1 daripada 1

Beckhoff KM1004-0001 Bus Terminal Module 32-Channel Digital Input

Beckhoff KM1004-0001 Bus Terminal Module 32-Channel Digital Input

Hanya 10 item tinggal dalam stok
  • Pengilang: BECKHOFF

  • No. Produk: KM1004-0001

  • Negara asal:Jerman

  • Jenis Produk: Bus Terminal Modules

  • Pembayaran: T/T, Western Union

  • Berat: 2000g

  • Dimensi: 75 mm x 100 mm x 55 mm

  • Pelabuhan penghantaran: Xiamen

  • Jaminan: 12 bulan

Kuantiti
Lihat butiran penuh

Description

Optimizing high-density discrete sensing layouts, the Beckhoff KM1004-0001 integrates 32 digital input channels within a single pluggable bus terminal interface. This compact module acts as an electrical isolator, routing 24 V DC field control signals from proximity sensors, switches, and limit contacts to the central K-bus processing image. By utilizing a 1-wire connection technology with a modular plug-in design, the Beckhoff KM1004-0001 minimizes field wiring volume while maintaining clean cabinet organization.

Key Features

  • High-Density Discrete Sensing: Houses 32 digital inputs structured across four 8-channel groupings.
  • 1-Wire Pluggable Design: Bundled with a 1-wire tension clamp connector block for fast installation and field-level toolless maintenance.
  • Integrated Signal Filtering: Employs a standard 3.0 ms hardware input filter to prevent relay contact bounce and electromagnetic interference.
  • Complete Electrical Isolation: Rated for up to 500 V isolation between the internal K-bus and the external field potential.
  • Modular Scalability: Fully integrates into standard Beckhoff K-bus networks alongside traditional 12 mm Bus Terminals.

Applications

  • Concentrated sensor integration in food processing and packaging machinery.
  • I/O expansion for material handling, conveyor systems, and sorting lines.
  • High-density control cabinet assemblies with limited physical mounting depth.

Product Suffix Variants

Order Code Connection Method LED Status Indicators
KM1004-0000 Pluggable connection (shipped without connector headers) No
KM1004-0001 1-wire pluggable connector (included) No
KM1004-0002 1-wire pluggable connector (included) Yes
KM1004-0004 3-wire pluggable connector (included) Yes

Technical Specifications

Manufacturer Beckhoff
Part Number / SKU KM1004-0001
Number of Inputs 32 (4 x 8 channels)
Nominal Voltage 24 V DC (-15% / +20%)
"0" Signal Voltage -3 V to +5 V
"1" Signal Voltage 15 V to 30 V
Input Filter Time typ. 3.0 ms
Input Current typ. 5 mA
Current Consumption K-Bus typ. 3 mA
Current Consumption Power Contacts None (no power contacts implemented)
Electrical Isolation 500 V (K-bus / field potential)
Process Image Bit Width 32 inputs
Connection Cross-Section 0.08 to 1.5 mm2 (solid or stranded)
Stripping Length 8 mm
Dimensions (W x H x D) 75 mm x 100 mm x 55 mm
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Relative Humidity 95% non-condensing
Protection Class IP20
Standard Compliance EN 61131-2 Type 1, EN 60068-2-6, EN 60068-2-27
Shipping Weight (Calculated) 0.20 kg (including plug-in assembly block)

Empirical Engineering Insights

Alternative Models & Compatibility

The KM1004-0001 is functionally identical to the KM1004-0000, except it is bundled from the factory with the compatible 1-wire ZS2001-0001 female header plugs. For configurations requiring visible diagnostics directly on the terminal face, the KM1004-0002 serves as the direct physical alternative, offering built-in state-tracking LEDs. The modular connector plates can be hot-swapped onto the same base unit without altering the system’s physical footprint.

Application Pitfalls & Engineering Notes

Be advised that the KM1004-0001 has no integrated power contacts. Field-side sensors cannot draw positive potential or ground loops directly from internal terminal pass-throughs. If utilizing multi-wire field sensors, external potential distributors (such as KL9100) must be positioned adjacent to the module to supply the reference potential. Additionally, always ensure that K-bus power consumption margins are budgeted in the system coupler configuration to prevent voltage drops.

Commissioning & Wiring Tips

When assembling the ZS2001-0001 header block, maintain an exact 8 mm stripping length. Stranded wires without ferrules should be installed with precision to avoid stray strands bridging neighboring terminal pins inside the high-density header. To avoid capacitive cross-talk within high-channel installations, keep the 24 V DC digital signal wires logically separate from 230/400 V AC power runs.

Installation Guidelines

CRITICAL WARNING:

Isolate all 24 V DC field power and K-bus primary power circuits before mounting, dismounting, or wiring this terminal module. Working with active electrical systems can trigger high-frequency noise spikes, damage solid-state K-bus interfaces, or lead to unintentional machine movement.

1
Position the KM1004-0001 module onto the 35 mm DIN rail (EN 60715) and push down firmly until the integrated locking hook securely snaps onto the rail profile.
2
Slide the female connector header (ZS2001-0001) into the housing guide channels until it locks flush with the terminal front face.
3
Terminate the 24 V DC field inputs utilizing standard tension-clamp tools, using stripped 0.08 to 1.5 mm2 solid or stranded conductors.
4
Power up the K-bus rail system and map the 32 input bits inside TwinCAT or other compatible PLC configuration platforms to verify full I/O mapping logic.
Loading product navigation…

What is the key difference between the KM1004-0001 and the KM1004-0000?

The KM1004-0001 includes the physical 1-wire ZS2001-0001 plug-in female terminal headers in the package, whereas the KM1004-0000 is supplied as the bare housing module without terminal blocks.

Does this module support feed-through electrical power contacts?

No. The KM1004-0001 has no integrated power contacts. Sensor supply voltage and grounds must be connected using external potential terminal distribution blocks.

What size wire can be used with the included plug-in connectors?

The terminal block accommodates both solid and stranded electrical conductors ranging from 0.08 to 1.5 mm2 (28 to 16 AWG).

Does this digital input module require hardware configuration settings?

No configuration or manual address settings are required. The module is automatically detected on the K-bus and maps 32 bits straight into the PLC controller process image.

Penghantaran Ekspres Global

  • Penghantaran Standard: 4-6 Hari Bekerja melalui DHL, FedEx, dan UPS.
  • Penghantaran Ekspres: Penghantaran pada hari yang sama untuk pesanan dalam stok yang dibuat sebelum 2:00 PM (GMT+8).
  • Liputan Seluruh Dunia: Berkhidmat di lebih 150 negara, termasuk penghantaran pantas ke Arab Saudi dan UAE.

Pemulangan & Jaminan

  • Jaminan 30 Hari: Pemulangan diterima untuk produk dalam stok dalam pembungkusan asal yang disegel kilang.
  • Jaminan 12 Bulan: Setiap komponen industri disokong oleh jaminan teknikal profesional kami.

Pesanan diproses dan dihantar Isnin-Jumaat (tidak termasuk cuti umum).


Untuk kelayakan penuh, yuran penyimpanan semula, dan butiran pemulangan antarabangsa, sila lihat rasmi kami Polisi Pemulangan & Pengembalian Wang .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknikal

Penggerak Elektrik Direka untuk Menggantikan Sistem Kuasa Cecair: Panduan Automasi Industri Praktikal

Artikel ini menerangkan bagaimana aktuator elektrik bersepadu, seperti siri e-Actuator SMC, mengubah kawalan gerakan industri dengan menggantikan sistem pneumatik dan hidraulik tradisional. Ia...

Operasi Matematik Menggunakan OpenPLC untuk Aplikasi Automasi Industri

Artikel ini menerangkan bagaimana sistem PLC melaksanakan operasi matematik teras seperti penambahan, penolakan, pendaraban, pembahagian, modulo, dan perpangkatan dalam automasi industri. Ia...

Logik Boolean Lanjutan dengan Pengaturcaraan FBD PLC: Aplikasi Industri Praktikal Melebihi Logik Asas

Artikel ini menerangkan beberapa fungsi logik Boolean lanjutan yang digunakan dalam pengaturcaraan PLC selain operasi asas AND, OR, dan NOT. Ia merangkumi bagaimana alat seperti jadual kebenaran,...

Logik Boolean dalam Pengaturcaraan PLC: Memahami Pintu Logik FBD

Logik Boolean adalah asas bagi setiap program PLC. Dari kawalan mesin yang mudah hingga sistem automasi industri yang kompleks, pintu logik menentukan bagaimana pengawal bertindak balas terhadap...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan untuk Pengapit Robotik: Dari Pengendalian Halus hingga Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...