1 daripada 3

Bently Nevada 330881-28-09-123-03-02 PROXPAC XL Proximity Transducer

Bently Nevada 330881-28-09-123-03-02 PROXPAC XL Proximity Transducer

Hanya 5 item tinggal dalam stok
  • Pengilang: Bently Nevada

  • No. Produk: 330881-28-09-123-03-02

  • Negara asal:Amerika Syarikat

  • Jenis Produk: PROXPAC XL Proximity Transducer

  • Kod bar: 8537101190

  • Pembayaran: T/T, Western Union

  • Berat: 250g

  • Dimensi: 60 mm x 110 mm x 110 mm (H x W x D)

  • Pelabuhan penghantaran: Xiamen

  • Jaminan: 12 bulan

Kuantiti
Lihat butiran penuh

Description

330881-28-09-123-03-02: PROXPAC XL Proximity Transducer, featuring an integrated 3300 XL 8 mm proximity probe with multiple agency approvals (Option 28), a 90 mm metric standoff adapter (Option 09), a precise 123 mm probe sleeve penetration length (Option 123), a single M20 conduit fitting with two plugs (Option 03), and a 3/4-14 NPT mounting thread (Option 02).

The integrated design of the PROXPAC XL Proximity Transducer Assembly combines both the proximity probe and the Proximitor sensor into a single, self-contained mechanical package. By eliminating the high-frequency extension cable between the probe and Proximitor, this system minimizes potential signal loss, connector wear, and wiring errors. Field wiring from the monitoring system connects directly to internal terminals inside the rugged housing, eliminating the need for separate Proximitor enclosures. Constructed from glass-reinforced Polyphenylene Sulfide (PPS) thermoplastic with conductive fibers, the housing safely dissipates electrostatic charges and is rated for IP66 and NEMA Type 4X environments, providing superior resistance to corrosive chemicals, hot water, and high humidity.

Features

  • Option 28 includes a 3300 XL 8 mm proximity probe with Multiple Approvals.
  • Option 09 specifies a 90 mm metric standoff adapter length.
  • Option 123 provides a precise 123 mm metric probe sleeve penetration depth.
  • Option 03 delivers one M20 conduit fitting and two plugs.
  • Option 02 equips the system with a 3/4-14 NPT mounting thread.
  • Self-contained design eliminates separate Proximitor housings and extension cables.
  • Polyphenylene Sulfide (PPS) thermoplastic housing offers excellent chemical and environmental resistance.
  • Conductive fiber formulation prevents electrostatic charge accumulation.
  • IP66 and Type 4X protection ratings for severe industrial installations.

Applications

  • Shaft vibration and axial position measurement on industrial rotating machinery.
  • Steam turbines, gas turbines, compressors, and high-speed pumps with restricted external mounting space.
  • Corrosive or severe industrial environments requiring NEMA Type 4X and IP66 rated enclosures.
  • Hazardous areas requiring intrinsically safe or non-incendive transducer configurations.

Ordering Information

Option Segment Code Value on This SKU Description / Meaning
Base Model Number 330881 PROXPAC XL Proximity Transducer Assembly, Metric
A: Probe and Approvals Option 28 3300 XL 8 mm probe with Multiple Approvals
B: Standoff Adapter Option 09 90 mm standoff adapter length (ordered in 10 mm increments)
C: Probe Penetration Option 123 123 mm sleeve penetration length (ordered in 1 mm increments)
D: Fittings Option 03 One M20 fitting, two plugs
E: Mounting Thread Option 02 3/4-14 NPT mounting thread (required for Standoff Adapter Option)

Technical Specifications

Manufacturer Bently Nevada
Part Number / SKU 330881-28-09-123-03-02
Product Family PROXPAC XL Proximity Transducer Assembly
Proximitor Sensor Input 3300 XL 8 mm Proximity Probe with a 1-meter cable
Power Requirements -17.5 Vdc to -26 Vdc without barriers at 12 mA maximum
Linear Range 2.0 mm (80 mils) nominal
Scale Factor 7.87 V/mm (200 mV/mil) nominal
Frequency Response 0 to 10 kHz: +0, -3 dB (with up to 305 meters of field wiring)
Housing Material Glass-reinforced, UV-resistant Polyphenylene Sulfide (PPS) with conductive fibers
Sleeve Material AISI 304 Stainless Steel
Retaining Screws AISI 303 Stainless Steel
Sleeve O-Ring Material Neoprene
Probe Case Material AISI 304 Stainless Steel
Probe Tip Material Polyphenylene Sulfide (PPS)
Probe Cable 1-meter length, 75 Ohm triaxial, FEP insulated with gold-plated brass ClickLoc connector
Probe Tensile Strength 330 N (75 lb) between probe cable and case maximum
Recommended Minimum Target Size 15.2 mm (0.6 in) diameter flat target
Recommended Minimum Shaft Diameter 76.2 mm (3.0 in)
Operating Temperature (Probe) -52 degC to +177 degC (-62 degF to +351 degF)
Operating Temperature (Housing / Sensor) -52 degC to +100 degC (-62 degF to +212 degF)
Storage Temperature -52 degC to +105 degC (-62 degF to +221 degF)
Relative Humidity 100% condensing, non-submersible (when properly sealed)
Environmental Rating IP66 and NEMA Type 4X
Impact Strength Withstands two 4 Joule impacts at -39 degC and +115 degC (BASEEFA verified)

Connections and Interfaces

Field wiring terminals are located within the housing lid and connect directly to the integrated 3300 XL Proximitor sensor. Use a 3-conductor, twisted, shielded cable of 1.0 mm2 (18 AWG) for connections between the transducer assembly and the monitoring system. Keep shield connections isolated from the transmitter housing and grounded at the monitoring rack.

Installation Guidelines

  • Cable Protection: Route field wiring through the M20 conduit fitting. Ensure that proper sealing is used at the conduit entry to prevent moisture from traveling down the conduit into the transmitter enclosure.
  • Mounting Torque: Tighten the probe sleeve locknut to 39.3 N-m (350 in-lb) and the outer sleeve housing retaining nut to 29.5 N-m (260 in-lb) to maintain structural integrity and a solid environmental seal.
  • Physical Adjustments: The threaded sleeve assembly allows for +/-12.7 mm (+/-0.5 in) of mechanical adjustment to facilitate physical positioning and probe gapping.

Compliance and Certifications

  • CE Mark: Compliant with applicable European directives.
  • ATEX / IECEx (Multiple Approvals): Ex ia IIC T4/T5 Ga, Ex ia IIIC T90C/T105C Dc when installed with intrinsically safe zener barriers or galvanic isolators.
  • cNRTLus (Multiple Approvals): Class I, Zone 0: AEx/Ex ia IIC T4/T5 Ga; Class I, Division 1, Groups A, B, C, and D.
  • Non-Incendive: Ex nA IIC T4/T5 Gc; Class I, Division 2, Groups A, B, C, and D when installed per manufacturer control drawings.
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Bently Nevada 330881-28-09-123-03-02 PROXPAC XL Proximity Transducer

What does Option 28 represent on the 330881-28-09-123-03-02?

Option 28 indicates that this transducer assembly is equipped with a 3300 XL 8 mm proximity probe configured with Multiple Approvals (ATEX, IECEx, and cNRTLus) for hazardous environments.

How are the standoff and penetration depths specified on this metric PROXPAC XL?

This specific configuration (330881-28-09-123-03-02) features a 90 mm metric standoff adapter (Option 09) and a 123 mm metric probe sleeve penetration depth (Option 123).

What type of fittings and mounting threads does this configuration use?

The assembly features Option 03 (one M20 conduit fitting and two plugs) and Option 02, which provides a standard 3/4-14 NPT mounting thread required for standoff adapter setups.

Penghantaran Ekspres Global

  • Penghantaran Standard: 4-6 Hari Perniagaan melalui DHL, FedEx, dan UPS.
  • Penghantaran Ekspres: Penghantaran pada hari yang sama untuk pesanan dalam stok yang dibuat sebelum 2:00 PM (GMT+8).
  • Liputan Seluruh Dunia: Berkhidmat di lebih 150 negara, termasuk penghantaran pantas ke Arab Saudi dan UAE.

Pemulangan & Jaminan

  • Jaminan 30 Hari: Pemulangan diterima untuk produk dalam stok dalam pembungkusan asal yang disegel kilang.
  • Jaminan 12 Bulan: Setiap komponen industri disokong oleh jaminan teknikal profesional kami.

Pesanan diproses dan dihantar Isnin-Jumaat (tidak termasuk cuti umum).


Untuk kelayakan penuh, yuran penyimpanan semula, dan butiran pemulangan antarabangsa, sila lihat rasmi kami Polisi Pemulangan & Bayaran Balik .

TECHNICAL SPECIFICATIONS

Country of origin
Amerika Syarikat

Produk yang Baru Dilihat

Pengetahuan teknikal

Penggerak Elektrik Direka untuk Menggantikan Sistem Kuasa Cecair: Panduan Automasi Industri Praktikal

Artikel ini menerangkan bagaimana aktuator elektrik bersepadu, seperti siri e-Actuator SMC, mengubah kawalan gerakan industri dengan menggantikan sistem pneumatik dan hidraulik tradisional. Ia...

Operasi Matematik Menggunakan OpenPLC untuk Aplikasi Automasi Industri

Artikel ini menerangkan bagaimana sistem PLC melaksanakan operasi matematik teras seperti penambahan, penolakan, pendaraban, pembahagian, modulo, dan perpangkatan dalam automasi industri. Ia...

Logik Boolean Lanjutan dengan Pengaturcaraan PLC FBD: Aplikasi Industri Praktikal Melebihi Logik Asas

Artikel ini menerangkan beberapa fungsi logik Boolean lanjutan yang digunakan dalam pengaturcaraan PLC selain operasi asas AND, OR, dan NOT. Ia merangkumi bagaimana alat seperti jadual kebenaran,...

Logik Boolean dalam Pengaturcaraan PLC: Memahami Pintu Logik FBD

Logik Boolean adalah asas bagi setiap program PLC. Dari kawalan mesin yang mudah hingga sistem automasi industri yang kompleks, pintu logik menentukan bagaimana pengawal bertindak balas terhadap...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan untuk Pengapit Robotik: Dari Pengendalian Halus hingga Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diilhamkan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang dikuasakan...