1 z 1

Honeywell LG1093AC01 Gas Turbine LG Flame Detector

Honeywell LG1093AC01 Gas Turbine LG Flame Detector

Only 1 item(s) left in stock
  • Manufacturer: Honeywell

  • Product No.: LG1093AC01

  • Country of origin:United States

  • Product Type: Flame Detector

  • Payment: T/T, Western Union

  • Weight: 910g

  • Dimensions: 15 x 15 x 10 cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Množství
Zobrazit veškeré podrobnosti

Description

The Honeywell LG1093AC01 is a ultraviolet (UV) radiation flame detector engineered for gas turbine flame monitoring systems. The unit senses the UV radiation emitted by a hydrocarbon flame and transmits a high-speed signal to indicate a flame or no-flame condition. Utilizing a Geiger Mueller-type phototube sensor, the detector is solar blind and tolerant to black body radiation. It is widely applied across General Electric and GE licensee gas turbines for power generation and compressor operations, delivering high sensitivity with typical response times of 0.1 seconds for flame presence.

Features

  • Geiger Mueller-type sensor phototube detecting UV radiation in the 180 to 260 nm spectral range
  • Solar blind design tolerant to black body radiation
  • High sensitivity with typical 0.1-second Flame Present Response Time and 0.2-second maximum Flame Loss Response Time
  • Two-year shelf life and 10,000-hour MTBF
  • Long-distance sensor-to-amplifier signal transmission capability up to 330 m (1000 ft)
  • Sealed viewing window rated for pressures up to 428 mbar (6.3 psi)
  • Integrated 9 ft (2.7 m) 2-conductor armored cable

Applications

  • General Electric (and GE licensee) heavy-duty gas turbines
  • Power generation gas turbine flame monitoring
  • Industrial compressor gas turbine installations

Technical Specifications

Parameter Specification
Manufacturer Honeywell
Product No. LG1093AC01
Product Type LG Flame Detector
Sensor Type Geiger Mueller-type phototube
Spectral Range 180 to 260 nm
Operating Temperature Range -40 to 176 degC
Cable Length 9 ft (2.7 m)
Cable Type 2-conductor armored cable
Flange Dimensions 1.73 in. O.D. by 0.14 in. wide flange
Viewing Window Pressure Rating 428 mbar (6.3 psi)
Supply Voltage Required No
Flame Present Response Time 0.1 sec typical
Flame Loss Response Time 0.2 sec max
MTBF 10,000 h
Max Operating Distance Up to 330 m (1000 ft) from sensor to amplifier
Hardware Output Compatibility EG1033 series amplifier modules only
Weight 0.91 kg

Installation Guidelines

  • Amplifier Compatibility: Hardware outputs are designed exclusively for connection to Honeywell EG1033 series amplifier modules (EG1033AA, EG1033AB, EG1033AC).
  • Wiring and Distance: Ensure proper routing of the attached 2-conductor armored cable. Sensor-to-amplifier runs can extend up to 330 m (1000 ft).
  • Pressure Rating: Verify that process conditions at the viewing interface do not exceed the window rating of 428 mbar (6.3 psi).
  • Hazardous Area Mounting: Observe all local codes and area classification constraints when mounting in classified explosive environments.
  • Low-NOx Exception Note: Standard LG1093 series detectors may not function as expected on GE/NP DLE (Dry Low NOx) gas turbines; these applications require specialized pre-selected variants.

Compliance and Certifications

  • CE / ATEX: EEx d IIA T3 or EEx d IIC T3, Zone 1 and 2 (Directive 94/9/EC, EMC 89/336/EEC, LVD 73/23/EEC)
  • Factory Mutual (FM): Class I, Div 1 and 2, Groups B, C, and D
Key Features:

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell LG1093AC01 Gas Turbine LG Flame Detector

What spectral range does the flame sensor detect?

The sensor phototube detects ultraviolet radiation within the 180 to 260 nm spectrum.

Which amplifier modules are compatible with this detector?

The hardware outputs are compatible exclusively with Honeywell EG1033 series amplifier modules, such as EG1033AA, EG1033AB, and EG1033AC.

What is the typical response time for flame detection?

The detector provides a typical Flame Present Response Time of 0.1 seconds and a maximum Flame Loss Response Time of 0.2 seconds.

Can this detector be used on GE DLE gas turbines?

Standard LG1093 series flame detectors may not operate as expected on GE/NP DLE (Low-NOx) turbines, which require specialized pre-selected units.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Recently Viewed Products

Technical knowledge

Modernizace HMI Bailey INFI 90 Symphony běžících na OpenVMS Alpha

Praktický průvodce výměnou zastaralých operátorských stanic Bailey Symphony běžících na OpenVMS Alpha. Porovnává emulaci Alpha, migraci OpenVMS na x86, přemostění OPC a postupnou modernizaci ABB.

Proč jsou údaje o údržbě nezbytné pro průmyslovou spolehlivost

Údaje o údržbě propojují pracovní příkazy, signály ze senzorů, historii majetku, náklady a znalosti techniků. Správné využití těchto dat zlepšuje plánování, spolehlivost, prediktivní údržbu, kontrolu...

Elektrické pohony navržené jako náhrada hydraulických systémů: Praktická příručka průmyslové automatizace

Tento článek vysvětluje, jak integrované elektrické pohony, jako je řada e-Actuator od SMC, mění průmyslové řízení pohybu nahrazením tradičních pneumatických a hydraulických systémů. Zdůrazňuje...

Matematické operace pomocí OpenPLC pro průmyslové automatizační aplikace

Tento článek vysvětluje, jak PLC systémy provádějí základní matematické operace, jako jsou sčítání, odčítání, násobení, dělení, modulo a umocňování v rámci průmyslové automatizace. Ukazuje, jak tyto...

Pokročilá Booleovská logika s programováním FBD PLC: Praktické průmyslové aplikace nad rámec základní logiky

Článek vysvětluje několik pokročilých funkcí Booleovy logiky používaných v programování PLC nad rámec základních operací AND, OR a NOT. Popisuje, jak se v diagramu funkčních bloků (FBD) využívají...

Booleovská logika v programování PLC: Pochopení logických bran FBD

Booleovská logika je základem každého programu PLC. Od jednoduchých ovládání strojů až po složité průmyslové automatizační systémy určují logické hradla, jak řadiče reagují na měnící se vstupy a...