1 von 1

Beckhoff IP2310-B810 Fieldbus Box 4-Channel Digital Input/Output Module

Beckhoff IP2310-B810 Fieldbus Box 4-Channel Digital Input/Output Module

Nur noch 10 Artikel auf Lager verfügbar
  • Hersteller: BECKHOFF

  • Produkt-Nr.: IP2310-B810

  • Herkunftsland:Deutschland

  • Produkttyp: Fieldbus I/O Modules

  • Zahlung: T/T, Western Union

  • Gewicht: 1000g

  • Abmessungen: 30 mm x 175 mm x 26.5 mm

  • Versandhafen: Xiamen

  • Garantie: 12 Monate

Menge
Vollständige Details anzeigen

Description

Decentralized field acquisition and control is handled directly at the machine level by the Beckhoff IP2310-B810 Fieldbus Box. This robust IP67-rated module integrates four digital inputs and four digital outputs into a single compact device, operating via a serial peer-to-peer connection. Designed to withstand harsh industrial environments without requiring an additional protective enclosure, it communicates using an open, documented protocol with support for variable baud rates up to 38.4 kbaud. System parameters and I/O status can be configured and diagnosed seamlessly using the KS2000 software package.

Key Features

  • Direct Field Integration: Fully sealed PA6 polyamide housing providing IP65, IP66, and IP67 protection ratings.
  • Mixed I/O Configuration: Equipped with 4 digital inputs (0.2 ms filter time) and 4 digital outputs (0.5 A per channel).
  • Serial Peer-to-Peer Bus Link: Reliable data transfer via shielded copper cabling up to a distance of 15 meters.
  • Short-Circuit Protection: Sensor supplies and individual output channels feature independent short-circuit protection.
  • Standardized Connections: Employs industry-standard M8 and M12 connections for fieldbus and auxiliary power lines, alongside 8 mm snap-type I/O ports.

Applications

  • Decentralized material handling and conveyor automation.
  • On-machine sensor and actuator concentration in automotive assembly lines.
  • Packaging machinery operating in wet, wash-down, or high-vibration zones.
  • Distributed pneumatic valve control terminals.

Technical Specifications

Manufacturer Beckhoff
Model / Article Number IP2310-B810
Number of Channels 4 digital inputs + 4 digital outputs
Bus Interface 1 x M12 socket, 5-pin, B-coded
Data Transfer Rates 9.6 kbaud, 19.2 kbaud, 38.4 kbaud (default)
Input Filter Time 0.2 ms
"0" Signal Voltage -3 to +5 V
"1" Signal Voltage 11 to 30 V (6 mA input current, EN 61131-2, type 2)
Rated Load Voltage 24 V DC (-15% / +20%)
Max. Output Current 0.5 A per channel (individually short-circuit proof)
Power Supply Input 24 V DC (-15% / +20%)
Box Supply Current 45 mA + sensor current (max. 0.5 A)
Electrical Isolation Control voltage/fieldbus: Yes
Housing Material PA6 (Polyamide)
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Dimensions (W x H x D) 30 mm x 175 mm x 26.5 mm
Weight 210 g
Shipping Weight (Calculated) 1.0 kg
Country of Origin Germany

Connections and Interfaces

Port Reference Connector Type Functional Assignment
Bus Interface M12 socket, 5-pin, B-coded Serial communication link (open protocol)
Power Supply Feed M8 male socket, 4-pin Control voltage (Us) and load voltage (Up) input
Downstream Power M8 female socket, 4-pin Power pass-through to subsequent Fieldbus Boxes
Digital Inputs (I1 to I4) 8 mm snap-type connection 24 V DC sensors with 0.2 ms signal filtration
Digital Outputs (O1 to O4) 8 mm snap-type connection Actuators, solenoid valves, or lamps up to 0.5 A

Empirical Engineering Insights

Alternative Models & Compatibility: The IP2310-B810 relies on a serial point-to-point physical connection. If transitioning system networks to EtherCAT or PROFIBUS, this module is not directly cross-compatible without a coupler box. When replacing legacy IP2310 units, verify the default serial transmission rate (baud rate) match; inconsistencies can cause communication timeouts or frame drops across the 15-meter loop.

Application Pitfalls & Engineering Notes: Although individual outputs are short-circuit proof to 1.5 A typically, the total box sensor supply has a cumulative limit of 0.5 A. Engineers must calculate total current draw of all four connected sensors. Running inductive loads without external flyback diodes is supported by the internal clamping circuit, but excessive cycling of high-inductance coils can generate localized thermal stress in enclosed areas with ambient temperatures approaching 55 degC.

Commissioning & Wiring Tips: To ensure reliable communication at 38.4 kbaud over long lines, use only double-shielded copper cable with a minimum cross-section of 2 x 0.25 mm². Ground the shield on the master controller side. Avoid routing the M8 sensor cables parallel to high-voltage variable frequency drive (VFD) output cables to prevent cross-talk on the 0.2 ms digital input lines.

Installation Guidelines

CRITICAL WARNING: SAFETY FIRST

Always completely isolate and de-energize both the auxiliary power (Us) and load voltage (Up) supply lines before mounting, cleaning, or changing any M8/M12 connections. Failure to follow this protocol can result in transient arcs, sensor failure, or unexpected field actuator state changes.

1

Mount the module on a flat machine frame surface using the two integrated 3.5 mm diameter fixing holes designed for standard M3 screws. Do not exceed 0.8 Nm tightening torque to avoid cracking the polyamide shell.

2

Ensure the IP67 sealing integrity by inserting and fully tightening all M8 and M12 mating connectors. Hand-tighten until the tactile seal resistance is felt, then turn an additional 1/4 turn.

3

Install protective plastic caps on any unused 8 mm snap-type or M8 downstream sockets to maintain environmental protection levels (IP65/66/67).

Loading product navigation…

What is the maximum distance for the serial peer-to-peer connection?

The IP2310-B810 supports a maximum cable length of 15 meters using high-quality shielded copper cable with a minimum conductor cross-section of 2 x 0.25 square millimeters.

Are the digital outputs on this Fieldbus Box protected against overcurrent?

Yes, each of the four digital output channels is individually short-circuit proof up to a typical limit of 1.5 A, protecting the internal electronics and cabling.

Can this module be used in wash-down environments without an enclosure?

Yes, the module is housed in a PA6 polyamide casing and is rated IP65/66/67, making it suitable for direct mounting in wet, dusty, or wash-down conditions.

How is the module's baud rate configured?

The default communication rate is 38.4 kbaud. Changes to the serial protocol speed (such as 9.6 kbaud or 19.2 kbaud) can be configured using Beckhoff's KS2000 software interface.

Globaler Expressversand

  • Standardlieferung: 4-6 Werktage per DHL, FedEx und UPS.
  • Expressversand: Versand am selben Tag für vorrätige Bestellungen, die vor 14:00 Uhr (GMT+8) eingehen.
  • Weltweite Abdeckung: Wir beliefern über 150 Länder, einschließlich schneller Lieferung nach Saudi-Arabien und in die VAE.

Rückgaben & Garantie

  • 30-Tage-Garantie: Rückgaben werden für vorrätige Produkte in originaler, werkversiegelter Verpackung akzeptiert.
  • 12-Monats-Garantie: Jede Industriekomponente ist durch unsere professionelle technische Garantie abgesichert.

Bestellungen werden von Montag bis Freitag bearbeitet und geliefert (außer an Feiertagen).


Für vollständige Anspruchsvoraussetzungen, Wiedereinlagerungsgebühren und internationale Rückgabebedingungen lesen Sie bitte unsere offiziellen Rückerstattungs- & Rückgaberecht .

TECHNICAL SPECIFICATIONS

Country of origin
Deutschland

Kürzlich angesehene Produkte

Technisches Wissen

Fortgeschrittene Boolesche Logik mit FBD-SPS-Programmierung: Praktische industrielle Anwendungen über die Grundlogik hinaus

Der Artikel erklärt mehrere erweiterte Boolesche Logikfunktionen, die in der SPS-Programmierung über die grundlegenden AND-, OR- und NOT-Operationen hinaus verwendet werden. Er behandelt, wie...

Boolesche Logik in der SPS-Programmierung: Verständnis von FBD-Logikgattern

Die boolesche Logik ist die Grundlage jedes SPS-Programms. Von einfachen Maschinensteuerungen bis hin zu komplexen industriellen Automatisierungssystemen bestimmen Logikgatter, wie Steuerungen auf...

Umfassender Leitfaden zu industriellen Firewalls und OT-Netzwerksegmentierung

Industrielle Firewalls spielen eine entscheidende Rolle in der OT-Cybersicherheit, indem sie PLC-, DCS- und SCADA-Netzwerke durch Segmentierung, Ein- und Ausgangskontrolle sowie IDS/IPS-Integration...

Leitfaden für Roboter-Greifer: Von der schonenden Handhabung bis zur Schwerlastautomatisierung

Moderne robotische Greifer entwickeln sich über traditionelle mechanische Greifbacken hinaus. Von gecko-inspirierten Haftsystemen und weichen, lebensmittelechten Greifern bis hin zu KI-gestützten...

Rückblick: Wie frühe Elektromotoren den Untertagebergbau veränderten

Von seilgetriebenen Gleichstromkompressoren bis hin zu batteriebetriebenen Grubenwagen markierten frühe Bergbauoperationen einen Wendepunkt in der industriellen Elektrifizierung. Dieser Artikel...

Factory I/O: Ein modernes PLC-Simulationswerkzeug für die Ausbildung in der Industrieautomatisierung

Factory I/O revolutioniert die SPS-Ausbildung, indem es immersive 3D-Industriesimulationen für Studenten, Ingenieure und Wartungsteams bereitstellt. Die Plattform überbrückt die Lücke zwischen...