Product Overview
The DSDI 110 (Product ID: 57160001-A/13) is a high-density Digital Input Board belonging to the ABB S100 I/O system. It is designed for use with Advant OCS with Master Software, 800xA, and MasterPiece 200/1 controllers. The board serves as a physical interface between external field sensors and the control system, processing discrete signals from switches, pushbuttons, and relay contacts. It features 32 input channels organized into groups, utilizing optical isolation to protect the internal controller logic from field-side electrical interference and transients.
Technical Specifications
| Parameter |
Specification |
| Model |
DSDI 110 |
| Product ID |
57160001-A/13 |
| Brand |
ABB |
| Product Type |
Digital Input Board (Opto-isolated) |
| Series |
S100 I/O |
| Number of Channels |
32 Inputs |
| Input Voltage |
24 V DC |
| Isolation |
Optical Isolation (Opto-Isol) |
| System Compatibility |
Advant OCS, 800xA, MasterPiece 200, MOD 300 |
| Mounting Type |
Subrack / Rack Mount (S100 I/O Rack) |
| Product Net Weight |
0.44 kg |
| Dimensions |
Standard S100 Module Width |
| Country of Origin |
Sweden |
| Customs Tariff Number |
85389091 |
Ordering Information
| Item |
Details |
| Global Commercial Alias |
DSDI 110 |
| Primary Product ID |
57160001-A/13 |
| Replacement Product ID (NEW) |
3BSE018295R1 |
| Part Type |
Spare Part / New |
| Minimum Order Quantity |
1 Piece |
| Standard Lead Time |
Subject to stock availability (Singapore Warehouse) |
Engineering & Installation Guide
Wiring and Shielding
All digital input signals should be wired using twisted-pair cables. For high-noise environments, shielded cables are recommended. The shield should be grounded at a single point, typically at the subrack grounding bar, to prevent ground loops. Ensure that the 24 V DC field power supply is stable and meets the ripple specifications required by the S100 I/O bus.
Module Replacement Precautions
When replacing an existing 57160001-A/13 board with the new replacement model 3BSE018295R1, verify the hardware revision and jumper settings (if applicable) on the backplane or the board itself. The S100 I/O system supports hot-replacement in many configurations, but it is best practice to power down the specific I/O branch if the process safety allows, to prevent accidental short circuits during insertion.
Lifecycle and Obsolescence
The DSDI 110 is a legacy component within the Advant OCS and MasterPiece ecosystems. While still available as a spare part, users should consider the lifecycle status. The 3BSE018295R1 is the current functional replacement. It is highly recommended to maintain a critical spare stock of at least 10% of the installed base for plants running 24/7 operations, as lead times for legacy S100 parts can fluctuate.
Common Installation Mistakes
-
Incorrect Polarities: Reversing the 24 V DC input common can lead to non-responsive channels or damage to the optocouplers.
-
Backplane Seating: Ensure the board is fully seated in the rack and the locking screws are tightened. Poor contact with the S100 bus connector can cause intermittent "Module Missing" errors in the controller diagnostics.
FAQs
-
Q: Can I use the DSDI 110 in an 800xA system?
-
Q: What is the difference between 57160001-A/13 and 3BSE018295R1?
-
Q: How do I identify a faulty channel?
-
Q: Is external fuse protection required?