Designed for high-precision temperature acquisition within EtherCAT networks, the Beckhoff EL3214 analog input terminal provides direct connection for up to four resistance sensors. This 16-bit resolution module features a highly compact, 12 mm High Density (HD) housing with integrated signal LEDs, saving critical space inside the control cabinet. The terminal dynamically supports both 2-wire and 3-wire connection technologies, ensuring flexible integration with standard RTD sensors including Pt100, Ni100, and various resistance transmitters. Powered directly via the E-bus, it delivers stable, linear measurement results with low noise levels and built-in limit value monitoring.

Key Features

  • Four independent analog input channels designed for RTD and resistance measurements.
  • High-resolution 16-bit analog-to-digital conversion for precise thermal monitoring.
  • Universal compatibility supporting Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, and KTY sensor series.
  • Dynamic 2-wire or 3-wire wiring configurations (configured default as 3-wire).
  • Integrated digital filter and configurable limit value monitoring via CoE registers.
  • Robust electrical isolation of up to 500 V between the E-bus and the signal channels.
  • Space-saving High Density (HD) polycarbonate enclosure equipped with status diagnostic LEDs.

Applications

  • Industrial Thermal Processing: Precise temperature tracking in furnaces, drying ovens, and heat-treatment chambers.
  • HVAC Control Systems: Monitoring of chilled water, supply air, and heating loop temperatures in plant automation.
  • Chemical and Plastics Manufacturing: Real-time temperature control on extruder barrels, injection molding machines, and chemical reactors.
  • Power Generation & Machinery: Monitoring motor bearings, winding temperatures, and oil reservoir thermal profiles.

Technical Specifications

Parameter Specification Value
Manufacturer Beckhoff Automation
Model Reference EL3214
Product Type EtherCAT Terminal (High Density Enclosure)
Number of Inputs 4 channels
Nominal Resolution 16 bit (0.1 degC per digit)
Supported Sensors Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, KTY, and Resistance (10 Ohm to 4 kOhm)
Measuring Range -200 to +850 degC (Pt sensors) / -60 to +250 degC (Ni sensors)
Measurement Error < +/-0.5 degC (Pt sensors in 4x 3-wire operation)
Measuring Current < 0.5 mA (dependent on load/sensor resistance)
Conversion Time approx. 170 ms (default settings)
Input Filter Limit Frequency typ. 1 kHz
Electrical Isolation 500 V (E-bus / signal voltage)
E-Bus Current Consumption typ. 140 mA
Operating Temperature Range -25 to +60 degC
Storage Temperature Range -40 to +85 degC
Relative Humidity 95%, non-condensing
Vibration / Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
Protection Rating / Installation IP20 / variable positions supported
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Product Weight approx. 60 g
Shipping Weight (Calculated) 0.25 kg (including packaging material)
Approvals and Markings CE, UL, DNV GL

Wiring and Terminal Specifications

Conductor Type Cross-Section Range AWG Size Range
Solid Conductor (s) 0.08 to 1.5 mm² AWG 28 to 16
Stranded Conductor (st) 0.25 to 1.5 mm² AWG 22 to 16
Flexible Conductor with Ferrule (f) 0.14 to 0.75 mm² AWG 26 to 19
Stripping Length 8 to 9 mm

Alternative Models & Compatibility

The EL3214 represents a High Density (HD) upgrade path for installations previously utilizing 2-channel temperature modules like the EL3202. While it significantly increases terminal density (4 channels within a 12 mm width), note that the EtherCAT process image mapping differs. Ensure that the corresponding TwinCAT System Manager configurations are refreshed and PLC variables are remapped when migrating older layouts to the EL3214 structure.

Application Pitfalls & Engineering Notes

RTD measurements are highly sensitive to self-heating effects. The EL3214 limits its active measuring current to less than 0.5 mA to keep this error margin negligible. However, when placing sensors in stagnant or poorly conductive fluids, small temperature offsets may occur. If electrical grid interference (50 Hz or 60 Hz) affects signal stability, configure the integrated digital filter via CoE (CANopen over EtherCAT) settings to align with your local AC line frequency to achieve optimal noise rejection.

Commissioning & Wiring Tips

To ensure the rated accuracy of under +/-0.5 degC in 3-wire configurations, all three connection leads must have the identical length, material, and cross-section. Differences in wire resistance between the signal and compensation lines directly introduce systematic offsets. Always use shielded, twisted-pair cabling for long-distance runs and ground the shield immediately at the entry point of the control panel on dedicated grounding rails, ensuring the DIN rail itself has a low-impedance connection to earth ground.

Installation Guidelines

CRITICAL WARNING: Disconnect all power sources from the E-bus and any external signal loops before inserting, removing, or wiring the EL3214 terminal. Failure to completely de-energize the system can cause permanent damage to the internal EtherCAT communication circuitry, leading to bus failure and equipment malfunction.
1

Align the EL3214 terminal with the adjacent EtherCAT module on the standard 35 mm DIN rail (conforming to EN 60715).

2

Press the module firmly down onto the rail until the side double-slot lock and the bottom DIN rail locking mechanism click into place.

3

Prepare conductors to a stripping length of 8 to 9 mm. Insert a flathead screwdriver into the spring actuator slot to open the terminal clamp, push the conductor in, and release the tension to secure.

Loading product navigation…

Can the EL3214 measure standard resistance instead of temperature?

Yes. In addition to standard RTDs, the EL3214 supports raw resistance measurement up to 4 kOhm (e.g., potentiometers) which can be configured within the CANopen over EtherCAT (CoE) register settings.

Does the EL3214 support 4-wire RTD sensor configurations?

No. The EL3214 natively supports 2-wire and 3-wire sensor topologies. If you are using 4-wire RTD sensors, connect them in a 3-wire configuration by leaving one of the return compensation leads disconnected, or upgrade to a dedicated 4-wire module.

How are different sensor types configured on the EL3214?

Sensor selection is managed entirely through the software via the CoE (CANopen over EtherCAT) online directory in TwinCAT. You must set the index register corresponding to each channel to select your specific sensor type, such as Pt100 or Ni1000.

What is the function of the LEDs on the face of the EL3214?

The integrated LEDs provide diagnostic feedback. They indicate the operational status of individual channels, revealing conditions such as broken wires, sensor out-of-range limits, and communication state with the E-bus.

Penghantaran Ekspres Global

  • Penghantaran Standard: 4-6 Hari Bekerja melalui DHL, FedEx, dan UPS.
  • Penghantaran Ekspres: Penghantaran pada hari yang sama untuk pesanan dalam stok yang dibuat sebelum 2:00 PM (GMT+8).
  • Liputan Seluruh Dunia: Berkhidmat di lebih 150 negara, termasuk penghantaran pantas ke Arab Saudi dan UAE.

Pemulangan & Jaminan

  • Jaminan 30 Hari: Pemulangan diterima untuk produk dalam stok dalam pembungkusan asal yang disegel kilang.
  • Jaminan 12 Bulan: Setiap komponen industri disokong oleh jaminan teknikal profesional kami.

Pesanan diproses dan dihantar Isnin-Jumaat (tidak termasuk cuti umum).


Untuk kelayakan penuh, yuran penyimpanan semula, dan butiran pemulangan antarabangsa, sila lihat rasmi kami Polisi Pemulangan & Pengembalian Wang .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknikal

Penggerak Elektrik Direka untuk Menggantikan Sistem Kuasa Cecair: Panduan Automasi Industri Praktikal

Artikel ini menerangkan bagaimana aktuator elektrik bersepadu, seperti siri e-Actuator SMC, mengubah kawalan gerakan industri dengan menggantikan sistem pneumatik dan hidraulik tradisional. Ia...

Operasi Matematik Menggunakan OpenPLC untuk Aplikasi Automasi Industri

Artikel ini menerangkan bagaimana sistem PLC melaksanakan operasi matematik teras seperti penambahan, penolakan, pendaraban, pembahagian, modulo, dan perpangkatan dalam automasi industri. Ia...

Logik Boolean Lanjutan dengan Pengaturcaraan FBD PLC: Aplikasi Industri Praktikal Melebihi Logik Asas

Artikel ini menerangkan beberapa fungsi logik Boolean lanjutan yang digunakan dalam pengaturcaraan PLC selain operasi asas AND, OR, dan NOT. Ia merangkumi bagaimana alat seperti jadual kebenaran,...

Logik Boolean dalam Pengaturcaraan PLC: Memahami Pintu Logik FBD

Logik Boolean adalah asas bagi setiap program PLC. Dari kawalan mesin yang mudah hingga sistem automasi industri yang kompleks, pintu logik menentukan bagaimana pengawal bertindak balas terhadap...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan untuk Pengapit Robotik: Dari Pengendalian Halus hingga Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...