1 trong số 1

Weidmuller 8965360000 ACT20X-HDI-SDO-S Isolating Switch Amplifier

Weidmuller 8965360000 ACT20X-HDI-SDO-S Isolating Switch Amplifier

Only 10 item(s) left in stock
  • Manufacturer: Weidmuller

  • Product No.: 8965360000

  • Country of origin:Đức

  • Product Type: Isolating Switch Amplifiers

  • Payment: T/T, Western Union

  • Weight: 1200g

  • Dimensions: 117.2 mm x 22.5 mm x 113.6 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Số lượng
Xem toàn bộ chi tiết

Processing digital signals from hazardous areas requires robust galvanic isolation, which the Weidmuller 8965360000 ACT20X-HDI-SDO-S delivers as a high-performance, 2-channel isolating switch amplifier. This device safely transmits switching states from NAMUR sensors or mechanical contacts located in Zone 0, 1, or 2 hazardous areas to the safe area control system, providing complete electrical separation and signal conditioning in a compact form factor.

Key Features

  • Dual-channel intrinsically safe input for NAMUR sensors or dry mechanical contacts.
  • Galvanic 4-way isolation between input, output, power supply, and status output.
  • Integrated line fault detection (LFD) for continuous wire-break and short-circuit monitoring.
  • FDT/DTM software-configurable parameters for custom application tuning and diagnostics.
  • Relay outputs (1 changeover contact per channel) for robust load switching.
  • Compact 22.5 mm DIN-rail housing to optimize cabinet space.

Applications

  • Intrinsically safe signal isolation in chemical and petrochemical processing plants.
  • Oil and gas pipeline monitoring systems requiring Zone 0/1 sensor deployment.
  • Water and wastewater treatment facility telemetry and pump control.
  • Hazardous area valve position feedback and limit switch integration.

Technical Specifications

Parameter Value
Manufacturer Weidmuller
Article Number 8965360000
Model ACT20X-HDI-SDO-S
Number of Channels 2
Input Type NAMUR sensor (DIN EN 60947-5-6) or mechanical switch
Output Type Relay (1 changeover contact per channel)
Nominal Switching Voltage 250 V AC / 30 V DC
Supply Voltage 19.2 to 31.2 V DC
Power Consumption <= 1.1 W
Isolation Voltage 2.6 kV AC (input / output / power)
Connection Technology Screw connection
Clamping Range 0.5 to 2.5 mm2
Flammability Rating UL 94 V-0
Protection Degree IP20
Operating Temperature -20 to +60 degC
Dimensions (H x W x D) 117.2 mm x 22.5 mm x 113.6 mm
Net Weight 0.170 kg

Connections and Interfaces

Terminal Pin Function / Circuit Assignment
11 / 12 Channel 1 Input (NAMUR Sensor / Mechanical Switch)
21 / 22 Channel 2 Input (NAMUR Sensor / Mechanical Switch)
51 / 52 / 53 Channel 1 Relay Output (NC / COM / NO)
61 / 62 / 63 Channel 2 Relay Output (NC / COM / NO)
91 / 92 Power Supply (19.2 to 31.2 V DC: + / -)

Alternative Models & Compatibility

The ACT20X-HDI-SDO-S is part of Weidmuller's premium ACT20X signal converter family. It serves as a direct replacement or upgrade path for legacy ACT20 series modules. When migrating from older systems, verify that your configuration files are updated in the FDT/DTM frame to match the specific firmware revision of the 8965360000 module.

Application Pitfalls & Engineering Notes

When utilizing standard mechanical switches instead of NAMUR sensors, the Line Fault Detection (LFD) circuit must be configured correctly. If LFD is enabled without external resistors, the module will interpret an open switch as a wire break and a closed switch as a short circuit. To prevent false diagnostics, either disable LFD via the DTM software or wire a resistor network (typically 1k Ohm in series and 10k Ohm in parallel) directly at the switch contacts.

Commissioning & Wiring Tips

Configuration is performed using the Weidmuller WI-Manager software via the front-panel service jack. Ensure the CBX200 USB interface cable is used for connection. For field wiring, maintain a minimum physical separation of 50 mm between the intrinsically safe (Ex i) blue terminals on the left side and the non-intrinsically safe terminals on the right side to comply with international hazardous area installation standards.

Installation Guidelines

CRITICAL WARNING

De-energize all power sources before mounting, wiring, or configuring the device. Failure to isolate power can result in electrical shock or spark generation in hazardous areas, compromising explosion protection safety.

1
Snap the module vertically onto a standard TS 35 DIN rail, ensuring the metal grounding spring on the back makes secure contact with the rail.
2
Connect the intrinsically safe field sensors to the blue terminals (11/12 and 21/22), ensuring proper cable routing away from power lines.
3
Wire the relay outputs and the 24 V DC power supply to the black terminals on the opposite side of the module.
4
Connect the configuration interface to set the desired input/output logic and LFD parameters using the FDT/DTM software before commissioning.

How do I configure the Line Fault Detection (LFD) for a standard mechanical switch?

To use LFD with a mechanical switch, you must wire an external resistor network at the switch contacts: a 1k Ohm resistor in series and a 10k Ohm resistor in parallel. Alternatively, you can disable LFD entirely using the Weidmuller FDT/DTM software.

What software is required to configure the ACT20X-HDI-SDO-S?

Configuration requires the Weidmuller WI-Manager software (FDT frame) along with the device-specific ACT20X DTM package and a CBX200 USB interface cable.

Can this isolating amplifier be installed directly in Zone 0?

No, the module itself must be installed in a safe area or Zone 2 (inside a suitable protective enclosure). However, its input circuits are certified intrinsically safe for direct connection to devices located in Zone 0, 1, or 2.

Vận chuyển nhanh toàn cầu

  • Giao hàng tiêu chuẩn: 4-6 ngày làm việc qua DHL, FedEx và UPS.
  • Giao hàng nhanh: Giao hàng trong ngày cho đơn đặt hàng có sẵn trong kho trước 2:00 chiều (GMT+8).
  • Phủ sóng toàn cầu: Phục vụ hơn 150 quốc gia, bao gồm giao hàng nhanh đến Saudi Arabia và UAE.

Trả hàng & Bảo hành

  • Đảm bảo 30 ngày: Chấp nhận trả hàng cho sản phẩm có sẵn trong kho với bao bì nguyên bản, niêm phong từ nhà máy.
  • Bảo hành 12 tháng: Mỗi linh kiện công nghiệp đều được bảo hành kỹ thuật chuyên nghiệp.

Đơn hàng được xử lý và giao từ thứ Hai đến thứ Sáu (không bao gồm ngày lễ).


Để biết đầy đủ điều kiện, phí lưu kho và chi tiết trả hàng quốc tế, vui lòng xem trang chính thức của chúng tôi Chính sách Hoàn tiền & Trả hàng .

TECHNICAL SPECIFICATIONS

Country of origin
Đức

Sản phẩm đã xem gần đây

Kiến thức kỹ thuật

Bộ truyền động điện được thiết kế để thay thế hệ thống thủy lực: Hướng dẫn tự động hóa công nghiệp thực tiễn

Bài viết này giải thích cách các bộ truyền động điện tích hợp, như dòng e-Actuator của SMC, đang thay đổi điều khiển chuyển động công nghiệp bằng cách thay thế các hệ thống khí nén và thủy lực truyền...

Các phép toán toán học sử dụng OpenPLC cho các ứng dụng tự động hóa công nghiệp

Bài viết này giải thích cách các hệ thống PLC thực hiện các phép toán cơ bản như cộng, trừ, nhân, chia, modulo và lũy thừa trong tự động hóa công nghiệp. Nó trình bày cách các khối chức năng này...

Logic Boolean Nâng Cao với Lập Trình PLC FBD: Ứng Dụng Công Nghiệp Thực Tiễn Vượt Xa Logic Cơ Bản

Bài viết giải thích một số hàm logic Boolean nâng cao được sử dụng trong lập trình PLC ngoài các phép toán cơ bản AND, OR và NOT. Nó trình bày cách các công cụ như bảng chân trị, bộ chọn đa kênh, bộ...

Logic Boolean trong Lập trình PLC: Hiểu về Cổng Logic FBD

Logic Boolean là nền tảng của mọi chương trình PLC. Từ các điều khiển máy đơn giản đến các hệ thống tự động hóa công nghiệp phức tạp, các cổng logic quyết định cách các bộ điều khiển phản ứng với các...

Hướng Dẫn Chi Tiết Về Tường Lửa Công Nghiệp và Phân Vùng Mạng OT

Tường lửa công nghiệp đóng vai trò quan trọng trong an ninh mạng OT, bảo vệ các mạng PLC, DCS và SCADA thông qua phân đoạn, kiểm soát truy nhập/ra vào và tích hợp IDS/IPS phù hợp với các nguyên tắc...

Hướng dẫn về Càng Robot: Từ Xử lý Nhẹ Nhàng đến Tự động Hóa Công Suất Nặng

Các bộ kẹp robot hiện đại đang phát triển vượt ra ngoài các hàm cơ học truyền thống. Từ hệ thống dính lấy cảm hứng từ tắc kè, bộ kẹp mềm đạt chuẩn thực phẩm đến các công cụ kho hàng được trang bị trí...