1 / 1

Beckhoff CX5010-0122 CX5000 Series Embedded PC Module

Beckhoff CX5010-0122 CX5000 Series Embedded PC Module

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: CX5010-0122

  • Country of origin:Németország

  • Product Type: Embedded PC Modules

  • Payment: T/T, Western Union

  • Weight: 500g

  • Dimensions: 106 mm x 100 mm x 92 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Mennyiség
Minden részlet megtekintése

Description

Engineered for DIN rail mounting in compact control cabinets, the Beckhoff CX5010-0122 delivers decentralized industrial control capability by combining a fanless Intel Atom Z510 processor with direct, automatic detection of both E-bus (EtherCAT) and K-bus (Bus Terminal) I/O architectures. This embedded controller features dual independent Gigabit Ethernet interfaces, enabling clean network segmentation between fieldbus communications and upper-level enterprise systems. An integrated 1-second UPS ensures that up to 1 MB of persistent process data is safely written to the standard Compact Flash storage during power interruptions, preventing database corruption and ensuring smooth cold-start sequences.

Features

  • Efficient Processing: Low-power Intel Atom Z510 CPU operating at 1.1 GHz for reliable deterministic control loops.
  • Flexible I/O Interface: Automatic, native recognition of either EtherCAT Terminals (E-bus) or legacy Bus Terminals (K-bus) on the backplane.
  • High-Speed Communication: Two RJ45 10/100/1000 Mbit/s interfaces supporting separate subnet topologies.
  • Data Security: Integrated hardware-based 1-second UPS protecting crucial operational variables on power loss.
  • Rugged Construction: Fanless, compact IP20 housing designed to withstand extreme temperature ranges.

Applications

  • Decentralized manufacturing automation and specialized machine building.
  • Wind turbine pitch control and substation environmental telemetry.
  • Conveyor tracking, high-speed sorting, and distribution center automation.
  • Hazardous-area operations requiring certified ATEX Zone 2 hardware configurations.

Technical Specifications

Specification Parameter Value / Rating
Manufacturer Beckhoff
Model Number CX5010-0122
Processor Intel Atom Z510, 1.1 GHz (Single Core)
System Memory 512 MB RAM (Non-expandable)
Flash Memory Compact Flash slot (128 MB card included)
Persistent Memory 1-second UPS integrated (saves 1 MB to Compact Flash)
Interfaces 2 x RJ45 (10/100/1000 Mbit/s), 1 x DVI-D, 4 x USB 2.0, 1 x Optional slot
I/O Coupling E-bus (EtherCAT) or K-bus (Bus Terminal) with auto-recognition
E-bus/K-bus Current Supply 2 A maximum
Supply Voltage 24 V DC (-15% / +20%)
Max Power Consumption 12 W
Operating / Storage Temp -25 to +60 degC / -40 to +85 degC
Protection Rating IP20
Ex Marking II 3 G Ex nA IIC T4 Gc (with optional CX1900-0105)
TwinCAT Platform Level Performance (40)
Dimensions (W x H x D) 106 mm x 100 mm x 92 mm
Net Weight 575 g
Shipping Weight (Calculated) 2.0 kg

Connections and Interfaces

Port Designation Functional Assignment / Circuit
X101 / X102 RJ45 Gigabit Ethernet ports (independent controllers for separation)
X201 - X204 4 x USB 2.0 Host interfaces (max. 500 mA per port)
DVI-D Port Direct connection for digital operating interfaces and panels
Power Input Terminals 24 V DC control power, 0 V return, PE shield contact

Empirical Engineering Insights

Alternative Models & Compatibility

The CX5010-0122 belongs to the legacy CX5000 family. If upgrading a system configured with older K-bus terminals, this unit serves as a direct bridge because of its dual-bus interface chip. However, note that if you are migrating code from TwinCAT 2 to TwinCAT 3 (XAR), you must ensure that your system target is configured to Platform Level 40 (Performance class). Using older TwinCAT 2 boot projects requires the operating system runtime to match (e.g., Windows CE 6 or WES 2009).

Application Pitfalls & Engineering Notes

To prevent thermal throttling under maximum execution load (12 W), the CX5010-0122 must be mounted vertically on a 35 mm DIN rail. Always maintain at least 30 mm of free ventilation clearance above and below the module. If installing inside fully sealed, unventilated cabinets with ambient temperatures regularly exceeding +50 degC, structural derating of the 2 A output capacity on the E-bus/K-bus backplane is recommended to prevent internal component degradation.

Commissioning & Wiring Tips

The internal 1-second UPS utilizes a persistent RAM buffer that flushes directly to the CF card. Always format replacement Compact Flash cards using the specific Beckhoff BIOS utility to guarantee the correct sector alignment; standard generic FAT/NTFS formatting can lead to persistent data write failures during a fast power loss event. Use double-shielded STP Cat.6 cables on the X101/X102 ports to prevent high-voltage motor drive emissions from introducing packet errors on your real-time network lines.

Installation Guidelines

CRITICAL WARNING: Prior to mounting or wiring this device, ensure the main 24 V DC power supply is completely de-energized. Do not extract or insert the Compact Flash card while the system status LED indicates active disk access. Failure to follow these isolation protocols can cause permanent electronic damage or filesystem corruption.
1

Snap the CX5010-0122 securely onto a grounded, standard 35 mm DIN rail (EN 60715) ensuring the locking mechanism clicks into position.

2

Connect your E-bus (EtherCAT) or K-bus (Bus Terminal) I/O stack to the right side of the controller. The built-in interface contacts will self-align.

3

Wire the 24 V DC power input using a clean, surge-suppressed PELV/SELV power supply unit, making sure to route the PE wire to the centralized ground bar.

4

Insert the pre-programmed Beckhoff Compact Flash card, connect the communication cables, and apply system voltage to initiate the automated hardware-recognition scan.

Can the system memory of the CX5010-0122 be upgraded?

No, the 512 MB RAM on the CX5010-0122 is integrated directly on the motherboard and is not expandable.

Does this controller support both K-bus and E-bus terminals?

Yes, the unit features an intelligent internal interface that automatically detects and communicates with both K-bus (Bus Terminals) and E-bus (EtherCAT Terminals) on startup.

What is the purpose of the integrated 1-second UPS on this model?

The integrated 1-second UPS uses local capacitors to provide power long enough to write up to 1 MB of critical persistent variables to the Compact Flash card when main power fails.

What TwinCAT 3 platform level applies to this hardware?

The CX5010-0122 is classified under TwinCAT 3 Platform Level 40 (Performance class).

Globális expressz szállítás

  • Normál szállítás: 4-6 munkanap a DHL, FedEx és UPS szolgáltatásával.
  • Gyors kiszállítás: A raktáron lévő, 14:00 (GMT+8) előtt leadott megrendeléseket aznap feladjuk.
  • Világszintű lefedettség: Több mint 150 országban szolgálunk ki, beleértve a gyors szállítást Szaúd-Arábiába és az Egyesült Arab Emírségekbe.

Visszaküldés és garancia

  • 30 napos garancia: Csak a raktáron lévő termékek eredeti, gyári zárt csomagolásban történő visszaküldését fogadjuk el.
  • 12 hónapos garancia: Minden ipari alkatrészünket szakmai műszaki garancia védi.

A megrendeléseket hétfőtől péntekig dolgozzuk fel és szállítjuk (állami ünnepnapok kivételével).


A teljes jogosultság, a készletfeltöltési díjak és a nemzetközi visszaküldési részletek megtekintéséhez kérjük, tekintse meg hivatalos oldalunkat Visszatérítési és Visszaküldési Szabályzat .

TECHNICAL SPECIFICATIONS

Country of origin
Németország

Nemrég megtekintett termékek

Műszaki ismeretek

Elektromos működtetők, amelyek a folyadékenergia-rendszereket váltják ki: Gyakorlati ipari automatizálási útmutató

Ez a cikk bemutatja, hogyan alakítják át az integrált elektromos működtetők, például az SMC e-Actuator sorozata, az ipari mozgásvezérlést azáltal, hogy kiváltják a hagyományos pneumatikus és...

Matematikai műveletek OpenPLC-vel ipari automatizálási alkalmazásokhoz

Ez a cikk bemutatja, hogyan hajtanak végre a PLC rendszerek alapvető matematikai műveleteket, mint az összeadás, kivonás, szorzás, osztás, modulo és hatványozás az ipari automatizálásban. Megmutatja,...

Fejlett Boole-logika FBD PLC programozással: Gyakorlati ipari alkalmazások a alapvető logikán túl

A cikk több fejlett Boole-logikai függvényt ismertet, amelyeket a PLC programozásban használnak az alapvető ÉS, VAGY és NEM műveleteken túl. Bemutatja, hogyan alkalmazhatók olyan eszközök, mint az...

Boole-logika a PLC programozásban: Az FBD logikai kapuk megértése

A Boole-logika minden PLC program alapja. Az egyszerű gépvezérlésektől a bonyolult ipari automatizálási rendszerekig a logikai kapuk határozzák meg, hogyan reagálnak a vezérlők a változó bemenetekre...

Részletes útmutató az ipari tűzfalakról és az OT hálózati szegmentációról

Az ipari tűzfalak kulcsfontosságú szerepet játszanak az OT kiberbiztonságban, védve a PLC, DCS és SCADA hálózatokat szegmentálás, be- és kimeneti forgalom szabályozás, valamint az IEC 62443 elveivel...

Útmutató a robotikus fogókhoz: a finomkezeléstől a nehézüzemi automatizálásig

A modern robotfogók túlmutatnak a hagyományos mechanikus állkapcsokon. A gyíkok tapadó rendszerétől és az élelmiszeripari puha fogóktól az MI-vezérelt raktári eszközökig a fejlett fogástechnológiák...