BECKHOFF EL3413 EtherCAT Terminal: 3-Phase Power Measurement

BECKHOFF EL3413 EtherCAT Terminal: 3-Phase Power Measurement

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: EL3413

  • Country of origin:Jerman

  • Product Type: EtherCAT Terminal

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 12 mm x 100 mm x 68 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

The EL3413 is a high-precision, 3-phase EtherCAT Terminal designed for comprehensive power measurement of alternating voltages up to 690 V AC. It is engineered to monitor energy consumption and power quality directly within the EtherCAT system. With its ability to perform harmonic analysis and measure effective, reactive, and apparent power, the EL3413 is an essential component for energy management and grid monitoring applications.

Features

  • 3-Phase Power Measurement: Capable of monitoring 3-phase systems, with optional single-phase operation.
  • Extensive Measured Values: Provides data for current (I1, I2, I3, In), voltage, effective/reactive/apparent power, energy, cos φ, frequency, and harmonic analysis.
  • Galvanic Isolation: High electrical isolation (4500 V) and galvanically isolated current inputs ensure safety and measurement accuracy.
  • Flexible Current Input: Adjustable range for current measurement: 100 mA, 1 A (default), and 5 A.
  • Compact Design: 12 mm wide housing for high-density DIN rail mounting in control cabinets.

Applications

  • Industrial energy monitoring and cost optimization
  • Power quality analysis in electrical grids
  • Monitoring of machinery energy efficiency
  • Preventive maintenance for motor-driven systems

Technical Specifications

Category Specification
Manufacturer BECKHOFF
Model EL3413
Measuring Voltage Max. 690 V AC (3-phase)
Measuring Current Adjustable (100 mA, 1 A, 5 A)
Electrical Isolation 4500 V
Resolution 1 μA, 0.1 mV, 10 mW
Measuring Error 0.5 % (U/I), 1 % (calculated values)
Current Consumption (E-bus) typ. 160 mA
Operating Temperature -25 to +60 degC
Protection Rating IP20
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm

Installation Guidelines

  • Mount on a 35 mm DIN rail (EN 60715) using the integrated lock mechanism.
  • Ensure proper wiring for 3-phase voltage and current inputs, utilizing the spring-actuated terminals for solid or flexible conductors (stripping length 8–9 mm).
  • Adhere to all local electrical safety regulations when connecting high-voltage (up to 690 V AC) circuits.
  • Follow EMC immunity standards (EN 61000-6-2/EN 61000-6-4) for cabinet wiring to prevent electromagnetic interference with power data.
  • Ensure consistent ambient conditions between -25 and +60 degC.

What is the maximum measuring voltage for the EL3413?

It can measure up to 690 V AC in a 3-phase system.

Does the EL3413 perform harmonic analysis?

Yes, it features integrated harmonic analysis as part of its power monitoring capabilities.

What is the adjustable range for the current inputs?

The current measurement range can be adjusted to 100 mA, 1 A (default), or 5 A.

Is the EL3413 suitable for single-phase operation?

Yes, it supports optional single-phase operation in addition to 3-phase measurement.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Putih Kelabu
Country of origin
Jerman

Recently Viewed Products

Technical knowledge

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan Pengapit Robotik: Dari Pengendalian Halus ke Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...

Throwback: Bagaimana Motor Elektrik Awal Mengubah Perlombongan Bawah Tanah

Dari pemampat DC yang digerakkan tali ke troli lombong bertenaga bateri, operasi perlombongan awal menandakan titik perubahan dalam elektrifikasi industri. Artikel ini meneroka bagaimana motor...

Factory I/O: Alat Simulasi PLC Moden untuk Latihan Automasi Industri

Factory I/O sedang mengubah pendidikan PLC dengan menyediakan simulasi industri 3D yang mendalam untuk pelajar, jurutera, dan pasukan penyelenggaraan. Platform ini merapatkan jurang antara teori dan...

Pengaturcaraan Kitaran Gerakan Paksi Tunggal pada Pemacu Servo CMZ

Tutorial ini mengkaji bagaimana fungsi PLC terbina dalam pemacu servo CMZ SBD dapat melaksanakan program gerakan berdiri sendiri, termasuk logik homing, kawalan kedudukan, dan pergerakan paksi...

Persediaan Kawalan Gerakan Paksi Tunggal dengan Pemacu Servo CMZ

Tutorial ini meneroka penyediaan sistem gerakan servo paksi tunggal menggunakan pemacu CMZ SBD, merangkumi penyediaan perkakasan, penskalaan paksi, konfigurasi homing, dan pengesahan gerakan selamat...