1 z 1

Beckhoff CX1010-0122 CX Series CPU Module

Beckhoff CX1010-0122 CX Series CPU Module

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: CX1010-0122

  • Country of origin:Niemcy

  • Product Type: PLC CPU Modules

  • Payment: T/T, Western Union

  • Weight: 500g

  • Dimensions: 58 mm x 120 mm x 91 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Ilość
Pokaż kompletne dane

Description

Architected as the central processing unit for modular control environments, the Beckhoff CX1010-0122 system module integrates an Intel Pentium MMX-compatible processor running at 500 MHz to handle basic PLC and motion control execution. This module functions as the execution core within a DIN-rail mounted control cluster, offering robust performance for legacy industrial networks and machine-level control systems. Equipped with 256 MB of non-expandable DDR RAM and an active Compact Flash Type II expansion slot, the CPU delivers deterministic processing capabilities when integrated with TwinCAT software control architectures.

Features

  • High-Efficiency Execution: Equipped with a 500 MHz Pentium MMX-compatible processor tailored for entry-level PLC and basic NC tasks.
  • Compact Storage: Features an accessible Compact Flash Type II slot with an integrated ejector, packaged with a 128 MB CF card.
  • Ethernet Connectivity: Built-in 10/100 Mbit/s RJ45 port for direct industrial networking and programming access.
  • Comprehensive Diagnostics: Five local LEDs provide direct hardware feedback for power, network speed, activity, TwinCAT status, and flash card access.
  • Flexible Bus Compatibility: Interfaces with K-bus, E-bus, and IP-Link I/O systems via compatible power supply modules.

Applications

  • Machine tool control and small-scale automation lines.
  • Building automation substations and HVAC management systems.
  • Material handling, sorting systems, and conveyor line control.
  • Legacy system migration and drop-in replacements for older CX series control racks.

Technical Specifications

Parameter Specification
Manufacturer Beckhoff
Model Number CX1010-0122
Processor Intel Pentium MMX compatible, 500 MHz
Number of Cores 1
Main Memory 256 MB DDR RAM (non-expandable)
Flash Memory Compact Flash Type II slot (128 MB CF card included)
Network Interfaces 1 x RJ45 10/100 Mbit/s
System Bus Link 16-bit ISA (PC/104)
Power Supply Via system bus (through connected CX1100-xxxx modules)
Max. Power Consumption 8 W
Diagnostic Indicators 1 x power, 1 x LAN speed, 1 x LAN activity, 1 x TC status, 1 x flash access
Internal Clock Battery-backed clock for date and time (battery replaceable)
Operating System Windows Embedded CE 6 / Windows Embedded Standard 2009
Control Software TwinCAT 2 PLC runtime or TwinCAT 2 NC PTP runtime
Protection Rating IP20
Operating Temperature 0 to +50 degC
Storage Temperature -25 to +85 degC
Relative Humidity 95%, non-condensing
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
Approvals/Markings CE, UL
Dimensions (W x H x D) 58 mm x 120 mm x 91 mm
Net Weight Approx. 355 g
Shipping Weight (Calculated) 3.0 kg (including protective packaging)

Empirical Engineering Insights

The hardware architecture of this CPU module demands specific maintenance considerations and configuration knowledge to ensure uninterrupted operation in industrial installations.

Alternative Models & Compatibility

This CPU module belongs to the legacy CX1010 hardware line. When replacing an older generation unit, verify your TwinCAT 2 license keys, as they are hard-coded to the unique System ID of the CPU. Upgrading to the higher-performance CX1020 or CX5100 series will require physical dimension adjustments on the DIN rail and project migration within TwinCAT 2.

Application Pitfalls & Engineering Notes

The module relies on entirely passive, fanless cooling. To prevent thermal throttling under high CPU utilization, do not block the air vents on the top and bottom of the housing. Maintain a minimum vertical clearance of 30 mm inside the electrical enclosure. Additionally, ensure that only SLC-type (Single-Level Cell) Compact Flash cards are used for the OS partition, as multi-level cell cards can experience premature failure due to continuous OS read/write cycles.

Commissioning & Wiring Tips

This CPU has no direct power terminals on its faceplate. It relies entirely on a connected CX1100-xxxx series power supply module. Ensure that the PC/104 system bus connector pins are straight and clean before joining the CPU to the power supply module. Misaligned pins during assembly can cause immediate system bus failure or permanent damage to the CPU motherboard when energized.

Installation Guidelines

CRITICAL WARNING: Never mount, demount, or adjust connections on the CPU assembly while the system is powered. Ensure all supply lines to connected CX1100 power supply modules and associated I/O modules are completely de-energized to prevent current spikes and potential system bus destruction.
1
Position the CPU module onto the 35 mm DIN rail next to the corresponding CX1100 power supply module, ensuring the PC/104 connectors align precisely.
2
Firmly push the modules together until they click into place on the rail, securing the mechanical latch to prevent shifting.
3
Insert the pre-configured Compact Flash card containing the system software into the Type II slot before initiating power-on sequence.
4
Connect the RJ45 industrial Ethernet cable to the native port to establish communications, then apply power via the main supply module.

What operating systems are supported by the CPU module?

This module is designed to run Windows Embedded CE 6 or Windows Embedded Standard 2009, optimized for industrial control applications.

Can the system memory on this CPU module be expanded?

No, the onboard 256 MB DDR RAM is integrated directly onto the system board and cannot be expanded or upgraded.

Does this module support both Beckhoff K-bus and E-bus terminals?

Yes, it supports both I/O architectures, but communication must be routed and powered through the connected CX1100 series power supply module.

What type of Compact Flash card should be used in this module?

It is highly recommended to use SLC-type (Single-Level Cell) Compact Flash cards in the Type II slot to ensure industrial-grade durability and write-cycle longevity.

Globalna ekspresowa wysyłka

  • Standardowa dostawa: 4-6 dni roboczych za pośrednictwem DHL, FedEx i UPS.
  • Ekspresowa wysyłka: Wysyłka tego samego dnia dla zamówień dostępnych w magazynie złożonych przed godziną 14:00 (GMT+8).
  • Globalne pokrycie: Obsługujemy ponad 150 krajów, w tym szybką dostawę do Arabii Saudyjskiej i ZEA.

Zwroty i gwarancja

  • 30-dniowa gwarancja: Zwroty przyjmowane są dla produktów dostępnych w magazynie, w oryginalnym, fabrycznie zapieczętowanym opakowaniu.
  • 12-miesięczna gwarancja: Każdy komponent przemysłowy objęty jest naszą profesjonalną gwarancją techniczną.

Zamówienia są przetwarzane i dostarczane od poniedziałku do piątku (z wyłączeniem dni świątecznych).


Aby poznać pełne warunki kwalifikowalności, opłaty za przyjęcie towaru z powrotem oraz szczegóły dotyczące zwrotów międzynarodowych, prosimy zapoznać się z naszym oficjalnym Polityka zwrotów i zwrotu pieniędzy .

TECHNICAL SPECIFICATIONS

Country of origin
Niemcy

Ostatnio oglądane produkty

Wiedza techniczna

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...