Description

Designed for high-precision temperature sensing in distributed control architectures, the Beckhoff EJ3202 is a dual-channel EtherCAT plug-in module designed for direct mounting on application-specific signal distribution boards. This space-saving module enables direct connection of Resistance Temperature Detectors (RTD) using 2-wire or 3-wire cabling methods. By supporting a broad range of RTD sensors like Pt100, Pt1000, and Ni100, the module delivers highly accurate temperature measurement capabilities directly into the EtherCAT communication network, making it highly suitable for demanding industrial machinery and automation environments.

Features

  • Two independent channels for RTD input.
  • Supports 2-wire and 3-wire connection configurations (2-wire as default).
  • Compatible with a wide array of temperature sensors: Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, and KTY sensors.
  • Integrated digital filter and configurable limit value monitoring for enhanced process control.
  • Direct installation onto EJ-series signal distribution boards, minimizing wiring complexity and footprint.
  • Provides 500 V electrical isolation between the E-bus and field potential.

Applications

  • Machinery and equipment manufacturing with customized signal boards.
  • Industrial furnace and HVAC control systems.
  • Process manufacturing requiring precise thermal profiling.
  • Food and beverage production lines requiring clean, distributed I/O installations.

Technical Specifications

Manufacturer Beckhoff
Part Number / Model EJ3202
Technology Temperature measurement (RTD)
Number of Inputs 2
Connection Method 2- or 3-wire (default: 2-wire)
Sensor Types Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer 10 Ohm to 1/4 kOhm), KTY sensors
Measuring Range -200 to +850 degC (Pt sensors); -60 to +250 degC (Ni sensors)
Resolution 0.1 degC per digit
Measurement Error / Uncertainty < +/-0.5 degC for Pt sensors
Input Filter Limit Frequency typ. 1 kHz
Conversion Time approx. 85 ms default setting (2 to 800 ms configurable)
Power Supply via the E-bus
Current Consumption E-bus typ. 165 mA
Electrical Isolation 500 V (E-bus/field potential)
Special Features Integrated digital filter, limit value monitoring, variable connection technology
Weight approx. 30 g
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Relative Humidity 95 %, non-condensing
EMC Immunity/Emission Conforms to EN 61000-6-2/EN 61000-6-4
Vibration/Shock Resistance Conforms to EN 60068-2-6/EN 60068-2-27
Protection Rating IP20

Installation Guidelines

  • Mounting: Ensure the module is properly plugged into the matching application-specific signal distribution board. Confirm latching mechanism is secure before powering the system.
  • Wiring: For 3-wire connections, ensure all lead wires have equal resistance to minimize measuring errors. Keep sensor cables separate from high-voltage motor cables to prevent electromagnetic noise coupling.
  • Thermal Management: Maintain standard operating ambient temperature range of -25 to +60 degC. Ensure adequate clearance for convection cooling inside the enclosure.
  • Grounding: Connect shielding of the RTD cables directly to the ground bus at the entry point of the control panel to minimize external interference.

Compliance and Certifications

  • CE
  • UL
Loading product navigation…

What sensor types are compatible with the Beckhoff EJ3202?

The EJ3202 supports a wide variety of RTD sensors, including Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, KTY sensors, and general resistance measurements (such as potentiometers ranging from 10 Ohm to 1/4 kOhm).

Does the EJ3202 module support 3-wire RTD measurements?

Yes, the EJ3202 supports both 2-wire and 3-wire connection methods. By default, the module is configured for 2-wire connection technology.

What is the typical measurement accuracy of the EJ3202 when using Pt sensors?

The measurement error or uncertainty for the EJ3202 when utilizing standard Pt sensors is less than +/-0.5 degC.

What is the operating temperature range for the Beckhoff EJ3202 plug-in module?

The EJ3202 is rated for an operating temperature range of -25 to +60 degC and a storage temperature range of -40 to +85 degC.

Penghantaran Ekspres Global

  • Penghantaran Standard: 4-6 Hari Bekerja melalui DHL, FedEx, dan UPS.
  • Penghantaran Ekspres: Penghantaran pada hari yang sama untuk pesanan dalam stok yang dibuat sebelum 2:00 PM (GMT+8).
  • Liputan Seluruh Dunia: Berkhidmat di lebih 150 negara, termasuk penghantaran pantas ke Arab Saudi dan UAE.

Pemulangan & Jaminan

  • Jaminan 30 Hari: Pemulangan diterima untuk produk dalam stok dalam pembungkusan asal yang disegel kilang.
  • Jaminan 12 Bulan: Setiap komponen industri disokong oleh jaminan teknikal profesional kami.

Pesanan diproses dan dihantar Isnin-Jumaat (tidak termasuk cuti umum).


Untuk kelayakan penuh, yuran penyimpanan semula, dan butiran pemulangan antarabangsa, sila lihat rasmi kami Polisi Pemulangan & Pengembalian Wang .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknikal

Aktuator Elektrik Direka untuk Menggantikan Cecair: Tutorial Praktikal

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Operasi Matematik Menggunakan OpenPLC untuk Aplikasi Automasi Industri

Artikel ini menerangkan bagaimana sistem PLC melaksanakan operasi matematik teras seperti penambahan, penolakan, pendaraban, pembahagian, modulo, dan perpangkatan dalam automasi industri. Ia...

Logik Boolean Lanjutan dengan Pengaturcaraan FBD PLC: Aplikasi Industri Praktikal Melebihi Logik Asas

Artikel ini menerangkan beberapa fungsi logik Boolean lanjutan yang digunakan dalam pengaturcaraan PLC selain operasi asas AND, OR, dan NOT. Ia merangkumi bagaimana alat seperti jadual kebenaran,...

Logik Boolean dalam Pengaturcaraan PLC: Memahami Pintu Logik FBD

Logik Boolean adalah asas bagi setiap program PLC. Dari kawalan mesin yang mudah hingga sistem automasi industri yang kompleks, pintu logik menentukan bagaimana pengawal bertindak balas terhadap...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan untuk Pengapit Robotik: Dari Pengendalian Halus hingga Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...