Optimized for continuous machinery protection and diagnostic monitoring, the Bently Nevada 330104-00-17-10-11-00 is an eddy current proximity probe belonging to the industry-standard 3300 XL 8 mm series. This non-contacting sensor measures static (gap) and dynamic (vibration) distances between the probe tip and the target shaft. It is specifically configured with an M10 x 1 thread, a fully threaded casing option, and a 1.0-meter system length. Equipped with a coaxial ClickLoc connector and FluidLoc cable, this probe prevents process fluids from migrating through the internal structure of the cable, ensuring reliable performance in harsh industrial environments.

Features

  • FluidLoc Cable Technology: Prevents moisture, oil, and process fluids from leaking through the cable interior.
  • ClickLoc Coaxial Connector: Heavy-duty connection mechanism with an integrated connector protector to prevent mechanical decoupling and dust ingress.
  • Fully Threaded Case: 0 mm unthreaded portion with a robust 170 mm overall case length for precise positioning inside deep-well machine housings.
  • High Temperature Stability: Designed to maintain accurate measurement characteristics across demanding industrial temperature profiles.
  • Broad Interoperability: Seamlessly integrates with Bently Nevada 3300 XL Proximitor Sensors and extension cables.

Applications

  • Steam and gas turbine shaft vibration and axial position monitoring.
  • Centrifugal compressor thrust and radial displacement measurements.
  • Gearbox bearing wear analysis and high-speed shaft tracking.
  • Boiler feed pump shaft dynamics monitoring in power generation plants.
  • Hydroelectric generator shaft alignment and runout tracking.

Ordering Information

Option Code Configuration Parameter Selected Specification
00 Unthreaded Length 0 mm (Fully Threaded Case)
17 Overall Case Length 170 mm
10 Total Length 1.0 meter (3.3 feet)
11 Connector & Cable Type Miniature coaxial ClickLoc connector with connector protector, FluidLoc cable
00 Agency Approval Not Required

Technical Specifications

Parameter Value / Specification
Manufacturer Bently Nevada
Part Number / SKU 330104-00-17-10-11-00
Probe Tip Diameter 8 mm
Thread Profile M10 x 1 (metric)
Linear Range 2.0 mm (80 mils) nominal
Operating Temperature Range -51 degC to +177 degC (-60 degF to +350 degF)
Scale Factor Compatibility 7.87 V/mm (200 mV/mil) with matched proximitor
Cable Type 75-ohm coaxial FluidLoc cable
Connector Style Miniature ClickLoc (male)
Net Weight 0.323 kg (0.71 lbs)
Shipping Weight (Calculated) 1.500 kg (3.31 lbs)
Country of Origin United States (U.S.A)

Empirical Engineering Insights

To ensure long-term stability in hazardous industrial processes, engineers must evaluate key physical and electrical parameters during system installation.

Alternative Models & Compatibility

The 330104 series probes must be matched with a Proximitor Sensor of the correct total system length. Because this probe features a 1.0-meter total length, it requires a 4.0-meter extension cable to configure a 5.0-meter total system, or an 8.0-meter extension cable to configure a 9.0-meter total system. Intermixing 5-meter probes with 9-meter sensor electronics will cause severe calibration scale factor errors.

Application Pitfalls & Engineering Notes

Because this probe has an overall case length of 170 mm with 0 mm unthreaded portion, any misalignment during insertion can cause cross-threading in the mounting hole. When installing in a deep housing, check for thread burrs. Avoid bending the FluidLoc cable beyond its minimum dynamic bend radius of 25.4 mm (1.0 inch) to prevent internal micro-fractures in the coaxial shielding.

Commissioning & Wiring Tips

During commissioning, verify the physical gap voltage matches the design setpoint (typically -10 VDC for mid-range calibration) using a calibrated digital multimeter before securing the locknut. Ensure the ClickLoc connector protector is fully seated; this prevents machine vibration from rubbing the connector contact surfaces, which manifests as high-frequency noise spikes in control room trends.

Installation Guidelines

CRITICAL WARNING

Verify the machinery has been fully de-energized, locked out, and tagged out (LOTO) prior to mounting the probe. Keep the sensor tip away from strong magnetic fields during installation. Do not exceed the maximum installation torque of 4.5 N-m (40 in-lb) for M10 threads.

1 Carefully clean and inspect the internal M10 x 1 mounting thread of the bracket or sleeve, removing any oily residues or particulate matter.
2 Thread the probe by hand into the sleeve until the tip gently contacts the target surface (shaft) to establish the zero point.
3 Back the probe out of the mounting hole by the specified distance to meet the target gap voltage (usually around 1.27 mm for standard calibration ranges).
4 Tighten the probe locknut to 4.5 N-m using a torque wrench. Avoid twisting the cable during final tightening.
5 Route the FluidLoc cable inside a dedicated protective conduit, avoiding sharp bends, and connect to the extension cable with the protector sleeve securely closed.
Loading product navigation…

Can I use this 1.0-meter probe with a 9-meter system setup?

Yes, but you must pair this 1.0-meter probe with an 8.0-meter extension cable to match the total 9.0-meter system length required by the 9-meter Proximitor Sensor.

What protection does the FluidLoc cable option provide?

The FluidLoc cable is engineered to prevent oil, water, or other process fluids from leaking through the inner core of the coaxial cable, isolating external environments from your terminal boxes.

What is the tightening torque limit for this M10 x 1 threaded probe?

Do not exceed the maximum installation torque of 4.5 N-m (40 in-lb) to prevent damage to the M10 threads and the internal physical assembly.

What does the 00 unthreaded length code signify?

An unthreaded length code of '00' indicates that the probe case is fully threaded along its entire length, allowing maximum adjustment within the mounting thread.

Globaler Expressversand

  • Standardlieferung: 4-6 Werktage per DHL, FedEx und UPS.
  • Expressversand: Versand am selben Tag für vorrätige Bestellungen, die vor 14:00 Uhr (GMT+8) eingehen.
  • Weltweite Abdeckung: Wir beliefern über 150 Länder, einschließlich schneller Lieferung nach Saudi-Arabien und in die VAE.

Rückgaben & Garantie

  • 30-Tage-Garantie: Rückgaben werden für vorrätige Produkte in originaler, werkversiegelter Verpackung akzeptiert.
  • 12-Monats-Garantie: Jede Industriekomponente ist durch unsere professionelle technische Garantie abgesichert.

Bestellungen werden von Montag bis Freitag bearbeitet und geliefert (außer an Feiertagen).


Für vollständige Anspruchsvoraussetzungen, Wiedereinlagerungsgebühren und internationale Rückgabebedingungen lesen Sie bitte unsere offiziellen Rückerstattungs- & Rückgaberecht .

TECHNICAL SPECIFICATIONS

Country of origin
Vereinigte Staaten

Kürzlich angesehene Produkte

Technisches Wissen

Fortgeschrittene Boolesche Logik mit FBD-SPS-Programmierung: Praktische industrielle Anwendungen über die Grundlogik hinaus

Der Artikel erklärt mehrere erweiterte Boolesche Logikfunktionen, die in der SPS-Programmierung über die grundlegenden AND-, OR- und NOT-Operationen hinaus verwendet werden. Er behandelt, wie...

Boolesche Logik in der SPS-Programmierung: Verständnis von FBD-Logikgattern

Die boolesche Logik ist die Grundlage jedes SPS-Programms. Von einfachen Maschinensteuerungen bis hin zu komplexen industriellen Automatisierungssystemen bestimmen Logikgatter, wie Steuerungen auf...

Umfassender Leitfaden zu industriellen Firewalls und OT-Netzwerksegmentierung

Industrielle Firewalls spielen eine entscheidende Rolle in der OT-Cybersicherheit, indem sie PLC-, DCS- und SCADA-Netzwerke durch Segmentierung, Ein- und Ausgangskontrolle sowie IDS/IPS-Integration...

Leitfaden für Roboter-Greifer: Von der schonenden Handhabung bis zur Schwerlastautomatisierung

Moderne robotische Greifer entwickeln sich über traditionelle mechanische Greifbacken hinaus. Von gecko-inspirierten Haftsystemen und weichen, lebensmittelechten Greifern bis hin zu KI-gestützten...

Rückblick: Wie frühe Elektromotoren den Untertagebergbau veränderten

Von seilgetriebenen Gleichstromkompressoren bis hin zu batteriebetriebenen Grubenwagen markierten frühe Bergbauoperationen einen Wendepunkt in der industriellen Elektrifizierung. Dieser Artikel...

Factory I/O: Ein modernes PLC-Simulationswerkzeug für die Ausbildung in der Industrieautomatisierung

Factory I/O revolutioniert die SPS-Ausbildung, indem es immersive 3D-Industriesimulationen für Studenten, Ingenieure und Wartungsteams bereitstellt. Die Plattform überbrückt die Lücke zwischen...