1 dari 3

GE Fanuc IS420UCSCS2 Mark VIeS UCSC Controller

GE Fanuc IS420UCSCS2 Mark VIeS UCSC Controller

Hanya 3 item tersisa di stok
  • Produsen: General Electric

  • Nomor Produk: IS420UCSDH1

  • Negara asal:Amerika Serikat

  • Jenis Produk: UCSC controller

  • Kode batang: 8537101190

  • Pembayaran: T/T, Western Union

  • Berat: 1200g

  • Dimensi: 210 mm x 160 mm x 55 mm

  • Pelabuhan pengiriman: Xiamen

  • Garansi: 12 bulan

Kuantitas
Lihat detail lengkap

Description

The GE Fanuc IS420UCSCS2 is a specialized standalone controller module developed for the Mark VIeS Safety Control System platform. Powered by a dual-core 1.6 GHz AMD G-Series processor, this single-board controller provides a secure and dedicated processing environment specifically tailored for critical safety loops, emergency shutdown (ESD) networks, and functional safety applications. Unlike general-purpose controllers, the IS420UCSCS2 processes safety-critical voter logic and communicates via specialized safety protocols to ensure high-integrity monitoring and deterministic execution. The module features a compact form factor that integrates communication, processing, and logic handling directly onto a single field-replaceable board, eliminating complex rack interconnections.

Features

  • Dedicated Safety Processing: Specifically engineered as a Mark VIeS Safety controller running safety voter logic rather than standard machine control loops.
  • High-Performance Architecture: Equipped with a dual-core AMD G-Series processor operating at 1.6 GHz to provide fast cycle times and highly predictable, deterministic execution.
  • Hazardous Location Certification: Fully certified for reliable installation and operation within hazardous and demanding industrial environments.
  • Single-Board Efficiency: Combines microprocessors, dual network interfaces, and localized system memory onto a compact hardware layout to increase overall mean time between failures (MTBF).
  • Seamless Fabric Integration: Links natively with Mark VIeS Safety I/O modules over dedicated, redundant Ethernet control networks (IONet) to maintain end-to-end communication safety.

Applications

  • Emergency Shutdown Systems (ESD): Serves as the primary processing node to execute emergency trip and shutdown sequences safely across critical processes.
  • Burner Management Systems (BMS): Provides high-reliability safety sequencing and flame monitoring controls for industrial boilers, furnaces, and thermal oxidizers.
  • Critical Loop Functional Safety: Implements protective monitoring configurations on industrial turbomachinery, fluid systems, and hazardous manufacturing processes where single-point failures must be prevented.

Technical Specifications

Parameter Value / Specification
Manufacturer GE Fanuc / GE Gas Power
Country of Origin United States
Control System Platform Mark VIeS Safety Control System
Processor Type Dual-core AMD G-Series
Processor Speed 1.6 GHz
Nominal Power Input 24.0 V DC / 28.0 V DC (Accepts a range of 18.0 to 30.0 V DC)
Maximum Current Draw 1.1 A DC
Operating Temperature 0 to 65 Celsius (32 to 149 degrees Fahrenheit) ambient
Cooling Convection / Natural air flow
Hazardous Location Ratings Certified for Class I, Division 2 (Groups A, B, C, D); Class I, Zone 2 (Group IIC); ATEX Zone 2
Shipping Weight (Calculated) 1.20 kg (2.65 lbs)
Package Dimensions (Calculated) 210 mm x 160 mm x 55 mm

Installation Guidelines

CRITICAL WARNING:

Before handling or placing the module, isolate and disconnect all control power lines feeding the panel area. Ensure the primary DC power supply harness is completely de-energized. Failure to strictly follow de-energization protocols in hazardous environments can lead to electrical arcing, severe tool-point hazards, or catastrophic failure of safety-critical logic systems.

1
Power Isolation Verification: Before handling or placing the module, isolate and disconnect all control power lines feeding the panel area. Ensure the primary DC power supply harness is completely de-energized.
2
Mechanical Mounting: Seat the module onto its designated panel space or mounting footprint. Tighten the grounding and mounting screws securely to the chassis structure to establish a clean electrical ground loop path.
3
IONet Cable Connection: Attach the high-speed Ethernet interface cables to the dedicated IONet ports. Ensure the RJ-45 connector clips lock firmly in place to support uninterrupted real-time safety network communications.
4
Power Up & Diagnostics: Apply the nominal 24 V DC source to the module. Observe the front panel diagnostic status indicators to verify that the boot sequence completes successfully and that the unit establishes a normal running state without triggering internal safety system faults.

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

GE Fanuc IS420UCSCS2 Mark VIeS UCSC Controller

正在加载 PDF,请稍候…

What core control platform is this specific controller module designed for?

This module is uniquely engineered for the Mark VIeS Safety Control System and is designated to run high-integrity safety voter logic rather than standard corporate machine loops.

What are the structural processor specs and processing capabilities of this unit?

The module utilizes a dual-core AMD G-Series processor operating at 1.6 GHz, providing deterministic cycle execution required for emergency shutdown and burner management tasks.

What is the recommended operational voltage range for the power input terminals?

The unit features a nominal power input rating of 24.0 V DC or 28.0 V DC, but it is engineered to safely accept a broad operating input spectrum ranging from 18.0 to 30.0 V DC.

Is this single-board controller certified for deployment in hazardous industrial spaces?

Yes, it carries hazardous location safety certifications including Class I, Division 2 (Groups A, B, C, D), Class I, Zone 2 (Group IIC), and ATEX Zone 2 environments.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 2:00 PM (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian kembali, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Color pattern
Hitam
Country of origin
Amerika Serikat
Power source
Daya DC

Produk yang Baru Dilihat

Pengetahuan teknis

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Dari sistem perekat yang terinspirasi oleh tokek dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga AI,...

Throwback: Bagaimana Motor Listrik Awal Mengubah Pertambangan Bawah Tanah

Dari kompresor DC yang digerakkan tali hingga gerobak tambang bertenaga baterai, operasi pertambangan awal menandai titik balik dalam elektrifikasi industri. Artikel ini mengeksplorasi bagaimana...

Factory I/O: Alat Simulasi PLC Modern untuk Pelatihan Otomasi Industri

Factory I/O mengubah pendidikan PLC dengan menyediakan simulasi industri 3D yang imersif untuk siswa, insinyur, dan tim pemeliharaan. Platform ini menjembatani kesenjangan antara teori dan praktik...

Pemrograman Siklus Gerakan Sumbu Tunggal pada CMZ Servo Drive

Tutorial ini membahas bagaimana fungsi PLC onboard di dalam drive servo CMZ SBD dapat menjalankan program gerakan mandiri, termasuk logika homing, kontrol posisi, dan pergerakan sumbu siklik tanpa...

Pengaturan Kontrol Gerak Sumbu Tunggal dengan CMZ Servo Drive

Tutorial ini membahas pengoperasian sistem gerak servo satu sumbu menggunakan drive CMZ SBD, meliputi pengaturan perangkat keras, penskalaan sumbu, konfigurasi homing, dan verifikasi gerakan aman...