Beckhoff KS6771 Bus Terminal MP-Bus Master Module

Beckhoff KS6771 Bus Terminal MP-Bus Master Module

Hanya 10 item tinggal dalam stok
  • Pengilang: BECKHOFF

  • No. Produk: KS6771

  • Negara asal:Jerman

  • Jenis Produk: Bus Terminals

  • Pembayaran: T/T, Western Union

  • Berat: 1500g

  • Dimensi: 12 mm x 100 mm x 68 mm

  • Pelabuhan penghantaran: Xiamen

  • Jaminan: 12 bulan

Kuantiti
Lihat butiran penuh

Description

Actuating as a dedicated integration link, the Beckhoff KS6771 Bus Terminal enables direct, bidirectional communication between a K-bus coupler and Belimo MP-Bus HVAC field devices. This module functions as an MP-Bus master, coordinating data acquisition and control command distribution over a single channel. The KS6771 design features a pluggable wiring level, allowing swift module swaps without disconnecting field-level wiring harnesses. Integration is fully managed via standard TwinCAT PLC function blocks, streamlining commissioning across complex commercial and industrial air handling architectures.

Features

  • Multi-Device Topologies: Controls up to 16 MP-Bus devices (maximum 8 drives and 8 sensors) over a single fieldbus drop.
  • Pluggable Wiring Interface: Uses tension-clamp connection terminals that can be detached as a single block for expedited terminal replacement.
  • Galvanic Isolation: Provides robust 500 V isolation between the internal K-bus and the external MP-Bus circuitry to suppress common-mode electrical noise.
  • Efficient Process Image: Maps directly into the controller configuration utilizing 12 bytes of input data and 12 bytes of output data.
  • Standardized Diagnostics: Fully compatible with the TwinCAT PLC MP-Bus software library for fast system integration and continuous error reporting.

Applications

  • HVAC Variable Air Volume (VAV) Systems: Direct control of volumetric flow controllers, damper actuators, and temperature sensors.
  • Industrial Environmental Controls: Closed-loop control of pressure relief valves and air-handling units within cleanrooms or pharmaceutical laboratories.
  • Building Management Systems (BMS): Integration of distributed Belimo valve actuators and auxiliary sensors into high-level Ethernet/IP or EtherCAT backbones.

Technical Specifications

Parameter Specification
Manufacturer Beckhoff Automation
Model Number KS6771
Interface Type MP-Bus Master (1 Channel)
Data Transfer Rate 1200 baud
Bus Access Protocol Polling
Nominal System Voltage 24 V DC (-15% / +20%)
K-Bus Current Consumption Typically 55 mA
Power Contact Consumption Typically 10 mA + actuator load
Maximum Power Contact Load 10 A
Isolation Voltage 500 V (K-bus to MP-Bus line)
Process Image Width 12 bytes input, 12 bytes output
Connection Cross-Section 0.08 to 1.5 mm² (AWG 28...16 solid/stranded; AWG 26...16 flexible)
Wire Stripping Length 9 to 10 mm
Environmental Rating IP20 (with variable installation orientation)
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Relative Humidity 95% non-condensing
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Explosion Protection Marking II 3 G Ex nA IIC T4 Gc (ATEX Zone 2)
Housing Material Polycarbonate (terminal housing with pluggable wiring)
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Product Net Weight Approximately 85 g
Shipping Weight (Calculated) 1.5 kg

Connections and Interfaces

Terminal Pin Number Signal Assignment Description
1 MP-Bus Line Bidirectional communications line to Belimo slave actuators.
2 24 V DC (Power Contact) Power feed to drive units (internally bridged to power contact).
5 GND (MP-Bus Reference) Common reference potential for MP-Bus communication.
6 0 V DC (Power Contact) Negative power rail reference (internally bridged to power contact).

Empirical Engineering Insights

Alternative Models & Compatibility

The KS6771 is direct operational equivalent to the standard KL6771 Bus Terminal. The critical difference lies in the "KS" terminal housing design, which includes a pluggable wiring block. From a software perspective, the TwinCAT hardware configuration treats the KS6771 identically to the KL6771, enabling seamless drop-in replacements in existing PLC programs without necessitating code modifications or IO mapping updates.

Application Pitfalls & Engineering Notes

When deploying the KS6771, engineers must monitor total current consumption on the external 24 V DC supply loop. The terminal relies on internal power contacts rated for a maximum of 10 A. If several heavy damper drives are powered directly through the bus terminal, ensure the combined peak inrush currents do not exceed this threshold. For installations spanning long physical distances, use shielded twisted-pair cables to mitigate inductive noise coupling, which can disrupt the 1200-baud polling cycles.

Commissioning & Wiring Tips

To configure the bus terminal within the TwinCAT environment, the Tc2_MPBus library must be integrated into the PLC project. When addressing Belimo devices, remember that the MP-Bus allows 8 active control drives and 8 passive sensors. When inserting stranded field conductors, use the pluggable tension-clamp release slot with a standard flat-head screwdriver (3.0 mm blade size) to avoid damaging the polycarbonate terminal guide locks.

Installation Guidelines

CRITICAL WARNING: Prior to installing, removing, or wiring the KS6771 terminal, completely de-energize the main system controller and all auxiliary 24 V power feeds. Failure to isolate power may cause communication bus disruption or permanent damage to the solid-state K-bus interface electronics.
1
Mount the terminal on a standard 35 mm DIN rail conforming to EN 60715, ensuring the lock mechanism snaps firmly into place.
2
Slide adjacent terminals together, using the integrated double slot and key connection for side-by-side electrical contact.
3
Prepare field wires by stripping insulation precisely to 9–10 mm, avoiding loose strands that could cross-contact neighboring terminals.
4
Insert field wiring into the pluggable tension clamps, using a spring-release screwdriver tool to lock each wire securely into position.
Loading product navigation…

What is the primary difference between the Beckhoff KS6771 and KL6771 terminals?

The KS6771 features a pluggable wiring level, enabling the field wiring block to be removed and plugged back on as a single assembly. The KL6771 uses fixed, non-removable terminal block connections.

How many Belimo actuator drives can I connect to a single KS6771 module?

The terminal supports a maximum of 16 MP-Bus devices, which is architecturally split into up to 8 drives and 8 sensors.

What software library is required to program this terminal in TwinCAT?

Integration requires the TwinCAT PLC MP-Bus library (typically Tc2_MPBus for TwinCAT 3), which provides dedicated function blocks for communication and device polling.

Is the KS6771 rated for use in hazardous locations?

Yes, it has ATEX approval with marking II 3 G Ex nA IIC T4 Gc, making it suitable for installation in Zone 2 hazardous areas.

Penghantaran Ekspres Global

  • Penghantaran Standard: 4-6 Hari Bekerja melalui DHL, FedEx, dan UPS.
  • Penghantaran Ekspres: Penghantaran pada hari yang sama untuk pesanan dalam stok yang dibuat sebelum 2:00 PM (GMT+8).
  • Liputan Seluruh Dunia: Berkhidmat di lebih 150 negara, termasuk penghantaran pantas ke Arab Saudi dan UAE.

Pemulangan & Jaminan

  • Jaminan 30 Hari: Pemulangan diterima untuk produk dalam stok dalam pembungkusan asal yang disegel kilang.
  • Jaminan 12 Bulan: Setiap komponen industri disokong oleh jaminan teknikal profesional kami.

Pesanan diproses dan dihantar Isnin-Jumaat (tidak termasuk cuti umum).


Untuk kelayakan penuh, yuran penyimpanan semula, dan butiran pemulangan antarabangsa, sila lihat rasmi kami Polisi Pemulangan & Pengembalian Wang .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknikal

Penggerak Elektrik Direka untuk Menggantikan Sistem Kuasa Cecair: Panduan Automasi Industri Praktikal

Artikel ini menerangkan bagaimana aktuator elektrik bersepadu, seperti siri e-Actuator SMC, mengubah kawalan gerakan industri dengan menggantikan sistem pneumatik dan hidraulik tradisional. Ia...

Operasi Matematik Menggunakan OpenPLC untuk Aplikasi Automasi Industri

Artikel ini menerangkan bagaimana sistem PLC melaksanakan operasi matematik teras seperti penambahan, penolakan, pendaraban, pembahagian, modulo, dan perpangkatan dalam automasi industri. Ia...

Logik Boolean Lanjutan dengan Pengaturcaraan FBD PLC: Aplikasi Industri Praktikal Melebihi Logik Asas

Artikel ini menerangkan beberapa fungsi logik Boolean lanjutan yang digunakan dalam pengaturcaraan PLC selain operasi asas AND, OR, dan NOT. Ia merangkumi bagaimana alat seperti jadual kebenaran,...

Logik Boolean dalam Pengaturcaraan PLC: Memahami Pintu Logik FBD

Logik Boolean adalah asas bagi setiap program PLC. Dari kawalan mesin yang mudah hingga sistem automasi industri yang kompleks, pintu logik menentukan bagaimana pengawal bertindak balas terhadap...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan untuk Pengapit Robotik: Dari Pengendalian Halus hingga Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...