1 daripada 1

Weidmuller 8965370000 ACT20X-2HDI-2SDO-RNO-S Isolating Switch Amplifiers

Weidmuller 8965370000 ACT20X-2HDI-2SDO-RNO-S Isolating Switch Amplifiers

Hanya 10 item tinggal dalam stok
  • Pengilang: Weidmuller

  • No. Produk: 8965370000

  • Negara asal:Jerman

  • Jenis Produk: Isolating Switch Amplifiers

  • Pembayaran: T/T, Western Union

  • Berat: 190g

  • Dimensi: 117.2 mm x 22.5 mm x 113.6 mm

  • Pelabuhan penghantaran: Xiamen

  • Jaminan: 12 bulan

Kuantiti
Lihat butiran penuh

Weidmuller 8965370000 ACT20X-2HDI-2SDO-RNO-S Isolating Switch Amplifiers

Description

Designed for intrinsic safety applications, the Weidmuller 8965370000 functions as a highly reliable isolating switch amplifier to transmit digital signals from hazardous areas (Zone 0, 1, 2) to safe areas. This 2-channel module is engineered to process signals from NAMUR sensors or mechanical contacts located in explosive atmospheres, providing complete galvanic isolation between the input, output, power supply, and alarm contacts.

The ACT20X-2HDI-2SDO-RNO-S features integrated line fault detection (LFD) to monitor the input circuits for wire breaks or short circuits. In the event of a fault, the device triggers an alarm relay, ensuring rapid diagnostics and minimizing system downtime. Configuration is easily managed via standard FDT/DTM software, allowing precise customization of operational parameters to match specific process requirements.

Features

  • Dual-channel signal isolation and transmission from Ex to non-Ex zones.
  • Intrinsically safe input circuits compatible with NAMUR sensors and mechanical switches.
  • Two normally open (NO) relay outputs for reliable signal switching.
  • Comprehensive line fault detection (LFD) for short-circuit and wire-break monitoring.
  • FDT/DTM software configuration for flexible parameter adjustment.
  • Complete galvanic isolation between input, output, power supply, and alarm contacts.
  • Compact 22.5 mm DIN-rail mountable housing to optimize cabinet space.

Applications

  • Chemical and petrochemical processing plants.
  • Oil and gas extraction, refining, and distribution facilities.
  • Water and wastewater treatment automation.
  • Hazardous area digital signal isolation (Zone 0, 1, 2, and Class I Div 1/2).

Technical Specifications

Manufacturer Weidmuller
Part Number / Model 8965370000 (ACT20X-2HDI-2SDO-RNO-S)
Product Type Isolating Switch Amplifier
Number of Channels 2
Input Type NAMUR sensor (DIN EN 60947-5-6) or switch contact
NAMUR Supply 8 V DC / 8 mA
Output Type Relay (1 NO contact per channel)
Nominal Switching Voltage 125 V AC / 110 V DC (safe area)
Continuous Current 0.5 A AC / 0.3 A DC
Supply Voltage 19.2 to 31.2 V DC
Power Consumption ≤ 1.9 W
Configuration FDT/DTM software
Connection Type Screw connection
Protection Degree IP20
Operating Humidity 0 to 95% (no condensation)
Dimensions (H x W x D) 117.2 mm x 22.5 mm x 113.6 mm
Weight 0.190 kg

Connections and Interfaces

Terminal Pin Function
Inputs (Hazardous Area) Channel 1 & Channel 2 NAMUR / Switch Contacts
Outputs (Safe Area) Channel 1 & Channel 2 Relay NO Contacts
Power Supply 24 V DC (+ / -)
Alarm Output Fault signaling relay contact

Installation Guidelines

  • Mounting: Mount vertically on a standard TS 35 DIN rail.
  • Wiring: Ensure strict physical separation between intrinsically safe (Ex i) input wiring and non-intrinsically safe output/power wiring. Maintain a minimum distance of 50 mm between the terminal groups.
  • Grounding: Connect the DIN rail to the local functional earth ground to ensure proper shielding and noise immunity.
  • Ventilation: Provide adequate clearance above and below the module to prevent heat buildup inside the control cabinet.

Compliance and Certifications

  • CE
  • ATEX
  • IECEx
  • UL Class I, Division 2 / Zone 2
Loading product navigation…

What is the primary function of the Weidmuller 8965370000?

It is a 2-channel isolating switch amplifier designed to safely transmit digital signals (such as NAMUR sensors or mechanical contacts) from hazardous Ex zones to safe areas.

How is the ACT20X-2HDI-2SDO-RNO-S configured?

The module is configured using standard FDT/DTM software, allowing precise adjustment of input types, line fault detection, and output behavior.

What type of outputs does this module provide?

It features two normally open (NO) relay outputs, along with an integrated alarm relay for system status and fault signaling.

Does the 8965370000 support line fault detection?

Yes, it includes built-in line fault detection (LFD) to monitor input circuits for short circuits and wire breaks.

Penghantaran Ekspres Global

  • Penghantaran Standard: 4-6 Hari Perniagaan melalui DHL, FedEx, dan UPS.
  • Penghantaran Ekspres: Penghantaran pada hari yang sama untuk pesanan dalam stok yang dibuat sebelum 2:00 PM (GMT+8).
  • Liputan Seluruh Dunia: Berkhidmat di lebih 150 negara, termasuk penghantaran pantas ke Arab Saudi dan UAE.

Pemulangan & Jaminan

  • Jaminan 30 Hari: Pemulangan diterima untuk produk dalam stok dalam pembungkusan asal yang disegel kilang.
  • Jaminan 12 Bulan: Setiap komponen industri disokong oleh jaminan teknikal profesional kami.

Pesanan diproses dan dihantar Isnin-Jumaat (tidak termasuk cuti umum).


Untuk kelayakan penuh, yuran penyimpanan semula, dan butiran pemulangan antarabangsa, sila lihat rasmi kami Polisi Pemulangan & Bayaran Balik .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknikal

Logik Boolean dalam Pengaturcaraan PLC: Memahami Pintu Logik FBD

Logik Boolean adalah asas bagi setiap program PLC. Dari kawalan mesin yang mudah hingga sistem automasi industri yang kompleks, pintu logik menentukan bagaimana pengawal bertindak balas terhadap...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan Pengapit Robotik: Dari Pengendalian Halus ke Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...

Throwback: Bagaimana Motor Elektrik Awal Mengubah Perlombongan Bawah Tanah

Dari pemampat DC yang digerakkan tali ke troli lombong bertenaga bateri, operasi perlombongan awal menandakan titik perubahan dalam elektrifikasi industri. Artikel ini meneroka bagaimana motor...

Factory I/O: Alat Simulasi PLC Moden untuk Latihan Automasi Industri

Factory I/O sedang mengubah pendidikan PLC dengan menyediakan simulasi industri 3D yang mendalam untuk pelajar, jurutera, dan pasukan penyelenggaraan. Platform ini merapatkan jurang antara teori dan...

Pengaturcaraan Kitaran Gerakan Paksi Tunggal pada Pemacu Servo CMZ

Tutorial ini mengkaji bagaimana fungsi PLC terbina dalam pemacu servo CMZ SBD dapat melaksanakan program gerakan berdiri sendiri, termasuk logik homing, kawalan kedudukan, dan pergerakan paksi...