BECKHOFF KL6781 Bus Terminal M-Bus Master

BECKHOFF KL6781 Bus Terminal M-Bus Master

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: KL6781

  • Country of origin:Németország

  • Product Type: Bus Terminals

  • Payment: T/T, Western Union

  • Weight: 60g

  • Shipping port: Xiamen

  • Warranty: 12 months

Mennyiség
Minden részlet megtekintése

Description

Designed to facilitate seamless integration of utility metering devices, the Beckhoff KL6781 operates as a single-channel M-Bus master terminal within the standard Beckhoff Bus Terminal system. This module enables direct, bidirectional communication with up to 40 standard M-Bus loads, such as heat, water, electricity, or gas meters, over a single bus segment without requiring external level converters. Operating in master-slave mode via polling, the KL6781 transmits data standard M-Bus physics, enabling consolidated energy management and resource tracking directly from the TwinCAT control environment.

The terminal features a 24-byte process image for inputs and outputs, allowing robust data transfer rates ranging from 300 to 9600 baud. Integration is streamlined through the TwinCAT PLC M-Bus library, which provides specialized function blocks for rapid field configuration. With built-in short-circuit protection and 500 V electrical isolation between the K-bus and the M-Bus physics, the module ensures robust operation and system-wide protection against electrical faults in harsh industrial or commercial environments.

Features

  • Single-Channel Architecture: Dedicated M-Bus interface supporting up to 40 standard M-Bus loads (1.5 mA current consumption per load).
  • Flexible Baud Rates: Configurable data transfer rates from 300 to 9600 baud (default transmission set to 2400 baud).
  • Electrical Isolation: Complete 500 V isolation barrier safeguarding the internal K-bus from the M-Bus network.
  • Integrated Protection: Full short-circuit proof design to prevent module failure during field wiring faults.
  • Software Compatibility: Programmed and configured directly through TwinCAT using official M-Bus PLC function blocks.

Applications

  • Commercial and industrial building automation systems (BAS).
  • Sub-metering networks for monitoring water, gas, steam, and electricity consumption.
  • Energy management systems (EMS) compliant with ISO 5001 standards.
  • District heating stations and utility billing infrastructure.

Technical Specifications

CategoryParameterValue
Administrative Manufacturer Beckhoff Automation
Part Number/Model KL6781
Product Series Bus Terminal System (KL Series)
Communication & Bus Technology M-Bus
Data Transfer Standard M-Bus physics
Number of Channels 1
Maximum Connected Loads 40 standard loads (1.5 mA each)
Data Transfer Rates 300 to 9600 baud (default: 2400 baud)
Bus Access Master-slave mode (polling)
Electrical Data Nominal Voltage 24 V DC (-10% / +8%)
Current Consumption (K-bus) Typically 65 mA
Current Consumption (Power Contacts) Maximum 250 mA
Protection & Safety Short-Circuit Protection Yes
Electrical Isolation 500 V (K-bus / M-Bus)
Process Image Bit Width 24 bytes input / 24 bytes output
Environmental & Mechanical Weight Approx. 60 g
Operating Temperature 0 to 55 degC
Storage Temperature -25 to 85 degC
Relative Humidity 95%, non-condensing
Standards & Approvals Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Certifications & Marks CE, UL

Connections and Interfaces

Terminal Point Signal/Function Description
1 M+ M-Bus Connection (+)
2 Shield Shielding / Functional Ground
3 +24 V DC External Power Supply (+)
5 M- M-Bus Connection (-)
7 0 V DC External Power Supply (0 V)

Installation Guidelines

  • Mounting: Mount the terminal vertically on standard 35 mm DIN rails (EN 60715) within an IP20-rated enclosure or control cabinet.
  • Wiring: Keep maximum cable lengths on the M-Bus segment below 300 meters. Use shielded twisted-pair (STP) cabling for optimal noise immunity.
  • Grounding: Connect the shield connection point directly to a low-impedance functional ground or DIN rail clamp.
  • Ventilation: Ensure a clearance of at least 30 mm above and below the terminal block to maintain normal operating temperatures between 0 and 55 degC.

What is the primary function of the Beckhoff KL6781?

The Beckhoff KL6781 acts as a single-channel M-Bus master terminal within a Beckhoff Bus Terminal system, enabling direct integration of M-Bus compliant utility meters (water, gas, electricity, heat) without external level converters.

How many M-Bus devices can be connected to the KL6781 terminal?

The KL6781 supports up to 40 standard M-Bus loads, assuming each connected device consumes a standard current of 1.5 mA.

What software is used to configure the KL6781?

Configuration is handled in TwinCAT using the official TwinCAT PLC M-Bus library, which contains dedicated function blocks for communicating with the meters.

Is the KL6781 protected against field wiring faults?

Yes, the module is short-circuit proof and features 500 V electrical isolation between the inner K-bus electronics and the external M-Bus physics.

What is the maximum cable length supported by the M-Bus line on the KL6781?

The terminal supports a maximum M-Bus cable length of up to 300 meters.

Globális expressz szállítás

  • Normál szállítás: 4-6 munkanap a DHL, FedEx és UPS szolgáltatásával.
  • Gyors kiszállítás: A raktáron lévő, 14:00 (GMT+8) előtt leadott megrendeléseket aznap feladjuk.
  • Világszintű lefedettség: Több mint 150 országban szolgálunk ki, beleértve a gyors szállítást Szaúd-Arábiába és az Egyesült Arab Emírségekbe.

Visszaküldés és garancia

  • 30 napos garancia: Csak a raktáron lévő termékek eredeti, gyári zárt csomagolásban történő visszaküldését fogadjuk el.
  • 12 hónapos garancia: Minden ipari alkatrészünket szakmai műszaki garancia védi.

A megrendeléseket hétfőtől péntekig dolgozzuk fel és szállítjuk (állami ünnepnapok kivételével).


A teljes jogosultság, a készletfeltöltési díjak és a nemzetközi visszaküldési részletek megtekintéséhez kérjük, tekintse meg hivatalos oldalunkat Visszatérítési és Visszaküldési Szabályzat .

TECHNICAL SPECIFICATIONS

Country of origin
Németország

Nemrég megtekintett termékek

Műszaki ismeretek

Elektromos működtetők, amelyek a folyadékenergia-rendszereket váltják ki: Gyakorlati ipari automatizálási útmutató

Ez a cikk bemutatja, hogyan alakítják át az integrált elektromos működtetők, például az SMC e-Actuator sorozata, az ipari mozgásvezérlést azáltal, hogy kiváltják a hagyományos pneumatikus és...

Matematikai műveletek OpenPLC-vel ipari automatizálási alkalmazásokhoz

Ez a cikk bemutatja, hogyan hajtanak végre a PLC rendszerek alapvető matematikai műveleteket, mint az összeadás, kivonás, szorzás, osztás, modulo és hatványozás az ipari automatizálásban. Megmutatja,...

Fejlett Boole-logika FBD PLC programozással: Gyakorlati ipari alkalmazások a alapvető logikán túl

A cikk több fejlett Boole-logikai függvényt ismertet, amelyeket a PLC programozásban használnak az alapvető ÉS, VAGY és NEM műveleteken túl. Bemutatja, hogyan alkalmazhatók olyan eszközök, mint az...

Boole-logika a PLC programozásban: Az FBD logikai kapuk megértése

A Boole-logika minden PLC program alapja. Az egyszerű gépvezérlésektől a bonyolult ipari automatizálási rendszerekig a logikai kapuk határozzák meg, hogyan reagálnak a vezérlők a változó bemenetekre...

Részletes útmutató az ipari tűzfalakról és az OT hálózati szegmentációról

Az ipari tűzfalak kulcsfontosságú szerepet játszanak az OT kiberbiztonságban, védve a PLC, DCS és SCADA hálózatokat szegmentálás, be- és kimeneti forgalom szabályozás, valamint az IEC 62443 elveivel...

Útmutató a robotikus fogókhoz: a finomkezeléstől a nehézüzemi automatizálásig

A modern robotfogók túlmutatnak a hagyományos mechanikus állkapcsokon. A gyíkok tapadó rendszerétől és az élelmiszeripari puha fogóktól az MI-vezérelt raktári eszközökig a fejlett fogástechnológiák...