1 z 1

EL9515 BECKHOFF 15 V DC Power Supply Terminal with Diagnostics

EL9515 BECKHOFF 15 V DC Power Supply Terminal with Diagnostics

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: EL9515

  • Country of origin:Niemcy

  • Product Type: Power supply terminal 15 V DC

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 12 mm x 100 mm x 68 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Ilość
Pokaż kompletne dane

Product Overview

The EL9515 (EL9515) is a high-precision power supply terminal designed to convert a standard 24 V DC input into a stabilized 15 V DC output within the EtherCAT terminal system. This module is specifically engineered to provide clean, low-noise power to specialized field devices—such as high-end analog sensors, encoders, or transducers—that require a 15 V potential. Equipped with integrated diagnostics and an overcurrent LED, the EL9515 ensures the integrity of the secondary power circuit. Its compact 12 mm design and ATEX certification make it an essential component for B2B industrial applications in hazardous areas, laboratory automation, and precision instrumentation where voltage stability is critical.

Technical Configuration (Deep Dive)

The EL9515 functions as a DC/DC converter, drawing power from the 24 V DC power contacts and providing a regulated 15 V DC output at a maximum current of 0.5 A. The output is exceptionally stable, boasting a ±1 % tolerance and a residual ripple of < 5 mV, which is vital for preventing signal jitter in sensitive analog measurements.

Safety and system uptime are prioritized through short-circuit proof circuitry and comprehensive diagnostics. The terminal reports its operational status—including overcurrent or fault conditions—directly into the EtherCAT process image. This allows the master controller to monitor the health of the 15 V supply in real-time. For visual inspection, a dedicated diagnostic LED provides immediate feedback on the module’s status without requiring a software connection.

Technical Specifications

Attribute Specification Details
Model EL9515
Brand BECKHOFF
Input Voltage 24 V DC (-15 % / +20 %)
Output Voltage 15 V DC (±1 %)
Output Current 0.5 A
Residual Ripple < 5 mV
Short-Circuit Proof Yes
Diagnostics Yes (Process image + Overcurrent LED)
Electrical Isolation 500 V (E-bus / Field potential)
Current Consumption (E-bus) Typically 90 mA
Operating Temperature 0 to +55 Celsius
Protection Rating IP20
Approvals CE, UL, ATEX (Ex nA IIC T4 Gc)

Technical FAQs

How do I access the diagnostics for the EL9515?

The diagnostics are mapped into the EtherCAT process image. You can link these variables in TwinCAT to monitor for "Under Voltage" or "Overcurrent" states. Additionally, the red LED on the front of the terminal will illuminate if the 0.5 A current threshold is exceeded.

Does the EL9515 provide power to the next terminal via power contacts?

The 15 V output is provided via the terminal connection points for field wiring. The internal power contacts (blades) typically carry the primary 24 V DC supply to downstream modules. Always verify the current path in your specific hardware configuration to ensure the 15 V potential is routed only where intended.

Is this terminal suitable for use in explosive atmospheres?

Yes. The EL9515 carries the ATEX marking (II 3 G Ex nA IIC T4 Gc), making it suitable for installation in Zone 2 hazardous areas when housed in an appropriately rated enclosure.


Engineering & Installation Guide

  • Voltage Sensitivity: Due to the low residual ripple (< 5 mV), this module is ideal for supplying power to high-resolution analog-to-digital converters (ADCs). To maintain this performance, keep the 15 V supply leads as short as possible and separate them from high-interference AC lines.

  • Wiring and Termination: The terminal features ES series pluggable wiring, allowing for the removal of the wiring level without disconnecting individual leads. Use a screwdriver to actuate the spring clamps, ensuring a stripping length of 8 to 9 mm for a secure, vibration-resistant connection.

  • Thermal Considerations: While the module is rated for 0.5 A, ensure the 24 V DC input supply is robust. The conversion process generates a small amount of heat; ensure the 12 mm terminal has sufficient vertical clearance (30 mm) for convective cooling within the cabinet.

Engineering Advantages

The EL9515 excels by eliminating the need for bulky, external 15 V power supplies, thereby saving significant DIN rail space. Its 500 V galvanic isolation protects the EtherCAT backplane from potential field-side electrical anomalies. Conforming to EN 61000-6-2/4 for EMC, it is built to operate reliably in electrically noisy industrial environments. For B2B machine builders, the integrated diagnostic feedback simplifies the creation of sophisticated HMI alerts, ensuring that power supply issues are identified and resolved before they lead to broader system failures.

 

Globalna ekspresowa wysyłka

  • Standardowa dostawa: 4-6 dni roboczych za pośrednictwem DHL, FedEx i UPS.
  • Ekspresowa wysyłka: Wysyłka tego samego dnia dla zamówień dostępnych w magazynie złożonych przed godziną 14:00 (GMT+8).
  • Globalne pokrycie: Obsługujemy ponad 150 krajów, w tym szybką dostawę do Arabii Saudyjskiej i ZEA.

Zwroty i gwarancja

  • 30-dniowa gwarancja: Zwroty przyjmowane są dla produktów dostępnych w magazynie, w oryginalnym, fabrycznie zapieczętowanym opakowaniu.
  • 12-miesięczna gwarancja: Każdy komponent przemysłowy objęty jest naszą profesjonalną gwarancją techniczną.

Zamówienia są przetwarzane i dostarczane od poniedziałku do piątku (z wyłączeniem dni świątecznych).


Aby poznać pełne warunki kwalifikowalności, opłaty za przyjęcie towaru z powrotem oraz szczegóły dotyczące zwrotów międzynarodowych, prosimy zapoznać się z naszym oficjalnym Polityka zwrotów i zwrotu pieniędzy .

TECHNICAL SPECIFICATIONS

Color pattern
Biały
Country of origin
Niemcy

Ostatnio oglądane produkty

Wiedza techniczna

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...