| Nominal Rated Input Voltage |
120/240 VAC, or 125 VDC |
| Input Voltage Range (AC Sourcing) |
90 to 264 VAC, 47 to 63 Hz operational limits |
| Input Voltage Range (DC Sourcing) |
100 to 150 VDC continuous input window |
| Input Power Draw |
135 watts typical, 160 watts maximum load envelope |
| Input Half Cycle Peak Inrush |
3 amps typical continuous limit |
| Active Power Factor |
Greater than 0.93 continuous at full operational loads |
| Output Power Capacity |
100 watts maximum total combined across all 3 output paths |
| Output Voltage (+5 VDC Rail) |
4.90 to 5.25 volts (5.07 volts nominal reference) |
| Output Voltage (+12 VDC Rail) |
11.75 to 12.6 volts |
| Output Voltage (-12 VDC Rail) |
-12.6 to -11.75 volts |
| Overvoltage Limit (+5 VDC Output) |
5.7 to 6.7 volts shutoff window |
| Overcurrent Limit (+5V Output) |
21 amps typical protection threshold |
| Overcurrent Limit (+12V Output) |
3.5 amps typical protection threshold |
| Overcurrent Limit (-12V Output) |
1.6 amps typical protection threshold |
| Holdup Time Capacity |
21 milliseconds minimum sustained from point of loss of AC input |
| Operating Temperature Range |
0 to 60 Celsius (32 to 140 Fahrenheit) ambient |
| Storage Temperature Range |
-40 to +85 Celsius (-40 to +185 Fahrenheit) ambient |
| Internal Fuse Rating & Type |
2 amp, 250 volt high-capacity safety fuse |
| Terminal Block Screw Torque |
12 in-lb (1.3 N-m) |
| Manufacturer |
GE Fanuc Automation |
| Country of Origin |
USA |
| Shipping Weight (Calculated) |
1.95 kg |
| Package Dimensions (Calculated) |
280 mm x 220 mm x 85 mm |