1 z 3

Woodward 9907-963 DLE Smart Pressure Transducer Manifold Assembly

Woodward 9907-963 DLE Smart Pressure Transducer Manifold Assembly

Only 1 item(s) left in stock
  • Manufacturer: Woodward

  • Product No.: 9907-963

  • Country of origin:United States

  • Product Type: Pressure Transducers

  • Payment: T/T, Western Union

  • Weight: 1500g

  • Shipping port: Xiamen

  • Warranty: 12 months

Množství
Zobrazit veškeré podrobnosti

Description

The Woodward 9907-963 DLE Smart Pressure Transducer Manifold Assembly is a high-precision pressure measurement device designed for dry low emissions (DLE) turbine control systems and industrial turbomachinery. It houses multiple internal pressure transducers on a central motherboard within an aluminum manifold housing, providing precise pressure monitoring and real-time data transmission to electronic control platforms such as MicroNet, NetCon, or Atlas.

The Woodward 9907-963 communicates with system controller interface modules or Field Termination Modules (FTM) using standard universal asynchronous receiver transmitter (UART) protocol over RS-422 differential signaling at 375 Kbaud. Power and communication lines are routed through integrated flying leads that pass through capacitive feed-through filter assemblies to suppress electrical noise picked up from field wiring.

Features

  • Integrates multiple smart pressure transducers inside a single rugged manifold assembly.
  • Employs RS-422 high-speed UART digital communication operating at 375 Kbaud.
  • Features high-precision pressure measurement accuracy of +/-0.047% of full scale across operating temperature ranges.
  • Includes internal capacitive feed-through filters on flying lead connections to attenuate external electrical noise.
  • Designed for remote installation up to 300 m (1000 ft) away from the field termination module.
  • Maintains fast dynamic response with a 20 Hz frequency response and 6 ms latency.

Applications

  • Dry Low Emissions (DLE) gas turbine fuel and combustion control systems.
  • Industrial turbomachinery monitoring and control platforms.
  • MicroNet, NetCon, and Atlas electronic turbine control system architectures.
  • High-accuracy industrial process pressure monitoring.

Technical Specifications

Parameter Value
Manufacturer Woodward
Model 9907-963
Housing Material Aluminum
Accuracy +/-0.047% of full scale (0 to 1000 psia / 0 to 69.0 bar) over operating temperature range
Resolution 16 bits (0.015 psi / 0.103 kPa)
Power Consumption 2.25 W maximum per transducer
Communications Protocol RS-422, @ 375 Kbaud (UART)
Response 20 Hz frequency response with 6 ms latency
Overpressure Limit 1500 psia / 103 bar (1.5 times rated pressure)
Communication Wiring Controlled impedance, low capacitance shielded wire
Power Wiring (One Pair) 20 AWG / 0.5 mm2 min if < 150 m (500 ft); 16 AWG / 1.0 mm2 min if < 300 m (1000 ft)
Power Wiring (Two Pair) 20 AWG / 0.5 mm2 min if < 300 m (1000 ft)
Pressure Fittings Flareless compression fittings for 1/4 inch stainless tubing
Operating Temperature Range (1) -40 to +125 degC (-40 to 257 degF) at 750 psia / 51.7 bar max
Operating Temperature Range (2) -35 to +125 degC (-31 to 257 degF) at 1000 psia / 69.0 bar max
Max Storage Temperature +150 degC (+302 degF)
Dimensions (H x W x D) 121.69 mm x 155.55 mm x 135.79 mm (5.346 in. x 6.124 in. x 4.791 in.)
Weight 3.9 kg (8.5 lb)
Shock Resistance US MIL-STD-810C, Figure 515.2-1 procedure 1 (20 g, 11 ms sawtooth)
Vibration Resistance US MIL-STD-810C, Figure 514.2-2 Curve J (5 g, 2 kHz) with at least a four-point mount

Connections/Interfaces

Wire / Lead Description Function
15 VDC (red) Positive 15 V Power Supply
15 GND (black) Power Supply Ground (0 V)
REC + (white) Receive Data Signal Positive
REC - (black) Receive Data Signal Negative
SHIELD Communication Shield Termination
XMIT + (white) Transmit Data Signal Positive
XMIT - (black) Transmit Data Signal Negative
SAFETY GROUND (green/yellow) Chassis / Earth Ground Connection

Installation Guidelines

  • Mount the manifold assembly in an orientation that allows condensation to drain away from the pressure inlet ports.
  • Ensure pressure tubing leading from the fluid source contains no low points where condensation or contaminants can accumulate.
  • Keep tubing length between the pressure source and the manifold assembly to 2.4 m (8 ft) or less for DLE system applications.
  • Tighten 1/4 inch Swagelok stainless steel fittings hand-tight, then rotate 1 to 1-1/4 turns with a wrench to seal the ferrule onto the tubing.
  • Apply a cover bolt torque of 9.2 N-m (81 lb-in) on flameproof / Zone 1 enclosures to guarantee complete enclosure sealing.
  • Power input must be supplied from an isolated Class 2 power source exhibiting less than 5000 pF total capacitance from output to earth/chassis.
  • For Class I, Division 1 or Zone 1 applications, install a conduit seal within 457 mm (18 inches) or 50 mm (2 inches) of the conduit entry, respectively.

Compliance and Certifications

  • CSA: Certified for Class I, Division 1, Groups C & D, and Class I, Division 2, Groups B, C, & D, T4 at 125 degC Ambient (Canada and USA). Certificate 1006295 (LR79726-5).
  • ATEX Directive 2014/34/EU: Category 2, Group IIG, Ex db IIB T4 Gb (TÜV 12 ATEX 7245 X).
  • UKEX: S.I. 2016 No. 1107, Certificate TÜV 22UKEX7110X (Ex db IIB T4 Gb).
  • IECEx: Certified IECEx TUR 11.0012X Ex db IIB T4 Gb.
  • EMC Directives: Declared to Directive 2014/30/EU and UK S.I. 2016 No. 1091 (EN 61000-6-2, EN 61000-6-4).
  • Single Sealing: Tested per ANSI/ISA 12.27.01 Single Sealing requirements (CSA test report 16584-701103164).
  • Machinery Directive: Compliant as partly completed machinery per Directive 2006/42/EC and UK S.I. 2008 No. 1597.
  • Pressure Equipment Directive: Compliant as SEP per Article 3.3 to Directive 2014/68/EU.
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Woodward 9907-963 DLE Smart Pressure Transducer Manifold Assembly

What communication protocol does the device use?

The device uses standard universal asynchronous receiver transmitter (UART) protocol over RS-422 differential signaling at 375 Kbaud.

What is the pressure measurement accuracy of the transducer assembly?

The pressure accuracy is +/-0.047% of full scale across the operating temperature range.

What is the maximum overpressure limit for the module?

The overpressure limit is 1500 psia (103 bar), which corresponds to 1.5 times the rated pressure.

What power supply specifications are required to operate the unit?

The unit requires a 15 VDC isolated power source complying with NEC or CEC Class 2 requirements, with total output-to-earth capacitance under 5000 pF.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Recently Viewed Products

Technical knowledge

Modernizace HMI Bailey INFI 90 Symphony běžících na OpenVMS Alpha

Praktický průvodce výměnou zastaralých operátorských stanic Bailey Symphony běžících na OpenVMS Alpha. Porovnává emulaci Alpha, migraci OpenVMS na x86, přemostění OPC a postupnou modernizaci ABB.

Proč jsou údaje o údržbě nezbytné pro průmyslovou spolehlivost

Údaje o údržbě propojují pracovní příkazy, signály ze senzorů, historii majetku, náklady a znalosti techniků. Správné využití těchto dat zlepšuje plánování, spolehlivost, prediktivní údržbu, kontrolu...

Elektrické pohony navržené jako náhrada hydraulických systémů: Praktická příručka průmyslové automatizace

Tento článek vysvětluje, jak integrované elektrické pohony, jako je řada e-Actuator od SMC, mění průmyslové řízení pohybu nahrazením tradičních pneumatických a hydraulických systémů. Zdůrazňuje...

Matematické operace pomocí OpenPLC pro průmyslové automatizační aplikace

Tento článek vysvětluje, jak PLC systémy provádějí základní matematické operace, jako jsou sčítání, odčítání, násobení, dělení, modulo a umocňování v rámci průmyslové automatizace. Ukazuje, jak tyto...

Pokročilá Booleovská logika s programováním FBD PLC: Praktické průmyslové aplikace nad rámec základní logiky

Článek vysvětluje několik pokročilých funkcí Booleovy logiky používaných v programování PLC nad rámec základních operací AND, OR a NOT. Popisuje, jak se v diagramu funkčních bloků (FBD) využívají...

Booleovská logika v programování PLC: Pochopení logických bran FBD

Booleovská logika je základem každého programu PLC. Od jednoduchých ovládání strojů až po složité průmyslové automatizační systémy určují logické hradla, jak řadiče reagují na měnící se vstupy a...