Integrating legacy serial instruments and third-party peripherals into modern Sysmac architectures is streamlined using the Omron NX-CIF210. This high-density serial communications interface unit expands the capabilities of NX-series I/O systems and NJ/NX CPU racks by adding two independent, non-isolated RS-232C ports. Operating primarily under "No-protocol" transmission modes, it allows raw ASCII or hexadecimal data exchange with devices such as barcode readers, weight scales, and industrial sensors, without requiring complex protocol stacks.

Features

  • Dual-Channel Interface: Equipped with two independent RS-232C communication channels utilizing industry-standard D-Sub 9-pin connectors.
  • Flexible Architecture: Mounts seamlessly to NX-series EtherCAT Coupler Units or directly to compatible NX-series Controller Units.
  • High-Speed Bus Sync: Synchronizes serial data buffering with the internal NX-bus cycle for deterministic control execution.
  • Simplified Configuration: Full setup, baud rate adjustment, and diagnostics integrated directly within the Sysmac Studio software environment.
  • Space-Saving Profile: Compact 30 mm housing width reduces overall footprint inside electrical control panels.

Applications

  • Connecting factory-floor barcode scanners and handheld RFID readers.
  • Interfacing with precision electronic weigh scales and laboratory instruments.
  • Establishing serial point-to-point links with legacy HMIs or display panels.
  • Data acquisition from temperature controllers and flow meters via serial command sets.

Technical Specifications

Specification Parameter Value / Detail
Manufacturer Omron
Model Number NX-CIF210
Product Series NX Series I/O System
Module Type Serial Communications Interface Unit
Number of Ports 2
Physical Interface RS-232C (D-Sub 9-pin Female connectors)
Communications Protocol No-protocol (Host Link support available depending on master controller configuration)
Isolation Method No isolation (between ports or internal bus circuits)
Product Dimensions 100 mm (H) x 30 mm (W) x 71 mm (D)
Net Weight 0.091 kg (91 grams)
Shipping Weight (Calculated) 1.50 kg (including commercial protective packaging)
Country of Origin Japan

Connections and Interfaces

The unit features two front-facing 9-pin D-sub connectors. The pin assignment conforms to standard RS-232C signal layouts:

Pin Number Signal Abbreviation Signal Direction Description
1 CD Input Carrier Detect
2 RDD (RXD) Input Receive Data
3 SDR (TXD) Output Transmit Data
4 DTR Output Data Terminal Ready
5 SG -- Signal Ground
6 DSR Input Data Set Ready
7 RTS Output Request to Send
8 CTS Input Clear to Send
9 RI Input Ring Indicator

Alternative Models & Compatibility

For installations requiring screwless push-in clamping terminals instead of D-Sub 9 connectors, the NX-CIF101 provides a single-channel RS-232C port. If RS-422A or RS-485 serial communication is required, the NX-CIF105 should be selected instead. Confirm firmware compatibility inside Sysmac Studio when mixing older unit revisions with newer NX1P2 or NX102 series controllers.

Application Pitfalls & Engineering Notes

Because this module is non-isolated, ensure that both the NX-series system ground and the ground of the connected RS-232C device are at identical electrical potentials. Significant potential differences can cause ground loop currents, resulting in communication errors or permanent damage to the module's transceiver IC. To preserve signal integrity, the maximum allowable cable length for RS-232C connections is strictly 15 meters.

Commissioning & Wiring Tips

When assembling custom RS-232C cables, always connect the cable shield to the metal hood of the D-Sub connector on the NX-CIF210 end only. This path routes high-frequency noise directly to the DIN rail ground system. If communication failures occur during startup, use the Sysmac Studio monitoring tools to verify if the frame length matches the buffer configuration set in the memory allocation table.

Installation Guidelines

CRITICAL WARNING

Always completely isolate the 24 VDC control power supply to the NX-bus and any connected serial devices before mounting, sliding, or unmounting the unit. Failure to fully de-energize the assembly can cause backplane communication lockouts or damage the internal bus contacts.

1

Align the interlocking guide rails of the NX-CIF210 with the adjacent NX unit on the DIN rail and slide the module together until the side lock click is engaged.

2

Hook the bottom mounting latch to the DIN rail and apply light upward pressure until the module locks firmly into place.

3

Insert the D-Sub 9-pin connector cables and hand-tighten the retaining screws to prevent loose contacts and maintain a continuous shield path.

Loading product navigation…

Can the NX-CIF210 be used for Modbus-RTU master communication?

Yes. When configured under Sysmac Studio and paired with an appropriate Omron CPU (such as the NX1P2 or NJ series), the unit supports Modbus-RTU master communication by utilizing dedicated system function blocks for serial send and receive.

How does the NX-CIF210 differ from the NX-CIF101?

The NX-CIF210 features two independent RS-232C channels terminated in standard D-Sub 9-pin female connectors. The NX-CIF101 features a single RS-232C channel terminated with screwless push-in clamping terminals.

Is there electrical isolation between the two RS-232C ports?

No, the two RS-232C ports on the unit are not electrically isolated from each other or from the internal NX-bus. Proper grounding and equipotential bonding are required to avoid ground loops.

What is the maximum cable length supported by this module?

Consistent with RS-232C standard specifications, the maximum cable run length from the unit to any connected peripheral is 15 meters.

Pengiriman Ekspres Global

  • Pengiriman Standar: 4-6 Hari Kerja melalui DHL, FedEx, dan UPS.
  • Pengiriman Ekspres: Pengiriman pada hari yang sama untuk pesanan dalam stok yang dilakukan sebelum pukul 14:00 (GMT+8).
  • Cakupan Seluruh Dunia: Melayani lebih dari 150 negara, termasuk pengiriman cepat ke Arab Saudi dan UAE.

Pengembalian & Garansi

  • Jaminan 30 Hari: Pengembalian diterima untuk produk yang tersedia dalam stok dengan kemasan asli yang tersegel pabrik.
  • Garansi 12 Bulan: Setiap komponen industri didukung oleh garansi teknis profesional kami.

Pesanan diproses dan dikirimkan Senin-Jumat (tidak termasuk hari libur nasional).


Untuk kelayakan penuh, biaya pengisian ulang, dan detail pengembalian internasional, silakan lihat resmi kami Kebijakan Pengembalian & Pengembalian Dana .

TECHNICAL SPECIFICATIONS

Country of origin
Jepang

Produk yang Baru Dilihat

Pengetahuan teknis

Aktuator Listrik yang Dirancang untuk Menggantikan Sistem Tenaga Fluida: Panduan Praktis Otomasi Industri

Artikel ini menjelaskan bagaimana aktuator listrik terintegrasi, seperti seri e-Actuator dari SMC, mengubah kontrol gerak industri dengan menggantikan sistem pneumatik dan hidrolik tradisional....

Operasi Matematika Menggunakan OpenPLC untuk Aplikasi Otomasi Industri

Artikel ini menjelaskan bagaimana sistem PLC melakukan operasi matematika inti seperti penjumlahan, pengurangan, perkalian, pembagian, modulo, dan perpangkatan dalam otomasi industri. Artikel ini...

Logika Boolean Lanjutan dengan Pemrograman FBD PLC: Aplikasi Industri Praktis di Luar Logika Dasar

Artikel ini menjelaskan beberapa fungsi logika Boolean lanjutan yang digunakan dalam pemrograman PLC selain operasi dasar AND, OR, dan NOT. Artikel ini membahas bagaimana alat seperti tabel...

Logika Boolean dalam Pemrograman PLC: Memahami Gerbang Logika FBD

Logika Boolean adalah dasar dari setiap program PLC. Dari kontrol mesin sederhana hingga sistem otomasi industri yang kompleks, gerbang logika menentukan bagaimana pengendali merespons perubahan...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Jaringan OT

Firewall industri memainkan peran penting dalam keamanan siber OT, melindungi jaringan PLC, DCS, dan SCADA melalui segmentasi, kontrol masuk/keluar, dan integrasi IDS/IPS yang sesuai dengan prinsip...

Panduan Gripper Robotik: Dari Penanganan Halus hingga Otomasi Berat

Gripper robot modern berkembang melampaui rahang mekanis tradisional. Mulai dari sistem adhesif yang terinspirasi oleh cicak dan gripper lembut yang aman untuk makanan hingga alat gudang bertenaga...