Description

Generating precise analog control signals within the Beckhoff I/O framework, the Beckhoff KL4424 operates as a high-density, four-channel current output module. Engineered to process signals in the standard 4 to 20 mA range, this terminal delivers high resolution and galvanic isolation to field-level actuators, control valves, and current-loop indicators. Its robust design is optimized for environments demanding dependable noise immunity and stable performance under fluctuating thermal conditions.

Key Features

  • Four Single-Ended Channels: Compact integration of four analog outputs within a single 12 mm Bus Terminal housing.
  • 12-Bit Resolution: High-precision digital-to-analog conversion providing precise process control execution.
  • Short-Circuit Proof: Outputs are protected against wiring faults and load fluctuations up to 350 Ohms.
  • Flexible Power Options: Operates natively via 24 V DC power contacts, with support for 15 V DC via the KL9515 power supply terminal.
  • Galvanic Isolation: Provides 500 V isolation between the internal K-bus electronics and the signal channels.
  • Comprehensive Certifications: Approved for hazardous areas with ATEX, IECEx, and cFMus Class I Division 2 ratings.

Applications

  • Modulating valve positioners and pneumatic actuators in oil and gas refineries.
  • Variable frequency drive speed reference control over standardized current loops.
  • Process instrumentation control in chemical processing plants.
  • Water and wastewater flow rate configuration systems.

Technical Specifications

Parameter Value / Specification
Manufacturer Beckhoff Automation
Model Series KL-Bus Terminal System (KL4xxx)
Number of Outputs 4 single-ended
Signal Current Range 4...20 mA
Resolution 12-bit
Output Load Limitation < 350 Ohm (short-circuit proof)
Output Error < ±0.1% (relative to end-scale value)
Conversion Time approx. 4 ms
Supply Voltage 24 V DC via power contacts (or 15 V DC via KL9515)
Current Consumption (K-bus) typ. 20 mA
Current Consumption (Power Contacts) typ. 60 mA + load current
Electrical Isolation 500 V (K-bus / signal voltage)
Bit Width in Process Image 4 x 16-bit output data (optional 4 x 8-bit control/status)
Operating Temperature 0 degC to +55 degC
Storage Temperature -25 degC to +85 degC
Relative Humidity 95%, non-condensing
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Protection Rating IP20 (variable installation position)
Net Weight approx. 75 g
Shipping Weight (Calculated) 0.15 kg
Package Dimensions (Calculated) 12.0 x 7.0 x 3.0 cm
Hazardous Location Approvals ATEX II 3 G Ex nA IIC T4 Gc / IECEx Ex ec IIC T4 Gc / cFMus Cl. I Div 2

Connections and Interfaces

Terminal Point Signal Name Description
1 Out 1 Analog Output 1 (4...20 mA)
2 Out 2 Analog Output 2 (4...20 mA)
3 Out 3 Analog Output 3 (4...20 mA)
4 Out 4 Analog Output 4 (4...20 mA)
5 0 V Common Ground Reference (Power Contact)
6 0 V Common Ground Reference (Power Contact)
7 0 V Common Ground Reference (Power Contact)
8 0 V Common Ground Reference (Power Contact)

Alternative Models & Compatibility

The terminal utilizes standard K-bus backplane communication and can be combined seamlessly with other standard bus terminals. For installations requiring pluggable wiring harnesses to minimize field maintenance times, the KS4424 version serves as the direct hardware equivalent featuring pluggable connector blocks.

Application Pitfalls & Engineering Notes

When sizing current loops, ensure that the total loop resistance does not exceed 350 Ohms. Exceeding this limit will cause the output driver to saturate before reaching the full 20 mA signal level, resulting in non-linear control. In high-density cabinet layouts with elevated ambient operating temperatures, consider powering the terminal at 15 V DC using a KL9515 terminal block to minimize local thermal dissipation within the enclosure.

Commissioning & Wiring Tips

To protect sensitive low-level analog signals from electromagnetic interference, use shielded twisted-pair (STP) cabling for all output runs. Ground the cable shield only at the entry point of the control cabinet to avoid forming ground loops. Ensure that the 0 V reference terminals (5 through 8) are properly bridged to the common power contact ground path to prevent common-mode voltage offsets on the analog signals.

Installation Guidelines

CRITICAL WARNING:

De-energize all field circuits and system power supplies before mounting or dismounting the terminal. Inserting or removing bus terminals while the backplane or external field power is energized can cause physical damage to the internal K-bus contacts and compromise surrounding modules.

1 Mounting on DIN Rail

Snap the module onto a standard 35 mm DIN rail (EN 60715), ensuring that the locking mechanism engages securely with the rail's edges.

2 Side-by-Side Integration

Slide the terminal horizontally along the DIN rail to interconnect the K-bus and power contacts with adjacent terminals. Verify that the side tongue-and-groove joints are fully locked.

3 Field Wiring Termination

Insert wire connections using a screwdriver to open the spring-loaded tension clamps. Ensure only stripped conductors without frayed copper strands are inserted, then release the spring clamp to lock the connection.

What is the maximum allowed loop load for the analog outputs on this terminal?

The maximum load resistance per channel is 350 Ohms. The outputs are short-circuit proof to prevent hardware damage from wiring faults.

Can this output terminal be used with a 15 V DC external power supply instead of 24 V DC?

Yes. This module supports alternative operation at 15 V DC when paired with a KL9515 power supply terminal, which helps minimize heat generation in enclosed control cabinets.

What is the difference between this model and the KS4424 version?

The KL4424 features fixed tension-clamp wire terminals, while the KS4424 is equipped with pluggable connector blocks to allow faster hot-swapping during field maintenance.

Does this terminal support individual channel configuration or scaling?

The terminal converts the digital 12-bit value in the process image linearly into the 4 to 20 mA range across all four outputs. Detailed scaling, filters, or range adjustments can be configured via TwinCAT software or controller-side mapping.

Globális expressz szállítás

  • Normál szállítás: 4-6 munkanap a DHL, FedEx és UPS szolgáltatásával.
  • Gyors kiszállítás: A raktáron lévő, 14:00 (GMT+8) előtt leadott megrendeléseket aznap feladjuk.
  • Világszintű lefedettség: Több mint 150 országban szolgálunk ki, beleértve a gyors szállítást Szaúd-Arábiába és az Egyesült Arab Emírségekbe.

Visszaküldés és garancia

  • 30 napos garancia: Csak a raktáron lévő termékek eredeti, gyári zárt csomagolásban történő visszaküldését fogadjuk el.
  • 12 hónapos garancia: Minden ipari alkatrészünket szakmai műszaki garancia védi.

A megrendeléseket hétfőtől péntekig dolgozzuk fel és szállítjuk (állami ünnepnapok kivételével).


A teljes jogosultság, a készletfeltöltési díjak és a nemzetközi visszaküldési részletek megtekintéséhez kérjük, tekintse meg hivatalos oldalunkat Visszatérítési és Visszaküldési Szabályzat .

TECHNICAL SPECIFICATIONS

Country of origin
Németország

Nemrég megtekintett termékek

Műszaki ismeretek

Elektromos működtetők, amelyek a folyadékenergia-rendszereket váltják ki: Gyakorlati ipari automatizálási útmutató

Ez a cikk bemutatja, hogyan alakítják át az integrált elektromos működtetők, például az SMC e-Actuator sorozata, az ipari mozgásvezérlést azáltal, hogy kiváltják a hagyományos pneumatikus és...

Matematikai műveletek OpenPLC-vel ipari automatizálási alkalmazásokhoz

Ez a cikk bemutatja, hogyan hajtanak végre a PLC rendszerek alapvető matematikai műveleteket, mint az összeadás, kivonás, szorzás, osztás, modulo és hatványozás az ipari automatizálásban. Megmutatja,...

Fejlett Boole-logika FBD PLC programozással: Gyakorlati ipari alkalmazások a alapvető logikán túl

A cikk több fejlett Boole-logikai függvényt ismertet, amelyeket a PLC programozásban használnak az alapvető ÉS, VAGY és NEM műveleteken túl. Bemutatja, hogyan alkalmazhatók olyan eszközök, mint az...

Boole-logika a PLC programozásban: Az FBD logikai kapuk megértése

A Boole-logika minden PLC program alapja. Az egyszerű gépvezérlésektől a bonyolult ipari automatizálási rendszerekig a logikai kapuk határozzák meg, hogyan reagálnak a vezérlők a változó bemenetekre...

Részletes útmutató az ipari tűzfalakról és az OT hálózati szegmentációról

Az ipari tűzfalak kulcsfontosságú szerepet játszanak az OT kiberbiztonságban, védve a PLC, DCS és SCADA hálózatokat szegmentálás, be- és kimeneti forgalom szabályozás, valamint az IEC 62443 elveivel...

Útmutató a robotikus fogókhoz: a finomkezeléstől a nehézüzemi automatizálásig

A modern robotfogók túlmutatnak a hagyományos mechanikus állkapcsokon. A gyíkok tapadó rendszerétől és az élelmiszeripari puha fogóktól az MI-vezérelt raktári eszközökig a fejlett fogástechnológiák...