, vui lòng xem trang chính thức của chúng tôi Chính sách Hoàn tiền & Trả hàng .

TECHNICAL SPECIFICATIONS

Color pattern
Bạc
Country of origin
Hoa Kỳ

Sản phẩm đã xem gần đây

Kiến thức kỹ thuật

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...