Omron DRT2-AD04 DRT2 Analog Input Terminal

Omron DRT2-AD04 DRT2 Analog Input Terminal

Hanya 7 item tersisa di stok
  • Produsen: Omron

  • Nomor Produk: DRT2-AD04

  • Negara asal:Jepang

  • Jenis Produk: Analog Input Terminals

  • Pembayaran: T/T, Western Union

  • Berat: 200g

  • Dimensi: 5 cm x 4.97 cm x 11.5 cm

  • Pelabuhan pengiriman: Xiamen

  • Garansi: 12 bulan

Jumlah
Lihat detail lengkap

Description

Distributed control environments requiring high-precision analog integration rely on the DRT2-AD04 analog input terminal to interface physical sensors with industrial networks. Operating as a DeviceNet smart slave, this module provides four distinct channels of configurable analog inputs, accommodating standard current loop and voltage signals to interface with Sysmac CJ/NJ Series automation platforms.

The module incorporates onboard diagnostic tools designed to simplify preventative maintenance. Users can monitor conversion status, detect sensor disconnection scenarios, and configure scaling and alarm thresholds directly via DeviceNet parameterization. Its localized smart features reduce the computational load on the host PLC by processing high-limit, low-limit, and peak-hold monitoring directly at the slave level.

Features

  • Four independent analog input points supporting both voltage and current operating modes.
  • Flexible analog signal selection: 0 to 5 V, 1 to 5 V, 0 to 10 V, -10 to 10 V, 0 to 20 mA, and 4 to 20 mA.
  • Fast analog-to-digital conversion cycle configurable from 1 to 4 active channels, achieving a maximum conversion cycle of 4 ms for all 4 channels.
  • High-precision 1/6,000 full-scale resolution ensuring accurate data rendering for sensitive industrial measurements.
  • Convenient bus-powered operation, drawing a maximum of 90 mA from the DeviceNet communications power supply.
  • Robust diagnostic suite providing sensor wire-break detection, value monitoring, and operational statistics tracking.

Applications

  • Distributed process control utilizing pressure transmitters, flow sensors, and level indicators.
  • Remote telemetry and signal aggregation in multi-zone manufacturing environments.
  • Integration with CJ/NJ Series PLC networks for high-speed automated processing.

Technical Specifications

ParameterSpecification
Manufacturer Omron
Model/Part Number DRT2-AD04
Series DRT2 Smart Slaves
Analog Inputs 4 points
Input Voltage Ranges 0 to 5 V, 1 to 5 V, 0 to 10 V, -10 to 10 V
Input Current Ranges 0 to 20 mA, 4 to 20 mA
AD Conversion Cycle 4 ms max. (with 4 channels active; adjustable from 1 to 4 points)
AD Conversion Data (Unipolar) 0000 to 1770 hex (for 0-5 V, 1-5 V, 0-10 V, 0-20 mA, 4-20 mA)
AD Conversion Data (Bipolar) F448 to 0BB8 hex (for -10 to 10 V)
Resolution 1/6,000 (full scale)
Power Supply Source DeviceNet communications power supply
Current Consumption 90 mA max.
Compatible Controllers CJ Series, NJ Series
Maximum Message Length 542 bytes
Dimensions (H x W x D) 5 cm x 4.97 cm x 11.5 cm
Weight 0.2 kg

Installation Guidelines

  • Mount the terminal securely on standard 35 mm DIN rail in a clean, dry control panel enclosure.
  • Always use shielded twisted-pair (STP) cabling for analog signals to minimize high-frequency electromagnetic interference.
  • Ensure that the DeviceNet communications power supply is appropriately rated and stable before initializing network traffic.
  • Isolate low-voltage signal wiring from high-voltage AC motor and power distribution cabling.
Loading product navigation…

What analog input signals does the Omron DRT2-AD04 support?

The module supports voltage signals (0 to 5 V, 1 to 5 V, 0 to 10 V, -10 to 10 V) and current loop signals (0 to 20 mA, 4 to 20 mA).

Does the DRT2-AD04 require an external 24 VDC power supply?

No, the module is bus-powered directly through the DeviceNet communications power supply network, drawing a maximum of 90 mA.

How fast is the analog-to-digital conversion on this terminal?

The conversion speed is a maximum of 4 ms for all four channels. You can shorten this conversion cycle by disabling unused input points (configurable from 1 to 4 points).

What is the resolution of the DRT2-AD04 digital conversion?

The terminal features a highly accurate resolution of 1/6,000 of the full scale.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman pada hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 14:00 (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian ulang, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Jepang

Produk yang Baru Dilihat

Pengetahuan teknis

Aktuator Listrik yang Dirancang untuk Menggantikan Sistem Tenaga Fluida: Panduan Praktis Otomasi Industri

Artikel ini menjelaskan bagaimana aktuator listrik terintegrasi, seperti seri e-Actuator dari SMC, mengubah kontrol gerak industri dengan menggantikan sistem pneumatik dan hidrolik tradisional....

Operasi Matematika Menggunakan OpenPLC untuk Aplikasi Otomasi Industri

Artikel ini menjelaskan bagaimana sistem PLC melakukan operasi matematika inti seperti penjumlahan, pengurangan, perkalian, pembagian, modulo, dan perpangkatan dalam otomasi industri. Artikel ini...

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Mulai dari sistem adhesif yang terinspirasi oleh cicak dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga...