Description

Designed for reliable industrial fieldbus integration, the Beckhoff BK8000 Bus Coupler links modular Beckhoff Bus Terminals directly to RS485 network architectures. This interface module processes up to 512 digital input/output channels and 256 analog input/output channels, translating physical peripheral signals into the open, documented RS485 serial communication protocol. System parameters and node addressing are easily set up using the KS2000 configuration software, ensuring seamless commissioning and diagnostics.

The BK8000 acts as the central decentralized head station, managing the internal K-bus system and distributing power to downstream terminal slices. With integrated galvanic isolation separating the fieldbus connection, the internal electronic components, and the 24 V DC power contacts, this bus coupler delivers excellent noise immunity and operational stability in demanding electrical environments.

Features

  • Efficient connection of up to 64 local Beckhoff Bus Terminals to an RS485 fieldbus network.
  • Direct configuration and advanced diagnostic mapping via the KS2000 software interface.
  • Galvanic isolation up to 500 V between power contacts, internal supply voltage, and the fieldbus interface.
  • Integrated power supply terminal designed to supply the internal K-bus with up to 1750 mA.
  • Support for standard serial transfer media via screened, twisted-pair copper cabling.

Applications

  • Industrial process automation and distributed control systems (DCS).
  • HVAC and building automation networks utilizing RS485 multidrop configurations.
  • Machine building and production lines requiring decentralized input/output blocks.
  • Energy management and remote telemetry systems.

Technical Specifications

Manufacturer BECKHOFF
Model / Part Number BK8000
Protocol Open, documented protocol
Bus Interface RS485 D-sub
Data Transfer Rates 9.6 kbaud, 19.2 kbaud, 38.4 kbaud
Max. Number of Bus Terminals 64
Max. Number of Fieldbus Bytes 512 byte input / 512 byte output
Digital Peripheral Signals 512 inputs / outputs
Analog Peripheral Signals 256 inputs / outputs
Power Supply 24 V DC (-15 % / +20 %)
Input Current 70 mA + (total K-bus current) / 4 (Max. 500 mA)
Starting Current 2.5 x continuous current
Recommended Fuse ≤ 10 A
K-Bus Current Supply 1750 mA
Power Contacts Max. 24 V DC / Max. 10 A
Electrical Isolation 500 V (power contact / supply voltage / fieldbus)
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Relative Humidity 95 %, non-condensing
Vibration / Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity / Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Protection Rating IP20
Installation Position Variable
Weight Approx. 170 g

Installation Guidelines

  • Mounting: Install on standard 35 mm DIN rail (EN 60715) in a clean, dry control cabinet. The installation position is variable, but vertical alignment is recommended for optimal convection cooling.
  • Wiring: Always use shielded, twisted-pair copper cables (recommended cross-section: 2 x 0.25 mm²) for the RS485 communication line to prevent electromagnetic interference.
  • Grounding: Ensure the DIN rail and the PE (protective earth) connection points are bonded to a low-impedance ground plane.
  • K-bus Protection: Ensure the total current consumption of connected Bus Terminals does not exceed the maximum K-bus current supply of 1750 mA. Install a power feed terminal if current requirements exceed this limit.

Compliance and Certifications

  • CE: Yes
  • UL: Yes
  • ATEX Markings: II 3 G Ex ec IIC T4 Gc
  • IECEx Markings: Ex ec IIC T4 Gc
  • Marine Approval: DNV GL
Loading product navigation…

What is the maximum number of Bus Terminals that can be connected to the BK8000?

The BK8000 RS485 Bus Coupler supports up to 64 local Bus Terminals.

How is the Beckhoff BK8000 configured?

Configuration and diagnostic parameterization are performed using the Beckhoff KS2000 software tool.

What data transfer rates does the BK8000 support?

The module supports data transfer rates of 9.6 kbaud, 19.2 kbaud, and 38.4 kbaud.

What is the maximum current capacity supplied to the K-bus?

The BK8000 supplies a maximum internal K-bus current of 1750 mA to power the connected terminal slices.

Is the BK8000 certified for use in hazardous areas?

Yes, the BK8000 carries ATEX (II 3 G Ex ec IIC T4 Gc) and IECEx certifications for Zone 2 hazardous environments.

Globaler Expressversand

  • Standardlieferung: 4-6 Werktage via DHL, FedEx und UPS.
  • Expressversand: Versand am selben Tag für vorrätige Bestellungen, die vor 14:00 Uhr (GMT+8) aufgegeben werden.
  • Weltweite Abdeckung: Wir bedienen über 150 Länder, einschließlich schneller Lieferung nach Saudi-Arabien und in die VAE.

Rückgaben & Garantie

  • 30-Tage-Garantie: Rückgaben werden für vorrätige Produkte in originaler, werkversiegelter Verpackung akzeptiert.
  • 12-Monats-Garantie: Jede Industriekomponente ist durch unsere professionelle technische Garantie abgesichert.

Bestellungen werden Montag bis Freitag bearbeitet und geliefert (außer an Feiertagen).


Für vollständige Anspruchsvoraussetzungen, Wiedereinlagerungsgebühren und internationale Rückgabedetails, sehen Sie bitte unsere offizielle Seite ein Rückerstattungs- & Rückgabebedingungen .

TECHNICAL SPECIFICATIONS

Country of origin
Deutschland

Kürzlich angesehene Produkte

Technisches Wissen

Elektrische Antriebe als Ersatz für Flüssigkeiten: Praktisches Tutorial

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Mathematische Operationen mit OpenPLC für industrielle Automatisierungsanwendungen

Dieser Artikel erklärt, wie SPS-Systeme grundlegende mathematische Operationen wie Addition, Subtraktion, Multiplikation, Division, Modulo und Exponentiation in der industriellen Automatisierung...

Fortgeschrittene Boolesche Logik mit FBD-SPS-Programmierung: Praktische industrielle Anwendungen über die Grundlogik hinaus

Der Artikel erklärt mehrere erweiterte Boolesche Logikfunktionen, die in der SPS-Programmierung über die grundlegenden AND-, OR- und NOT-Operationen hinaus verwendet werden. Er behandelt, wie...

Boolesche Logik in der SPS-Programmierung: Verständnis von FBD-Logikgattern

Boolesche Logik ist die Grundlage jedes SPS-Programms. Von einfachen Maschinensteuerungen bis hin zu komplexen industriellen Automatisierungssystemen bestimmen Logikgatter, wie Steuerungen auf sich...

Umfassender Leitfaden zu industriellen Firewalls und OT-Netzwerksegmentierung

Industrielle Firewalls spielen eine entscheidende Rolle in der OT-Cybersicherheit, indem sie SPS-, DCS- und SCADA-Netzwerke durch Segmentierung, Ein- und Ausgangskontrolle sowie IDS/IPS-Integration...

Leitfaden für Roboter-Greifer: Von der schonenden Handhabung bis zur Schwerlastautomatisierung

Moderne robotische Greifer entwickeln sich über traditionelle mechanische Greifbacken hinaus. Von gecko-inspirierten Haftsystemen und weichen, lebensmittelechten Greifern bis hin zu KI-gestützten...