Regulating analog actuators and control loops within Sysmac PLC architectures is the primary functional role of the Omron CJ1W-DA021. This CJ-series Special I/O Unit provides two high-resolution analog output channels, supporting standard industrial current and voltage ranges. Built with internal photocoupler isolation between the controller backplane and the external interface, this module prevents field electrical noise from corrupting core logic operations. The physical connection is established through an 18-point detachable terminal block with M3 screws, facilitating rapid wiring, commissioning, and simplified hot-swap unit replacement during field maintenance.

Key Features

  • Dual-Channel Output: Supports two independent analog outputs configurable for voltage or current loops.
  • Flexible Signal Ranges: Compatible with standard industry spans including 1 to 5 V, 0 to 5 V, 0 to 10 V, -10 to 10 V, and 4 to 20 mA.
  • High Resolution: Operates at a maximum conversion resolution of up to 40,000 for precise variable control.
  • Photocoupler Isolation: Secure isolation barrier between the internal PLC controller backplane and external output circuitry.
  • Maintenance-Friendly Terminal Block: Detachable 18-point block with M3 screws allows replacement without disconnecting field wiring.

Applications

  • Variable Speed Drive Regulation: Direct frequency and speed commanding for industrial inverters and VFDs.
  • Proportional Valve Control: Modulating flow rates, pneumatic pressures, and hydraulic positions in process loops.
  • HVAC Damper Actuation: Positioning air dampers and control valves based on real-time environmental demands.
  • External Chart Recording: Routing physical process variables to analog instrumentation, displays, or recording units.

Technical Specifications

Parameter Value / Specification
Manufacturer Omron
Model Code CJ1W-DA021
Product Type CJ-series Special I/O Unit (Analog Output Module)
Number of Outputs 2 channels
Output Ranges (Voltage) 1 to 5 V, 0 to 5 V, 0 to 10 V, -10 to 10 V
Output Ranges (Current) 4 to 20 mA
Max Resolution 1/40,000 (Set data: 16-bit binary)
Output Impedance (Voltage) 0.5 Ohm max.
Max Output Current (Voltage) 12 mA (for 1 point)
Max Permissible Load Resistance 600 Ohm (for current output)
Backplane Current Consumption 5 VDC, 120 mA max.
External Power Supply Requirements 24 VDC +10% -15%, 140 mA max. (Inrush: 20 A max., 1 ms min. pulse)
Isolation Method Photocoupler isolation between I/O and controller backplane (No isolation between channels)
External Connections 18-point detachable terminal block (M3 screws)
Unit Weight 0.15 kg
Shipping Weight 1.50 kg (including secure export packaging)

Connections and Interfaces

Terminal Assignment Signal Name Functional Circuit Assignment
V OUT 1 Voltage Output 1 Positive voltage output connection for Channel 1
I OUT 1 Current Output 1 Positive current output connection for Channel 1
COM 1 Output Common 1 Common return terminal for Channel 1
V OUT 2 Voltage Output 2 Positive voltage output connection for Channel 2
I OUT 2 Current Output 2 Positive current output connection for Channel 2
COM 2 Output Common 2 Common return terminal for Channel 2
24 VDC External Power Supply (+) Positive supply terminal for external 24 VDC input
0 VDC External Power Supply (-) Negative/Ground reference for external 24 VDC input

Empirical Engineering Insights

Alternative Models & Compatibility

The CJ1W-DA021 serves as a direct drop-in replacement for older CJ1W-DA021 revision versions. When planning retrofits from older Sysmac platforms (such as the C200H series), direct logic mapping is required because of backplane addressing variations. Ensure your CJ1G, CJ1H, or CJ2H CPU unit has been allocated corresponding DM and CIO Area channels using CX-Programmer or Sysmac Studio software to match the unit's rotary physical address switches.

Application Pitfalls & Engineering Notes

A key layout constraint is that no isolation exists between output channels 1 and 2. Both channels share a common internal ground point. If you connect this module to two field devices that are separately grounded at different physical points, ground loops can form, causing signal drift or module damage. To prevent this, always route outputs to devices with internally isolated inputs, or add physical external loop isolators between the module and any non-isolated field targets.

Commissioning & Wiring Tips

Ensure that the external 24 VDC power supply is fully active before or simultaneously with the PLC CPU backplane startup. If the external 24 VDC drops below the -15% tolerance limit (20.4 VDC), the module's orange status indicator will trip, and an I/O verification error will register at the processor level. Always use shielded, twisted-pair cables for analog routing and ground the shield only at the PLC chassis ground terminal to avoid ambient RF noise infiltration.

Installation Guidelines

CRITICAL WARNING

Disconnect all electrical power to the PLC rack and field-side circuits before physically attaching or removing this Special I/O Unit. Failure to completely de-energize the assembly can destroy internal components or cause erratic PLC CPU behavior.

1

Set the unit number rotary dials on the front panel of the CJ1W-DA021 to the desired address (0 to 95) prior to mounting. Avoid duplicating unit numbers across the PLC backplane.

2

Align the upper and lower track hooks of the module with the adjacent rack unit, slide the unit securely into position, and engage the locking slide clamps on the top and bottom of the CJ-series rack.

3

Wire the 18-point detachable terminal block with crimped M3 terminals, ensuring positive 24 VDC external supply connections are completed before powering on the system.

Loading product navigation…

Does the CJ1W-DA021 provide isolated outputs between individual channels?

No. The module provides optical isolation between the controller backplane and the overall analog circuit, but the individual output channels (Channel 1 and Channel 2) share a common internal return line (COM) and are not isolated from each other.

What behavior occurs if the external 24 VDC power supply drops out?

If external 24 VDC power is disconnected or falls below the minimum limit (20.4 VDC), the module will deactivate its analog outputs, the orange status indicator will illuminate, and the host PLC CPU will trigger a Special I/O Unit error.

How is the CJ1W-DA021 address configured in the PLC software?

The module unit number is set manually using the front-panel rotary switches. The PLC CPU reserves memory blocks in the Special I/O Unit CIO and DM areas corresponding directly to this hardware address, where configuration parameters are written via CX-Programmer.

Can I use voltage and current outputs simultaneously on the CJ1W-DA021?

Yes. Each channel is configured independently in the PLC memory settings, and you can wire Channel 1 for a current loop (such as 4-20 mA) while wiring Channel 2 for a voltage loop (such as 0-10 V) using the dedicated V OUT and I OUT terminals.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman pada hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 14:00 (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian ulang, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Jepang

Produk yang Baru Dilihat

Pengetahuan teknis

Operasi Matematika Menggunakan OpenPLC untuk Aplikasi Otomasi Industri

Artikel ini menjelaskan bagaimana sistem PLC melakukan operasi matematika inti seperti penjumlahan, pengurangan, perkalian, pembagian, modulo, dan perpangkatan dalam otomasi industri. Artikel ini...

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Mulai dari sistem adhesif yang terinspirasi oleh cicak dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga...

Kilasan Masa Lalu: Bagaimana Motor Listrik Awal Mengubah Pertambangan Bawah Tanah

Dari kompresor DC yang digerakkan tali hingga gerobak tambang bertenaga baterai, operasi pertambangan awal menandai titik balik dalam elektrifikasi industri. Artikel ini mengeksplorasi bagaimana...