Description

Integrating serial communication directly into the Beckhoff I/O system, the Beckhoff KL6011 serial interface terminal enables connection to devices equipped with a 20 mA current loop (TTY) interface. The terminal operates fully independently of the higher-level bus system, executing bidirectional transmission of data channels (TxD and RxD) in full duplex mode. The active or passive status of the current loop can be established through external wiring configurations, ensuring high adaptability to legacy serial interfaces, industrial weighing systems, and long-distance terminal connections up to 1000 meters.

Features

  • Active/Passive Flexibility: Configurable 2 x 20 mA active or passive current loops to interface with various sender/receiver architectures.
  • Configurable Baud Rates: Supports transfer rates ranging from 1200 baud up to 19,200 baud to match legacy serial peripherals.
  • Integrated Data Buffering: Equipped with a 128-byte receive buffer and a 16-byte transmit buffer to handle temporary data peaks without processing loss.
  • K-Bus Galvanic Isolation: Provides robust 500 V electrical isolation between the internal K-bus and the field-side signal paths to safeguard control networks.
  • Variable Process Image: Flexible bit-width configuration in the process image (from 3 x 8-bit to 5 x 8-bit user data plus control/status byte).

Applications

  • Legacy Peripheral Integration: Connecting older industrial printers, barcode readers, and display terminals to modern EtherCAT/K-bus architectures.
  • Industrial Weighing Systems: Direct communication with load cells and digital balances that rely on 20 mA current loops.
  • Long-Distance Serial Links: Point-to-point serial communication up to 1000 meters in high-noise environments where RS232 is ineffective.

Technical Specifications

Parameter Specification Value
Manufacturer Beckhoff
Model / Article Number KL6011
Interface Type TTY (20 mA current loop)
Number of Channels 2 (1 transmit TxD, 1 receive RxD), full duplex
Data Transfer Rates 1200 to 19,200 baud (Default: 9600 baud, 8 data bits, no parity, 1 stop bit)
Bit Transfer Current 2 x 20 mA
Loop Resistance (Load) Less than 500 ohms
Cable Length Max. 1000 m shielded twisted pair
Power Supply Via the internal K-bus
Current Consumption (K-bus) Typical 55 mA
Electrical Isolation 500 V (K-bus to signal voltage)
Process Image Bit Width Input/Output: 3 x 8-bit user data, 1 x 8-bit control/status (up to 5 x 8-bit user data possible)
Protection Class IP20
Operating Temperature Range 0 to +55 degC
Storage Temperature Range -25 to +85 degC
Relative Humidity 95%, non-condensing
Ex Marking II 3 G Ex nA IIC T4 Gc
Unit Weight Approx. 60 g
Shipping Weight (Calculated) 0.15 kg
Package Dimensions (Calculated) 125 mm x 80 mm x 25 mm

Connections and Interfaces

Terminal Point Signal / Function Description
1 TxD+ Transmitter current loop output (Positive)
5 TxD- Transmitter current loop return (Negative)
2 RxD+ Receiver current loop input (Positive)
6 RxD- Receiver current loop return (Negative)
3 20 mA Active Tx Internal current source connection for active Tx operation
7 20 mA Active Rx Internal current source connection for active Rx operation

Empirical Engineering Insights

Alternative Models & Compatibility

For applications requiring pluggable wiring terminal structures, the KS6011 represents the direct functional alternative, retaining the exact same internal logic and register mapping. If your infrastructure utilizes RS485 or RS232 protocols rather than 20 mA current loops, migrate to the KL6021 or KL6001 terminals, respectively, as the KL6011 electrical physical layer is restricted strictly to TTY communication.

Application Pitfalls & Engineering Notes

A frequent commissioning failure involves improper active/passive configuration of the 20 mA current loop. Because a TTY loop requires exactly one current source to function, placing two active devices on the same loop will cause hardware damage or component burnout due to overcurrent. Ensure that if the connected external device is active (supplying the loop current), the KL6011 is wired strictly in its passive configuration (avoiding terminals 3 and 7).

Commissioning & Wiring Tips

To optimize transmission reliability up to the 1000 m limit, use low-capacitance, shielded twisted-pair (STP) cabling. Connect the shield on one end only—ideally at the Bus Coupler ground rail—to prevent ground loops. Note that configuration of the data format (baud rate, parity, stop bits) is managed dynamically via the terminal registers using TwinCAT or alternative coupler configuration software, requiring no physical dip-switch adjustments on the hardware block.

Installation Guidelines

CRITICAL WARNING

Disconnect all electrical supplies before inserting or removing terminals from the K-bus assembly. Failure to isolate the power contacts can lead to permanent damage of the bus contacts, the bus coupler, or the adjacent I/O modules.

1
Ensure the DIN rail is securely grounded to the main cabinet ground system to facilitate proper EMC shielding.
2
Mount the terminal onto the DIN rail by aligning the integrated tongue-and-groove slot with the neighboring terminal and pushing firmly until it clicks.
3
Use a flathead screwdriver to depress the spring-loaded wire clamps, insert the pre-stripped signal wires, and release to secure.
Loading product navigation…

Can the KL6011 be used to interface with an RS232 device?

No, it is strictly designed for TTY 20 mA current loop interfaces. To connect to an RS232 device, use the Beckhoff KL6001 module.

How do I configure the active or passive status of the current loop on this terminal?

The configuration is determined by the external physical wiring of the terminals. Connecting to the internal 20 mA sources on terminals 3 and 7 configures the circuit as active. Leaving them disconnected runs the loop as passive.

What is the maximum distance supported by the serial interface?

It supports communication distances up to 1000 meters when utilizing high-quality shielded twisted-pair cabling.

Is an external power supply required for the field-side serial loop?

No, the internal logic and active loop current (if utilized via terminals 3 and 7) are powered directly through the standard K-bus.

Penghantaran Ekspres Global

  • Penghantaran Standard: 4-6 Hari Bekerja melalui DHL, FedEx, dan UPS.
  • Penghantaran Ekspres: Penghantaran pada hari yang sama untuk pesanan dalam stok yang dibuat sebelum 2:00 PM (GMT+8).
  • Liputan Seluruh Dunia: Berkhidmat di lebih 150 negara, termasuk penghantaran pantas ke Arab Saudi dan UAE.

Pemulangan & Jaminan

  • Jaminan 30 Hari: Pemulangan diterima untuk produk dalam stok dalam pembungkusan asal yang disegel kilang.
  • Jaminan 12 Bulan: Setiap komponen industri disokong oleh jaminan teknikal profesional kami.

Pesanan diproses dan dihantar Isnin-Jumaat (tidak termasuk cuti umum).


Untuk kelayakan penuh, yuran penyimpanan semula, dan butiran pemulangan antarabangsa, sila lihat rasmi kami Polisi Pemulangan & Pengembalian Wang .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknikal

Penggerak Elektrik Direka untuk Menggantikan Sistem Kuasa Cecair: Panduan Automasi Industri Praktikal

Artikel ini menerangkan bagaimana aktuator elektrik bersepadu, seperti siri e-Actuator SMC, mengubah kawalan gerakan industri dengan menggantikan sistem pneumatik dan hidraulik tradisional. Ia...

Operasi Matematik Menggunakan OpenPLC untuk Aplikasi Automasi Industri

Artikel ini menerangkan bagaimana sistem PLC melaksanakan operasi matematik teras seperti penambahan, penolakan, pendaraban, pembahagian, modulo, dan perpangkatan dalam automasi industri. Ia...

Logik Boolean Lanjutan dengan Pengaturcaraan FBD PLC: Aplikasi Industri Praktikal Melebihi Logik Asas

Artikel ini menerangkan beberapa fungsi logik Boolean lanjutan yang digunakan dalam pengaturcaraan PLC selain operasi asas AND, OR, dan NOT. Ia merangkumi bagaimana alat seperti jadual kebenaran,...

Logik Boolean dalam Pengaturcaraan PLC: Memahami Pintu Logik FBD

Logik Boolean adalah asas bagi setiap program PLC. Dari kawalan mesin yang mudah hingga sistem automasi industri yang kompleks, pintu logik menentukan bagaimana pengawal bertindak balas terhadap...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan untuk Pengapit Robotik: Dari Pengendalian Halus hingga Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...