The CX 5010-N031-0003 (CX5010-N031-0003) is a compact, fanless Embedded PC designed for high-reliability industrial automation applications. Powered by the Intel Atom Z510 processor (1.1 GHz), this unit serves as a robust controller for demanding tasks in manufacturing, building automation, and process control systems. By integrating a persistent 1-second UPS and supporting both E-bus and K-bus I/O systems, this module ensures high system availability and seamless integration, effectively reducing downtime in critical field operations.
The CX 5010 is built on a modular architecture that combines high-performance processing with efficient power management. It features 512 MB of non-expandable RAM and utilizes a Compact Flash card slot for scalable storage, with 128 MB included. The system is engineered for dual-environment support, compatible with both Windows Embedded CE 6 and Windows Embedded Standard 2009. Communication is facilitated through dual Gigabit RJ45 ports and four USB 2.0 interfaces, while the TwinCAT runtime environment provides the deterministic control logic necessary for real-time automation. An integrated 1-second UPS ensures that data on the Compact Flash is safely stored in the event of a power failure.
| Feature | Specification |
| Model | CX 5010-N031-0003 |
| Brand | BECKHOFF |
| Processor | Intel Atom Z510, 1.1 GHz |
| RAM | 512 MB |
| Storage | Compact Flash (128 MB included) |
| Interfaces | 2 x RJ45, 1 x DVI-D, 4 x USB 2.0 |
| I/O Support | E-bus and K-bus (Auto-detect) |
| Power Input | 24 V DC (-15% / +20%) |
| Power Consumption | 12 W |
| Dimensions | 106 mm x 100 mm x 92 mm |
| Operating Temp | -25 to 60 deg C |
Is the memory upgradeable on this model?
No, the 512 MB main memory is fixed and not expandable. However, the storage capacity can be scaled by upgrading the Compact Flash card.
What power supply requirements should I meet?
The unit requires 24 V DC power with a tolerance of -15% to +20%. The maximum power consumption is 12 W, but ensure your power supply can handle the inrush current and the load of connected I/O terminals.
Can this unit be used in hazardous locations?
Yes, with the CX1900-0105 ordering option, the unit meets ATEX requirements (II 3 G Ex nA IIC T4 Gc), making it suitable for specific zones in process industries.
How is the system status monitored?
The unit features four integrated diagnostic LEDs covering power status, TwinCAT runtime state, flash access, and fieldbus communication status for quick on-site troubleshooting.
Global Express Shipping
Returns & Warranty
Orders are processed and delivered Monday-Friday (excluding public holidays).
For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .
| Color pattern |
نقرهای
|
| Country of origin |
آلمان
|