Description

Designed for high-accuracy voltage measurement within automated control topologies, the Beckhoff EL3602 is a dual-channel analog input terminal operating on the EtherCAT protocol. This high-precision module processes differential input signals across several user-configurable voltage ranges, providing reliable 24-bit resolution to the central control system. Optimized for applications requiring exceptional signal fidelity, it features electrical isolation and robust integrated filters to manage electrical noise in demanding industrial environments.

Features

  • Two independent, differential analog input channels.
  • Parameterizable measurement ranges: +/-10 V, +/-5 V, +/-2.5 V, and +/-1.25 V.
  • Exceptional 24-bit resolution (including sign) for microscopic voltage tracking.
  • Extremely low measurement error of less than +/-0.01 percent at 25 degC (relative to full scale).
  • Galvanic isolation of 500 V between the internal E-bus and the input channels.
  • Configurable conversion times ranging from 1 ms to 400 ms (20 ms default).

Applications

  • High-precision automated test benches and calibration systems.
  • Process monitoring in semiconductor manufacturing and laboratory environments.
  • Tension and load monitoring loops requiring highly stable differential voltage feedback.
  • Multi-axis motion systems needing micro-positioning analog feedback.

Technical Specifications

Specification Parameter Value
Manufacturer Beckhoff
Model Series EL3602 (EtherCAT Terminal Series)
Number of Inputs 2 (Differential)
Signal Voltage Ranges -10 to +10 V, -5 to +5 V, -2.5 to +2.5 V, -1.25 to +1.25 V
Resolution 24 bits (including sign)
Internal Resistance Greater than 200 kOhm
Input Filter Limit Frequency 3 kHz
E-bus Current Consumption Typically 190 mA
Common-Mode Voltage (Ucm) Maximum 35 V
Crosstalk Attenuation Greater than 60 dB
Electrical Isolation 500 V (E-bus / signal voltage)
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Relative Humidity 95 percent, non-condensing
Protection Rating IP20
Approvals & Markings CE, UL, ATEX (II 3 G Ex nA IIC T4 Gc)
Housing Dimensions 12 mm x 100 mm x 68 mm
Net Module Weight 60 g
Shipping Weight (Calculated) 0.15 kg
Package Dimensions (Calculated) 120 mm x 80 mm x 25 mm
Country of Origin Germany

Connections and Interfaces

Terminal Point Signal Assignment (Channel 1) Terminal Point Signal Assignment (Channel 2)
1 Input + 2 Input +
5 Input - 6 Input -
3 Shield 7 Shield
4 Analog Ground (AGND) 8 Analog Ground (AGND)

Empirical Engineering Insights

Alternative Models & Compatibility

When replacing or integrating the EL3602, verify the TwinCAT software version and active EtherCAT XML Device Description (ESI) files. The EL3602 features dynamic configuration via CoE (CAN over EtherCAT) variables. Ensure that older systems designed for the calibrated alternative EL3602-0010 are checked, as scaling and calibration coefficients differ within the PLC program. When using multiple EL series modules, verify that the total E-bus current budget does not exceed the limits of the coupler or the power supply terminal; the EL3602 draws a sustained 190 mA from the E-bus.

Application Pitfalls & Engineering Notes

The common-mode voltage (Ucm) must be kept strictly below 35 V relative to the internal E-bus ground to prevent measurement errors and potential damage. Ground loops are the primary source of drift in 24-bit applications. If measuring floating voltage sources, ensure the AGND terminal is linked to a clean, stable system reference to prevent the differential inputs from drifting into saturation. Additionally, allow a 15-minute thermal stabilization period after powering the cabinet to ensure the internal reference reaches equilibrium for 24-bit resolution stability.

Commissioning & Wiring Tips

Use twisted-pair shielded cabling for all analog signals. The shield should be terminated directly at the terminal (Terminal 3 or 7) for best high-frequency performance. In high-interference environments, utilize the TwinCAT system manager to activate the 50 Hz or 60 Hz notch filter inside the module's CoE registers. This significantly attenuates electrical line noise and maintains the module's ultra-low measurement error rating.

Installation Guidelines

CRITICAL WARNING

Always isolate the power supply of the entire EtherCAT station before inserting or removing terminals. Failure to de-energize the E-bus could cause damage to the internal contact pins or result in system communication failures.

1

Align the terminal onto the 35 mm DIN rail (conforming to EN 60715) and slide it to lock into the adjoining module using the double slot and key connection.

2

Push the terminal forward until the orange locking slide snaps securely over the rail.

3

Insert a flathead screwdriver into the spring-actuated terminal openings to wire connections. Solid or stranded conductors (0.08 to 2.5 mm2, AWG 28-14) must be stripped exactly 8 to 9 mm.

4

Verify connection status using the integrated LEDs before applying full system logic power.

Loading product navigation…

What is the default conversion time of the EL3602, and can it be adjusted?

The default conversion time is 20 ms. However, it is fully parameterizable via CoE (CAN over EtherCAT) settings between 1 ms and 400 ms.

What is the maximum common-mode voltage allowed on this analog module?

The maximum common-mode voltage (Ucm) is 35 V. Exceeding this rating can lead to saturated analog signals, measurement errors, or terminal damage.

Does the EL3602 require an external power supply connection?

No, the EL3602 receives its operational power entirely from the internal E-bus connection, drawing typically 190 mA.

Can I configure the channels for single-ended voltage measurement?

The EL3602 features dedicated differential inputs. For single-ended measurements, you must connect the negative terminal to the reference ground (AGND) while verifying you do not violate the 35 V common-mode limit.

Penghantaran Ekspres Global

  • Penghantaran Standard: 4-6 Hari Bekerja melalui DHL, FedEx, dan UPS.
  • Penghantaran Ekspres: Penghantaran pada hari yang sama untuk pesanan dalam stok yang dibuat sebelum 2:00 PM (GMT+8).
  • Liputan Seluruh Dunia: Berkhidmat di lebih 150 negara, termasuk penghantaran pantas ke Arab Saudi dan UAE.

Pemulangan & Jaminan

  • Jaminan 30 Hari: Pemulangan diterima untuk produk dalam stok dalam pembungkusan asal yang disegel kilang.
  • Jaminan 12 Bulan: Setiap komponen industri disokong oleh jaminan teknikal profesional kami.

Pesanan diproses dan dihantar Isnin-Jumaat (tidak termasuk cuti umum).


Untuk kelayakan penuh, yuran penyimpanan semula, dan butiran pemulangan antarabangsa, sila lihat rasmi kami Polisi Pemulangan & Pengembalian Wang .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknikal

Penggerak Elektrik Direka untuk Menggantikan Sistem Kuasa Cecair: Panduan Automasi Industri Praktikal

Artikel ini menerangkan bagaimana aktuator elektrik bersepadu, seperti siri e-Actuator SMC, mengubah kawalan gerakan industri dengan menggantikan sistem pneumatik dan hidraulik tradisional. Ia...

Operasi Matematik Menggunakan OpenPLC untuk Aplikasi Automasi Industri

Artikel ini menerangkan bagaimana sistem PLC melaksanakan operasi matematik teras seperti penambahan, penolakan, pendaraban, pembahagian, modulo, dan perpangkatan dalam automasi industri. Ia...

Logik Boolean Lanjutan dengan Pengaturcaraan FBD PLC: Aplikasi Industri Praktikal Melebihi Logik Asas

Artikel ini menerangkan beberapa fungsi logik Boolean lanjutan yang digunakan dalam pengaturcaraan PLC selain operasi asas AND, OR, dan NOT. Ia merangkumi bagaimana alat seperti jadual kebenaran,...

Logik Boolean dalam Pengaturcaraan PLC: Memahami Pintu Logik FBD

Logik Boolean adalah asas bagi setiap program PLC. Dari kawalan mesin yang mudah hingga sistem automasi industri yang kompleks, pintu logik menentukan bagaimana pengawal bertindak balas terhadap...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan untuk Pengapit Robotik: Dari Pengendalian Halus hingga Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...