1 trong số 1

Weidmuller 1469520000 PRO ECO 960W 24V 40A Switch-mode Power Supply Unit

Weidmuller 1469520000 PRO ECO 960W 24V 40A Switch-mode Power Supply Unit

Only 10 item(s) left in stock
  • Manufacturer: Weidmuller

  • Product No.: PRO ECO 960W 24V 40A

  • Country of origin:Đức

  • Product Type: DIN Rail Power Supplies

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 160 mm x 125 mm x 120 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Số lượng
Xem toàn bộ chi tiết

Engineered for high-capacity DC power distribution in demanding industrial environments, the Weidmuller 1469520000 (Model: PRO ECO 960W 24V 40A) switch-mode power supply unit delivers a regulated 24 V DC output at up to 40 A. This robust DIN-rail mountable module combines a compact form factor with 93% operational efficiency, minimizing thermal load inside control cabinets and ensuring stable power delivery to PLCs, HMIs, and field actuators.

Key Features

  • High Operational Efficiency: Achieves up to 93% efficiency, significantly reducing energy dissipation and cabinet heat buildup.
  • Wide Input Range: Supports universal AC input from 85 to 264 V AC and DC input from 80 to 370 V DC for global compatibility.
  • Tri-Color LED Diagnostics: Real-time status monitoring via Green (Uoutput > 21.6 V DC), Yellow (Ioutput > 90% rated), and Red (overload, short-circuit, or overtemperature) indicators.
  • Parallel Capability: Supports direct parallel connection of up to 3 units to scale current capacity or establish redundant power architectures.
  • Robust Protection Suite: Integrated varistor surge protection, short-circuit protection, overload protection, and thermal shutdown.

Industrial Applications

  • Factory Automation: Centralized 24 V DC power distribution for PLC racks, I/O drops, and industrial PCs.
  • Process Control Systems: Reliable power source for transmitters, solenoid valves, and safety barriers in continuous process plants.
  • Machine Building: Heavy-duty power supply for packaging, material handling, and CNC machinery control panels.
  • Water and Wastewater: Robust power infrastructure for outdoor telemetry and pump control stations.

Ordering Information

Order Number Type Designation GTIN / EAN Standard Package Qty
1469520000 PRO ECO 960W 24V 40A 4050118275704 1 pc(s).

Technical Specifications

Manufacturer Weidmuller
Series PROeco
Rated Output Voltage 24 V DC ± 1 % (adjustable 22 to 28 V DC via potentiometer)
Continuous Output Current 40 A @ 50 degC / 24 A @ 70 degC
Output Power 960 W
AC Input Voltage Range 85 to 264 V AC (derating required below 100 V AC)
DC Input Voltage Range 80 to 370 V DC (derating required below 120 V DC)
AC Current Consumption 4.6 A @ 230 V AC / 9.9 A @ 110 V AC
Frequency Range AC 47 to 63 Hz
Inrush Current Max. 5 A
Efficiency 93%
Power Loss (Idle / Nominal) 8 W (Idling) / 85 W (Nominal Load)
Connection System Screw connection
Housing Version Metal, corrosion resistant
Operating Temperature -25 degC to 70 degC
Storage Temperature -40 degC to 85 degC
Dimensions (W x H x D) 160 mm x 125 mm x 120 mm
Net Weight 3190 g
Shipping Weight (Calculated) 3.5 kg

Diagnostic LED Status Mapping

LED Color Status / Threshold Operational Meaning
Green Uoutput > 21.6 V DC Normal operation; output voltage within acceptable limits.
Yellow Ioutput > 90% IRated typ. High load warning; output current is approaching maximum capacity.
Red Uoutput < 20.4 V DC Fault condition; overload, overtemperature, short-circuit, or low voltage.

Empirical Engineering Insights

Alternative Models & Compatibility

The PROeco series is designed as a highly space-efficient and cost-effective alternative to Weidmuller's premium PROmax and PROtop series. When replacing older 40 A power supplies, verify the 160 mm width footprint on the TS 35 rail, as high-power units require adequate lateral spacing for heat dissipation.

Application Pitfalls & Engineering Notes

A critical consideration for the PRO ECO 960W is its thermal derating profile. While it delivers a full 40 A at ambient temperatures up to 50 degC, the output capacity derates linearly to 24 A at 70 degC. Operating the unit near its limit in unventilated enclosures will trigger the internal thermal protection, causing output cycling.

Commissioning & Wiring Tips

Due to the high 40 A output current, ensure that output wiring is sized appropriately (minimum 10 AWG / 6 mm² copper wire recommended) to prevent significant voltage drop across the run. When configuring parallel operation for up to 3 units, use a precise digital multimeter to adjust the output voltage of each unit via the front potentiometer to within ±50 mV of each other before tying the outputs together.

Installation Guidelines

CRITICAL WARNING

De-energize all AC and DC power sources before attempting installation, wiring, or maintenance. Ensure the input circuit breaker is locked out. Do not open the metal housing; high residual voltage may remain stored in internal capacitors even after power is disconnected.

1

Snap the unit securely onto a standard TS 35 DIN rail. Ensure the mounting orientation is vertical, with the input terminals at the bottom and output terminals at the top to facilitate natural convection cooling.

2

Maintain a minimum clearance of 50 mm above and below the unit, and 20 mm of lateral clearance from adjacent active heat-producing components.

3

Connect the protective earth (PE) ground terminal first. Wire the AC input (L, N) or DC input terminals using the integrated screw connections, tightening to the manufacturer-specified torque.

4

Connect the 24 V DC load lines to the output terminals, ensuring correct polarity. Energize the input source and verify that the green LED illuminates.

What is the thermal derating behavior of the PRO ECO 960W power supply?

The unit delivers its full rated output of 40 A at ambient temperatures up to 50 degC. Above 50 degC, the output current derates linearly down to 24 A at 70 degC.

Can multiple 1469520000 units be connected in parallel for higher current output?

Yes, up to three units can be connected in parallel to increase current capacity. Ensure the output voltages of all units are calibrated within 50 mV of each other before connection.

What do the three diagnostic LEDs on the front panel indicate?

The Green LED indicates output voltage is above 21.6 V DC. The Yellow LED indicates output current is above 90% of the rated current. The Red LED indicates a fault such as overload, overtemperature, short-circuit, or output voltage below 20.4 V DC.

What are the recommended backup fuses for the input side?

Recommended backup fuses include a 16 A DI safety fuse, a 20 A Character B circuit breaker, or a 16 A Character C circuit breaker.

Vận chuyển nhanh toàn cầu

  • Giao hàng tiêu chuẩn: 4-6 ngày làm việc qua DHL, FedEx và UPS.
  • Giao hàng nhanh: Giao hàng trong ngày cho đơn đặt hàng có sẵn trong kho trước 2:00 chiều (GMT+8).
  • Phủ sóng toàn cầu: Phục vụ hơn 150 quốc gia, bao gồm giao hàng nhanh đến Saudi Arabia và UAE.

Trả hàng & Bảo hành

  • Đảm bảo 30 ngày: Chấp nhận trả hàng cho sản phẩm có sẵn trong kho với bao bì nguyên bản, niêm phong từ nhà máy.
  • Bảo hành 12 tháng: Mỗi linh kiện công nghiệp đều được bảo hành kỹ thuật chuyên nghiệp.

Đơn hàng được xử lý và giao từ thứ Hai đến thứ Sáu (không bao gồm ngày lễ).


Để biết đầy đủ điều kiện, phí lưu kho và chi tiết trả hàng quốc tế, vui lòng xem trang chính thức của chúng tôi Chính sách Hoàn tiền & Trả hàng .

TECHNICAL SPECIFICATIONS

Country of origin
Đức

Sản phẩm đã xem gần đây

Kiến thức kỹ thuật

Bộ truyền động điện được thiết kế để thay thế hệ thống thủy lực: Hướng dẫn tự động hóa công nghiệp thực tiễn

Bài viết này giải thích cách các bộ truyền động điện tích hợp, như dòng e-Actuator của SMC, đang thay đổi điều khiển chuyển động công nghiệp bằng cách thay thế các hệ thống khí nén và thủy lực truyền...

Các phép toán toán học sử dụng OpenPLC cho các ứng dụng tự động hóa công nghiệp

Bài viết này giải thích cách các hệ thống PLC thực hiện các phép toán cơ bản như cộng, trừ, nhân, chia, modulo và lũy thừa trong tự động hóa công nghiệp. Nó trình bày cách các khối chức năng này...

Logic Boolean Nâng Cao với Lập Trình PLC FBD: Ứng Dụng Công Nghiệp Thực Tiễn Vượt Xa Logic Cơ Bản

Bài viết giải thích một số hàm logic Boolean nâng cao được sử dụng trong lập trình PLC ngoài các phép toán cơ bản AND, OR và NOT. Nó trình bày cách các công cụ như bảng chân trị, bộ chọn đa kênh, bộ...

Logic Boolean trong Lập trình PLC: Hiểu về Cổng Logic FBD

Logic Boolean là nền tảng của mọi chương trình PLC. Từ các điều khiển máy đơn giản đến các hệ thống tự động hóa công nghiệp phức tạp, các cổng logic quyết định cách các bộ điều khiển phản ứng với các...

Hướng Dẫn Chi Tiết Về Tường Lửa Công Nghiệp và Phân Vùng Mạng OT

Tường lửa công nghiệp đóng vai trò quan trọng trong an ninh mạng OT, bảo vệ các mạng PLC, DCS và SCADA thông qua phân đoạn, kiểm soát truy nhập/ra vào và tích hợp IDS/IPS phù hợp với các nguyên tắc...

Hướng dẫn về Càng Robot: Từ Xử lý Nhẹ Nhàng đến Tự động Hóa Công Suất Nặng

Các bộ kẹp robot hiện đại đang phát triển vượt ra ngoài các hàm cơ học truyền thống. Từ hệ thống dính lấy cảm hứng từ tắc kè, bộ kẹp mềm đạt chuẩn thực phẩm đến các công cụ kho hàng được trang bị trí...