1 de 3

Foxboro P0973CN I/A Series Expansion Baseplate

Foxboro P0973CN I/A Series Expansion Baseplate

Il ne reste que 10 article(s) en stock
  • Fabricant : Foxboro

  • N° de produit : P0973CN

  • Pays d'origine :France

  • Type de produit : Expansion Baseplates

  • Paiement : Virement bancaire, Western Union

  • Poids : 800g

  • Dimensions : 240.0 mm x 216.0 mm x 30.3 mm (H x W x D)

  • Port d'expédition : Xiamen

  • Garantie : 12 mois

Quantité
Voir les détails complets

Description

The Foxboro P0973CN is a 4-position vertical DIN rail mounted expansion baseplate used in the Foxboro I/A Series DCS. It provides a dedicated hardware platform to house a fault-tolerant pair of FCP270 field control processors in two positions and a redundant pair of FEM100 fieldbus expansion modules in the remaining two positions. Operating on a passive backplane structure, the Foxboro P0973CN delivers high-reliability power routing and communication interconnections across the 2 Mbps Module Fieldbus. Mounting positions are specifically integrated onto the baseplate to accommodate fiber optic splitter/combiners required for fault-tolerant FCP270 processor operations.

Features

  • Vertical DIN rail mounting configuration for standard enclosure layouts.
  • Four dedicated module positions configured for two FCP270 processors and two FEM100 modules.
  • Integrated mounting space for fiber optic splitter/combiners to support FCP270 redundancy.
  • Dual primary and secondary 24 V dc power connections.
  • Shielded twisted-pair Module Fieldbus interconnections operating at 2 Mbps.
  • Hot-swappable module support allowing unit addition or replacement without disrupting active bus communication.
  • Passive backplane architecture designed to maximize overall DCS operational reliability.

Applications

  • Foxboro I/A Series DCS system expansion requiring additional 200 Series FBM fieldbus channels.
  • High-density industrial automation control cabinets requiring fault-tolerant processing and fieldbus expansion.
  • Continuous processing plant infrastructure utilizing DIN rail mounted hardware subsystems.

Technical Specifications

Specification Value
Manufacturer Foxboro (Invensys)
Model P0973CN
System Compatibility Foxboro I/A Series
Mounting Orientation Vertical DIN Rail
Capacity 4 Module Positions (2x FCP270, 2x FEM100)
Input Voltage Range 24 V dc +5%, -10% (Redundant)
Communication Protocol 2 Mbps HDLC Module Fieldbus
Baseplate ID DIP Switch Not present (Does not require hardwired address)
Operating Temperature -20 to +70 degC (-4 to +158 degF)
Storage Temperature -40 to +70 degC (-40 to +158 degF)
Relative Humidity 5 to 95% (noncondensing)
Altitude -300 to +3,000 m (-1,000 to +10,000 ft)
Contamination Class Class G3 (Harsh) per ISA S71.04; Pollution degree 2 per IEC 664-1
Material PC and ABS, inflammability UL94 V0
Color Black
Max Cable Length 60 m (198 ft) total overall Module Fieldbus cabling

Connections/Interfaces

Connector Pin / Interface Function
Primary Power Connector Direct 24 V dc primary power input connection from FPS power supply
Secondary Power Connector Direct 24 V dc secondary power input connection from FPS power supply
Fieldbus and Time Strobe A/B Connections for redundant Module Fieldbus (2 Mbps) and optional time strobe signals
Dedicated FCP270 Slots Keyed slots for fault-tolerant FCP270 control processors
Dedicated FEM100 Slots Keyed slots for redundant FEM100 fieldbus expansion modules
Splitter/Combiner Mount Integrated mounting provisions for FCP270 fiber optic splitter/combiners

Installation Guidelines

  • DIN Rail Mounting: Secure the baseplate to a non-isolated, mechanically supported vertical DIN rail using the designated fasteners.
  • Power Cabling: Connect primary and secondary 24 V dc feed cables from the system power supply (such as FPS400-24, FPS240-24, or FPS120-24) to the primary and secondary power terminals.
  • Fieldbus Interconnection: Use shielded twisted-pair cables for A/B Module Fieldbus daisy-chain connections between baseplates, maintaining a maximum total fieldbus length of 60 m (198 ft).
  • Clearance: Ensure adequate enclosure clearance around the mounted baseplate to accommodate module insertion, removal, and field wiring clearance.
  • Live Insertion: Baseplates can be connected or expanded without removing the system from service provided a redundant bus structure is in place.

Compliance and Certifications

  • European EMC Directive: 89/336/EEC (EN 50081-2, EN 50082-2, EN 61326 Annex A)
  • ISM Radio-frequency: CISPR 11 Class A
  • Immunity: IEC 61000-4-2 (ESD), IEC 61000-4-3 (Radiated Field), IEC 61000-4-4 (EFT/Burst), IEC 61000-4-5 (Surge), IEC 61000-4-6 (Conducted), IEC 61000-4-8 (Magnetic Field)
  • Product Safety: UL/UL-C listed for Class 1, Groups A-D, Division 2, T4 enclosure systems
  • European Low Voltage Directive: 2006/95/EC
  • ATEX Directive: 94/9/EC (CENELEC certified EEx n IIC for Zone 2)
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Foxboro P0973CN I/A Series Expansion Baseplate

What is the Foxboro P0973CN used for?

The Foxboro P0973CN is a 4-position vertical DIN rail mounted expansion baseplate used to host a fault-tolerant pair of FCP270 control processors and a redundant pair of FEM100 fieldbus expansion modules in the I/A Series DCS.

Which modules are supported on the P0973CN baseplate?

The module dedicated positions on the baseplate support two FCP270 field control processors and two FEM100 fieldbus expansion modules.

Does the Foxboro P0973CN require DIP switch addressing?

No. The P0973CN expansion baseplate does not feature a baseplate identification DIP switch because it does not require a hardwired address.

What power input voltage does the baseplate require?

The baseplate requires a redundant 24 V dc power supply input with a functional operating range of +5% to -10%.

Expédition express mondiale

  • Livraison standard : 4 à 6 jours ouvrables via DHL, FedEx et UPS.
  • Expédition express : Expédition le jour même pour les commandes en stock passées avant 14h00 (GMT+8).
  • Couverture mondiale : Service dans plus de 150 pays, avec livraison rapide en Arabie Saoudite et aux Émirats Arabes Unis.

Retours et garantie

  • Garantie de 30 jours : Retours acceptés pour les produits en stock dans leur emballage d'origine scellé en usine.
  • Garantie de 12 mois : Chaque composant industriel est couvert par notre garantie technique professionnelle.

Les commandes sont traitées et livrées du lundi au vendredi (hors jours fériés).


Pour connaître l'éligibilité complète, les frais de restockage et les détails des retours internationaux, veuillez consulter notre site officiel Politique de remboursement et de retour .

TECHNICAL SPECIFICATIONS

Country of origin
France

Produits récemment consultés

Connaissances techniques

Qu’est-ce qu’un variateur de fréquence (VFD) ? Des variateurs de fréquence qui font vraiment la différence

Un variateur de fréquence convertit le réseau à fréquence fixe en une tension et une fréquence contrôlées afin que les moteurs à courant alternatif s’adaptent à la charge réelle, réduisant ainsi la...

Qu’est-ce qu’un automate programmable industriel (API) ? Les contrôleurs qui font toujours fonctionner l’atelier de production

Les automates programmables industriels (API) pilotent toujours l’atelier : les cycles de scrutation, les E/S et les langages de la norme IEC 61131-3 déterminent si les machines restent...

Ce qu’il faut vraiment pour apprendre l’automatisation industrielle en 2026

Apprendre l’automatisation industrielle signifie désormais maîtriser les automates programmables, les réseaux et les systèmes de protection — pas seulement les robots. Ce guide présente les...

Modernisation des IHM Bailey INFI 90 Symphony fonctionnant sous OpenVMS Alpha

Un guide pratique pour remplacer les postes opérateur vieillissants Bailey Symphony fonctionnant sous OpenVMS Alpha. Il compare l’émulation Alpha, la migration vers OpenVMS x86, la refonte basée sur...

Pourquoi les données de maintenance sont essentielles à la fiabilité industrielle

Les données de maintenance relient les ordres de travail, les signaux des capteurs, l’historique des actifs, les coûts et les connaissances des techniciens. Lorsqu’elles sont bien exploitées, elles...

Actionneurs électriques conçus pour remplacer les systèmes de puissance fluidique : guide pratique de l’automatisation industrielle

Cet article explique comment les actionneurs électriques intégrés, tels que la série e-Actuator de SMC, transforment le contrôle des mouvements industriels en remplaçant les systèmes pneumatiques et...