1 daripada 1

Mitsubishi Electric FR-A840-03610-2-60 FR-A800 Variable Frequency Drive

Mitsubishi Electric FR-A840-03610-2-60 FR-A800 Variable Frequency Drive

Hanya 10 item tinggal dalam stok
  • Pengilang: Mitsubishi Electric

  • No. Produk: FR-A840-03610-2-60

  • Negara asal:Amerika Syarikat

  • Jenis Produk: Variable Frequency Drives

  • Pembayaran: T/T, Western Union

  • Berat: 80000g

  • Pelabuhan penghantaran: Xiamen

  • Jaminan: 12 bulan

Kuantiti
Lihat butiran penuh

Description

Engineered for highly demanding industrial automation applications, the Mitsubishi Electric FR-A840-03610-2-60 variable frequency drive provides advanced speed, torque, and vector control as part of the premier FR-A800 Series. This high-capacity, three-phase inverter is configured as a standard model featuring specialized circuit board conformal coating (Class 3C2) for superior environmental resistance in harsh operating conditions, though it does not include plated conductors. Utilizing an adaptable multi-rating architecture, it optimizes performance across various duty cycles, ensuring robust motor control and minimized downtime in complex system integrations.

Features

  • Conformal Coating (3C2): Enhanced defense against dust, humidity, and corrosive atmospheric gases.
  • Multi-Rating Flexibility: Four built-in overload ratings (SLD, LD, ND, HD) to match specific load characteristics.
  • Advanced Vector Control: Supports Real Sensorless Vector Control (RSV) and PM sensorless vector control for precise torque performance.
  • Energy-Saving Technology: Optimum excitation control maximizes motor efficiency and minimizes power consumption.
  • Comprehensive Safety Functions: Features integrated safe torque off (STO) safety inputs complying with global safety standards.

Applications

  • High-capacity water and wastewater pumping networks.
  • Industrial fan systems and air handling units with variable torque demands.
  • Extruders, mixers, and heavy-duty conveyor systems.
  • Hoisting, crane, and material handling systems requiring high starting torque.

Technical Specifications

Parameter Specification Value
Manufacturer Mitsubishi Electric
Model Code FR-A840-03610-2-60
Series FR-A800 Series
Voltage Class 400V Class (Three-Phase 380V to 500V AC, 50/60Hz)
SLD Rated Current 361 A (Super Light Duty)
LD Rated Current 310 A (Light Duty)
ND Rated Current 260 A (Normal Duty)
HD Rated Current 216 A (Heavy Duty)
Structure/Functionality Standard Model (Type 0)
Board Coating With Conformal Coating (IEC 60721-3-3 Class 3C2)
Plated Conductor Without Plating
Cooling Method Forced Air Cooling
Operating Temperature -10 degC to +50 degC (non-freezing, matching rated load capacity)
Shipping Weight (Calculated) 80.0 kg

Connections and Interfaces

Terminal Group Description & Assignment
R/L1, S/L2, T/L3 Three-phase AC power input supply terminals
U, V, W Three-phase AC output connections to the motor
STF / STR Forward Start / Reverse Start digital input control commands
SD / PC Common terminal for contact input / External transistor power source (24VDC)
A1, B1, C1 Relay output terminals (Fault output indicator)

Empirical Engineering Insights

Alternative Models & Compatibility

When replacing an older legacy series inverter (such as the FR-A740 series), keep in mind that control terminal configurations are substantially compatible, but terminal block positioning and dimensions may vary. The "-2-60" suffix indicates this drive features specialized 3C2 conformal board coating; it serves as a direct, rugged upgrade to standard uncoated variants (such as the base FR-A840-03610) without modifying any application parameters or cabinet configurations.

Application Pitfalls & Engineering Notes

At the 361A Super Light Duty rating, the drive is highly sensitive to input supply phase imbalances. Ensure line-side voltage deviation does not exceed 3% between phases to prevent localized overheating in the input rectifier bridge. Because this model does not feature plated conductors, avoid deploying this specific configuration in environments with active exposure to direct hydrogen sulfide gas unless the main enclosure is sealed to an IP54 or higher standard and utilizes external heat exchanges.

Commissioning & Wiring Tips

Verify the position of the slide switch on the control terminal circuit board to correctly select between SINK (NPN) and SOURCE (PNP) logic states before powering up the drive's control circuitry. Improper selection may lead to internal control board damage or unexpected behavior of digital inputs. Keep control signal wiring separated from high-power motor cabling by at least 30 cm, crossing them only at right angles to minimize electro-magnetic interference (EMI).

Installation Guidelines

CRITICAL WARNING: HIGH VOLTAGE HAZARD

Isolate all electrical power sources before performing mechanical installation or internal wiring. Verify that the DC bus charge indicator LED on the front cover is completely unlit, and measure the voltage across terminal blocks P/+ and N/- using a calibrated voltmeter to ensure it is below 45V DC. Failure to follow discharge protocol can result in catastrophic shock or fatal injury.

1

Mount the inverter vertically to a rigid, non-flammable vertical support panel. Ensure at least 10 cm of clear vertical space above and below the unit to allow free airflow from the forced cooling fans.

2

Connect the dedicated ground terminal to the main system grounding point using heavy gauge wire conforming to local electrical codes to mitigate high-frequency leakage currents.

3

Wire the main power input terminals (R/L1, S/L2, T/L3) and the motor output terminals (U, V, W) using appropriately sized cable lugs torqued precisely to the manufacturer's specified tightening values.

Loading product navigation…

What is the primary function of the -60 suffix in this specific model?

The -60 suffix specifies that the control and power circuit boards are protected with an IEC 60721-3-3 Class 3C2 conformal coating, which provides safety and corrosion resistance in highly humid or dusty environments.

Does this model come equipped with plated conductors?

No, this specific configuration (FR-A840-03610-2-60) is configured without plated conductors.

What are the output current ratings for the different duty cycles of this drive?

This drive features multiple ratings: Super Light Duty (SLD) is 361A, Light Duty (LD) is 310A, Normal Duty (ND) is 260A, and Heavy Duty (HD) is 216A.

Can I use this inverter in an environment with high vibrational stress?

Yes, standard mechanical mounting with adequate vibration dampening is recommended. The heavy-duty physical chassis is designed for panel installations inside robust industrial cabinets.

Penghantaran Ekspres Global

  • Penghantaran Standard: 4-6 Hari Bekerja melalui DHL, FedEx, dan UPS.
  • Penghantaran Ekspres: Penghantaran pada hari yang sama untuk pesanan dalam stok yang dibuat sebelum 2:00 PM (GMT+8).
  • Liputan Seluruh Dunia: Berkhidmat di lebih 150 negara, termasuk penghantaran pantas ke Arab Saudi dan UAE.

Pemulangan & Jaminan

  • Jaminan 30 Hari: Pemulangan diterima untuk produk dalam stok dalam pembungkusan asal yang disegel kilang.
  • Jaminan 12 Bulan: Setiap komponen industri disokong oleh jaminan teknikal profesional kami.

Pesanan diproses dan dihantar Isnin-Jumaat (tidak termasuk cuti umum).


Untuk kelayakan penuh, yuran penyimpanan semula, dan butiran pemulangan antarabangsa, sila lihat rasmi kami Polisi Pemulangan & Pengembalian Wang .

TECHNICAL SPECIFICATIONS

Country of origin
Amerika Syarikat

Produk yang Baru Dilihat

Pengetahuan teknikal

Penggerak Elektrik Direka untuk Menggantikan Sistem Kuasa Cecair: Panduan Automasi Industri Praktikal

Artikel ini menerangkan bagaimana aktuator elektrik bersepadu, seperti siri e-Actuator SMC, mengubah kawalan gerakan industri dengan menggantikan sistem pneumatik dan hidraulik tradisional. Ia...

Operasi Matematik Menggunakan OpenPLC untuk Aplikasi Automasi Industri

Artikel ini menerangkan bagaimana sistem PLC melaksanakan operasi matematik teras seperti penambahan, penolakan, pendaraban, pembahagian, modulo, dan perpangkatan dalam automasi industri. Ia...

Logik Boolean Lanjutan dengan Pengaturcaraan FBD PLC: Aplikasi Industri Praktikal Melebihi Logik Asas

Artikel ini menerangkan beberapa fungsi logik Boolean lanjutan yang digunakan dalam pengaturcaraan PLC selain operasi asas AND, OR, dan NOT. Ia merangkumi bagaimana alat seperti jadual kebenaran,...

Logik Boolean dalam Pengaturcaraan PLC: Memahami Pintu Logik FBD

Logik Boolean adalah asas bagi setiap program PLC. Dari kawalan mesin yang mudah hingga sistem automasi industri yang kompleks, pintu logik menentukan bagaimana pengawal bertindak balas terhadap...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan untuk Pengapit Robotik: Dari Pengendalian Halus hingga Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...