Description

Actuating as a dedicated integration link, the Beckhoff KS6771 Bus Terminal enables direct, bidirectional communication between a K-bus coupler and Belimo MP-Bus HVAC field devices. This module functions as an MP-Bus master, coordinating data acquisition and control command distribution over a single channel. The KS6771 design features a pluggable wiring level, allowing swift module swaps without disconnecting field-level wiring harnesses. Integration is fully managed via standard TwinCAT PLC function blocks, streamlining commissioning across complex commercial and industrial air handling architectures.

Features

  • Multi-Device Topologies: Controls up to 16 MP-Bus devices (maximum 8 drives and 8 sensors) over a single fieldbus drop.
  • Pluggable Wiring Interface: Uses tension-clamp connection terminals that can be detached as a single block for expedited terminal replacement.
  • Galvanic Isolation: Provides robust 500 V isolation between the internal K-bus and the external MP-Bus circuitry to suppress common-mode electrical noise.
  • Efficient Process Image: Maps directly into the controller configuration utilizing 12 bytes of input data and 12 bytes of output data.
  • Standardized Diagnostics: Fully compatible with the TwinCAT PLC MP-Bus software library for fast system integration and continuous error reporting.

Applications

  • HVAC Variable Air Volume (VAV) Systems: Direct control of volumetric flow controllers, damper actuators, and temperature sensors.
  • Industrial Environmental Controls: Closed-loop control of pressure relief valves and air-handling units within cleanrooms or pharmaceutical laboratories.
  • Building Management Systems (BMS): Integration of distributed Belimo valve actuators and auxiliary sensors into high-level Ethernet/IP or EtherCAT backbones.

Technical Specifications

Parameter Specification
Manufacturer Beckhoff Automation
Model Number KS6771
Interface Type MP-Bus Master (1 Channel)
Data Transfer Rate 1200 baud
Bus Access Protocol Polling
Nominal System Voltage 24 V DC (-15% / +20%)
K-Bus Current Consumption Typically 55 mA
Power Contact Consumption Typically 10 mA + actuator load
Maximum Power Contact Load 10 A
Isolation Voltage 500 V (K-bus to MP-Bus line)
Process Image Width 12 bytes input, 12 bytes output
Connection Cross-Section 0.08 to 1.5 mm² (AWG 28...16 solid/stranded; AWG 26...16 flexible)
Wire Stripping Length 9 to 10 mm
Environmental Rating IP20 (with variable installation orientation)
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Relative Humidity 95% non-condensing
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Explosion Protection Marking II 3 G Ex nA IIC T4 Gc (ATEX Zone 2)
Housing Material Polycarbonate (terminal housing with pluggable wiring)
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Product Net Weight Approximately 85 g
Shipping Weight (Calculated) 1.5 kg

Connections and Interfaces

Terminal Pin Number Signal Assignment Description
1 MP-Bus Line Bidirectional communications line to Belimo slave actuators.
2 24 V DC (Power Contact) Power feed to drive units (internally bridged to power contact).
5 GND (MP-Bus Reference) Common reference potential for MP-Bus communication.
6 0 V DC (Power Contact) Negative power rail reference (internally bridged to power contact).

Empirical Engineering Insights

Alternative Models & Compatibility

The KS6771 is direct operational equivalent to the standard KL6771 Bus Terminal. The critical difference lies in the "KS" terminal housing design, which includes a pluggable wiring block. From a software perspective, the TwinCAT hardware configuration treats the KS6771 identically to the KL6771, enabling seamless drop-in replacements in existing PLC programs without necessitating code modifications or IO mapping updates.

Application Pitfalls & Engineering Notes

When deploying the KS6771, engineers must monitor total current consumption on the external 24 V DC supply loop. The terminal relies on internal power contacts rated for a maximum of 10 A. If several heavy damper drives are powered directly through the bus terminal, ensure the combined peak inrush currents do not exceed this threshold. For installations spanning long physical distances, use shielded twisted-pair cables to mitigate inductive noise coupling, which can disrupt the 1200-baud polling cycles.

Commissioning & Wiring Tips

To configure the bus terminal within the TwinCAT environment, the Tc2_MPBus library must be integrated into the PLC project. When addressing Belimo devices, remember that the MP-Bus allows 8 active control drives and 8 passive sensors. When inserting stranded field conductors, use the pluggable tension-clamp release slot with a standard flat-head screwdriver (3.0 mm blade size) to avoid damaging the polycarbonate terminal guide locks.

Installation Guidelines

CRITICAL WARNING: Prior to installing, removing, or wiring the KS6771 terminal, completely de-energize the main system controller and all auxiliary 24 V power feeds. Failure to isolate power may cause communication bus disruption or permanent damage to the solid-state K-bus interface electronics.
1
Mount the terminal on a standard 35 mm DIN rail conforming to EN 60715, ensuring the lock mechanism snaps firmly into place.
2
Slide adjacent terminals together, using the integrated double slot and key connection for side-by-side electrical contact.
3
Prepare field wires by stripping insulation precisely to 9–10 mm, avoiding loose strands that could cross-contact neighboring terminals.
4
Insert field wiring into the pluggable tension clamps, using a spring-release screwdriver tool to lock each wire securely into position.

What is the primary difference between the Beckhoff KS6771 and KL6771 terminals?

The KS6771 features a pluggable wiring level, enabling the field wiring block to be removed and plugged back on as a single assembly. The KL6771 uses fixed, non-removable terminal block connections.

How many Belimo actuator drives can I connect to a single KS6771 module?

The terminal supports a maximum of 16 MP-Bus devices, which is architecturally split into up to 8 drives and 8 sensors.

What software library is required to program this terminal in TwinCAT?

Integration requires the TwinCAT PLC MP-Bus library (typically Tc2_MPBus for TwinCAT 3), which provides dedicated function blocks for communication and device polling.

Is the KS6771 rated for use in hazardous locations?

Yes, it has ATEX approval with marking II 3 G Ex nA IIC T4 Gc, making it suitable for installation in Zone 2 hazardous areas.

Globális expressz szállítás

  • Normál szállítás: 4-6 munkanap a DHL, FedEx és UPS szolgáltatásával.
  • Gyors kiszállítás: A raktáron lévő, 14:00 (GMT+8) előtt leadott megrendeléseket aznap feladjuk.
  • Világszintű lefedettség: Több mint 150 országban szolgálunk ki, beleértve a gyors szállítást Szaúd-Arábiába és az Egyesült Arab Emírségekbe.

Visszaküldés és garancia

  • 30 napos garancia: Csak a raktáron lévő termékek eredeti, gyári zárt csomagolásban történő visszaküldését fogadjuk el.
  • 12 hónapos garancia: Minden ipari alkatrészünket szakmai műszaki garancia védi.

A megrendeléseket hétfőtől péntekig dolgozzuk fel és szállítjuk (állami ünnepnapok kivételével).


A teljes jogosultság, a készletfeltöltési díjak és a nemzetközi visszaküldési részletek megtekintéséhez kérjük, tekintse meg hivatalos oldalunkat Visszatérítési és Visszaküldési Szabályzat .

TECHNICAL SPECIFICATIONS

Country of origin
Németország

Nemrég megtekintett termékek

Műszaki ismeretek

Elektromos működtetők, amelyek a folyadékenergia-rendszereket váltják ki: Gyakorlati ipari automatizálási útmutató

Ez a cikk bemutatja, hogyan alakítják át az integrált elektromos működtetők, például az SMC e-Actuator sorozata, az ipari mozgásvezérlést azáltal, hogy kiváltják a hagyományos pneumatikus és...

Matematikai műveletek OpenPLC-vel ipari automatizálási alkalmazásokhoz

Ez a cikk bemutatja, hogyan hajtanak végre a PLC rendszerek alapvető matematikai műveleteket, mint az összeadás, kivonás, szorzás, osztás, modulo és hatványozás az ipari automatizálásban. Megmutatja,...

Fejlett Boole-logika FBD PLC programozással: Gyakorlati ipari alkalmazások a alapvető logikán túl

A cikk több fejlett Boole-logikai függvényt ismertet, amelyeket a PLC programozásban használnak az alapvető ÉS, VAGY és NEM műveleteken túl. Bemutatja, hogyan alkalmazhatók olyan eszközök, mint az...

Boole-logika a PLC programozásban: Az FBD logikai kapuk megértése

A Boole-logika minden PLC program alapja. Az egyszerű gépvezérlésektől a bonyolult ipari automatizálási rendszerekig a logikai kapuk határozzák meg, hogyan reagálnak a vezérlők a változó bemenetekre...

Részletes útmutató az ipari tűzfalakról és az OT hálózati szegmentációról

Az ipari tűzfalak kulcsfontosságú szerepet játszanak az OT kiberbiztonságban, védve a PLC, DCS és SCADA hálózatokat szegmentálás, be- és kimeneti forgalom szabályozás, valamint az IEC 62443 elveivel...

Útmutató a robotikus fogókhoz: a finomkezeléstől a nehézüzemi automatizálásig

A modern robotfogók túlmutatnak a hagyományos mechanikus állkapcsokon. A gyíkok tapadó rendszerétől és az élelmiszeripari puha fogóktól az MI-vezérelt raktári eszközökig a fejlett fogástechnológiák...