Description

Processing industrial automation logic directly at the control level, the Beckhoff CX5130-0100 acts as a fanless, DIN-rail mountable control controller equipped with a dual-core Intel Atom E3827 processor running at 1.75 GHz. Designed to execute complex PLC, visualization, and motion control tasks within space-constrained control cabinets, this industrial PC features integrated, hardware-level automatic detection for both E-bus (EtherCAT) and K-bus (Bus Terminals) physical I/O slices. The system includes 4 GB of internal DDR3 RAM and dual independent Gigabit Ethernet ports, facilitating robust division between OT and IT communication lines. An integrated 1-second UPS leverages onboard ultra-capacitors to guarantee secure persistence of critical operational variables directly to the CFast card slot during unexpected power failures.

Key Features

  • Intel Atom E3827 CPU: Dual-core processing architecture clocked at 1.75 GHz for highly deterministic execution cycles.
  • 4 GB DDR3 RAM: High-speed internal system memory optimized for heavy automation runtimes and local visual processing.
  • Dual Storage Slots: Accommodates one CFast card and one microSD card to isolate operating system installations from application data logging.
  • Integrated 1-Second UPS: Automatically writes up to 1 MB of persistent variables to the flash media upon detection of main supply loss.
  • Hybrid I/O Backplane: Built-in automatic identification of connected E-bus (EtherCAT Terminals) or K-bus (standard Bus Terminals) systems.
  • Comprehensive Connectivity: Equipped with 2 x RJ45 Gigabit Ethernet ports, 1 x DVI-I display interface, and 4 x USB 2.0 peripheral ports.

Applications

  • High-speed EtherCAT-based synchronized multi-axis motion control systems.
  • Industrial IoT gateways bridging fieldbus communication networks with cloud-level architectures.
  • Compact localized visual machine-to-machine control panels requiring direct, high-definition DVI output.
  • Heavy-duty assembly and packaging machine automation requiring reliable, fanless execution in harsh thermal environments.

Technical Specifications

Parameter Specification Values
Manufacturer BECKHOFF
Model / Article Number CX5130-0100
Processor Intel Atom E3827, 1.75 GHz, Dual-Core
System Memory 4 GB DDR3 RAM (Non-expandable)
Storage Slots 1 x CFast card slot, 1 x microSD card slot (Cards not included)
Persistent Storage Integrated 1-second UPS (Saves up to 1 MB of data to CFast)
Communication Interfaces 2 x RJ45 10/100/1000 Mbit/s, 1 x DVI-I, 4 x USB 2.0
Power Supply Input 24 V DC (-15% / +20%)
Current Feed E-bus/K-bus 2 A maximum
Power Consumption 14 W (Typical) / 20 W (While charging internal UPS)
System Diagnostics 1 x Power, 1 x TC Status, 1 x Flash Access, 2 x Bus Status LEDs
Operating System No operating system pre-installed
Control Software No TwinCAT pre-installed
TwinCAT 3 Platform Level Performance (Level 40)
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Protection Class IP20
Physical Dimensions 142 mm x 100 mm x 92 mm (W x H x D)
Unit Weight 1095 g
Shipping Weight (Calculated) 3.0 kg

Connections and Interfaces

Interface ID Connector Type Functional Assignment / Wiring Circuit
X101 / X102 RJ45 Dual independent Gigabit Ethernet interfaces for OT/IT control connection.
X201 DVI-I Visual output for displays/HMIs (supports analog VGA via adapter).
USB 1...4 USB Type-A 4 x USB 2.0 ports for mouse, keyboard, or system diagnostic storage devices.
X401 Power Connector Primary 24 V DC power input connection point, functional ground, and I/O bus power lines.

Empirical Engineering Insights

Alternative Models & Compatibility

The CX5130-0100 is a blank hardware configuration, meaning it does not include a pre-installed operating system or TwinCAT runtime license. This specific variant is standard for systems integrators who intend to load specialized, lightweight Linux kernels or who possess existing TwinCAT licenses to install manually. For applications requiring an out-of-the-box Windows environment, look to the CX5130-0120 (Windows Embedded Compact 7) or the CX5130-0150 (Windows 10 IoT Enterprise) modules to minimize setup preparation.

Application Pitfalls & Engineering Notes

While the integrated 1-second UPS utilizes highly durable, maintenance-free ultra-capacitors instead of standard lead-acid or lithium chemistry, it is only engineered to support the preservation of up to 1 MB of marked persistent variables (VAR PERSISTENT) during a sudden power event. It does *not* provide backup power to continue operating the CPU or visual interface. If you run complex disk-write processes or databases on the system, ensure your applications are optimized to handle sudden shutdowns without corrupting primary CFast partition tables. Always specify industrial-grade Beckhoff CFast cards with high write-endurance metrics to guarantee system stability.

Commissioning & Wiring Tips

When powering a mixed stack of standard K-bus and high-performance E-bus terminals, verify the total current draw of your slice terminals. Although the CX5130-0100 is capable of supplying up to 2 A directly to the internal terminal bus, high-density analog modules or high-frequency digital units can quickly exceed this rating. If your aggregate current calculation exceeds 2 A, you must isolate the bus power and insert a dedicated power feed terminal (such as an EL9410) down-line to maintain stable terminal bus communication. Always hook up the functional earth (FE) terminal on the primary CX power supply block directly to your main backplate ground busbar to minimize high-frequency electromagnetic interference.

Installation Guidelines

CRITICAL SAFETY WARNING

Isolate all high-voltage and low-voltage field power distribution lines prior to mounting or dismounting the hardware. Failure to switch off the 24 V DC power supply line can lead to electrical arcing, which damages the internal terminal contact pins and risks immediate diagnostic processor failure on the main unit.

1

Mount the CX5130 unit securely on an grounded, horizontal DIN rail (EN 60715, 35 mm) by locking the lower mounting latches firmly onto the rail geometry.

2

Insert a compatible, formatted CFast card loaded with your chosen operating system and execution software into the primary drive bay located beneath the cover door.

3

Align and connect the terminal block slices (E-bus or K-bus) onto the right-hand bus interface. Verify that the interlocking lateral locking mechanisms engage fully with a click sound.

4

Connect the 24 V DC input wires to the front X401 terminal block. Tighten the wire cage clamps securely and ground the chassis via the functional earth tab to ensure proper noise immunity.

Loading product navigation…

Does the CX5130-0100 come pre-loaded with an operating system?

No, this specific model (CX5130-0100) is shipped as a bare hardware unit with no pre-installed operating system or TwinCAT software licenses. Users must install their own OS or purchase software options separately.

Can I expand the onboard 4 GB DDR3 RAM on this unit?

No, the 4 GB DDR3 RAM memory configuration on the CX5130-0100 is integrated directly onto the motherboard and is not expandable or upgradeable.

How does the built-in 1-second UPS function on this controller?

The integrated 1-second UPS utilizes internal ultra-capacitors to provide brief backup power upon a main supply failure. It keeps the CPU active just long enough to save up to 1 MB of specified persistent variables directly to the CFast card to prevent data corruption.

Does this controller support both K-bus and E-bus terminals?

Yes. The CX5130-0100 features intelligent, automatic hardware-level identification. It automatically recognizes whether E-bus (EtherCAT) or K-bus (standard bus terminals) terminal slices are connected to its right-hand side and adjusts communication protocols accordingly.

Penghantaran Ekspres Global

  • Penghantaran Standard: 4-6 Hari Perniagaan melalui DHL, FedEx, dan UPS.
  • Penghantaran Ekspres: Penghantaran pada hari yang sama untuk pesanan dalam stok yang dibuat sebelum 2:00 PM (GMT+8).
  • Liputan Seluruh Dunia: Berkhidmat di lebih 150 negara, termasuk penghantaran pantas ke Arab Saudi dan UAE.

Pemulangan & Jaminan

  • Jaminan 30 Hari: Pemulangan diterima untuk produk dalam stok dalam pembungkusan asal yang disegel kilang.
  • Jaminan 12 Bulan: Setiap komponen industri disokong oleh jaminan teknikal profesional kami.

Pesanan diproses dan dihantar Isnin-Jumaat (tidak termasuk cuti umum).


Untuk kelayakan penuh, yuran penyimpanan semula, dan butiran pemulangan antarabangsa, sila lihat rasmi kami Polisi Pemulangan & Bayaran Balik .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknikal

Logik Boolean Lanjutan dengan Pengaturcaraan PLC FBD: Aplikasi Industri Praktikal Melebihi Logik Asas

Artikel ini menerangkan beberapa fungsi logik Boolean lanjutan yang digunakan dalam pengaturcaraan PLC selain operasi asas AND, OR, dan NOT. Ia merangkumi bagaimana alat seperti jadual kebenaran,...

Logik Boolean dalam Pengaturcaraan PLC: Memahami Pintu Logik FBD

Logik Boolean adalah asas bagi setiap program PLC. Dari kawalan mesin yang mudah hingga sistem automasi industri yang kompleks, pintu logik menentukan bagaimana pengawal bertindak balas terhadap...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan Pengapit Robotik: Dari Pengendalian Halus ke Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...

Throwback: Bagaimana Motor Elektrik Awal Mengubah Perlombongan Bawah Tanah

Dari pemampat DC yang digerakkan tali ke troli lombong bertenaga bateri, operasi perlombongan awal menandakan titik perubahan dalam elektrifikasi industri. Artikel ini meneroka bagaimana motor...

Factory I/O: Alat Simulasi PLC Moden untuk Latihan Automasi Industri

Factory I/O sedang mengubah pendidikan PLC dengan menyediakan simulasi industri 3D yang mendalam untuk pelajar, jurutera, dan pasukan penyelenggaraan. Platform ini merapatkan jurang antara teori dan...