1 of 6

ABB S100 I/O 57160001-A/13 DSDI-110 Digital Input Board

ABB S100 I/O 57160001-A/13 DSDI-110 Digital Input Board

Only 5 item(s) left in stock
  • Manufacturer: ABB

  • Product No.: DSDI-110

  • Country of origin:Sweden

  • Product Type: Digital Input Board

  • Barcode: 85371099

  • Payment: T/T, Western Union

  • Weight: 300g

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Product Overview

The DSDI 110 (Product ID: 57160001-A/13) is a high-density Digital Input Board belonging to the ABB S100 I/O system. It is designed for use with Advant OCS with Master Software, 800xA, and MasterPiece 200/1 controllers. The board serves as a physical interface between external field sensors and the control system, processing discrete signals from switches, pushbuttons, and relay contacts. It features 32 input channels organized into groups, utilizing optical isolation to protect the internal controller logic from field-side electrical interference and transients.

Technical Specifications

Parameter Specification
Model DSDI 110
Product ID 57160001-A/13
Brand ABB
Product Type Digital Input Board (Opto-isolated)
Series S100 I/O
Number of Channels 32 Inputs
Input Voltage 24 V DC
Isolation Optical Isolation (Opto-Isol)
System Compatibility Advant OCS, 800xA, MasterPiece 200, MOD 300
Mounting Type Subrack / Rack Mount (S100 I/O Rack)
Product Net Weight 0.44 kg
Dimensions Standard S100 Module Width
Country of Origin Sweden
Customs Tariff Number 85389091

Ordering Information

Item Details
Global Commercial Alias DSDI 110
Primary Product ID 57160001-A/13
Replacement Product ID (NEW) 3BSE018295R1
Part Type Spare Part / New
Minimum Order Quantity 1 Piece
Standard Lead Time Subject to stock availability (Singapore Warehouse)

Engineering & Installation Guide

Wiring and Shielding

All digital input signals should be wired using twisted-pair cables. For high-noise environments, shielded cables are recommended. The shield should be grounded at a single point, typically at the subrack grounding bar, to prevent ground loops. Ensure that the 24 V DC field power supply is stable and meets the ripple specifications required by the S100 I/O bus.

Module Replacement Precautions

When replacing an existing 57160001-A/13 board with the new replacement model 3BSE018295R1, verify the hardware revision and jumper settings (if applicable) on the backplane or the board itself. The S100 I/O system supports hot-replacement in many configurations, but it is best practice to power down the specific I/O branch if the process safety allows, to prevent accidental short circuits during insertion.

Lifecycle and Obsolescence

The DSDI 110 is a legacy component within the Advant OCS and MasterPiece ecosystems. While still available as a spare part, users should consider the lifecycle status. The 3BSE018295R1 is the current functional replacement. It is highly recommended to maintain a critical spare stock of at least 10% of the installed base for plants running 24/7 operations, as lead times for legacy S100 parts can fluctuate.

Common Installation Mistakes

  • Incorrect Polarities: Reversing the 24 V DC input common can lead to non-responsive channels or damage to the optocouplers.

  • Backplane Seating: Ensure the board is fully seated in the rack and the locking screws are tightened. Poor contact with the S100 bus connector can cause intermittent "Module Missing" errors in the controller diagnostics.


FAQs

  • Q: Can I use the DSDI 110 in an 800xA system?

    • A: Yes, the DSDI 110 is compatible with 800xA systems that utilize S100 I/O racks connected via CI810 or equivalent bus extenders.

  • Q: What is the difference between 57160001-A/13 and 3BSE018295R1?

    • A: 57160001-A/13 is the original manufacturing part number. 3BSE018295R1 is the updated ABB global order number for the equivalent replacement unit. They are functionally identical.

  • Q: How do I identify a faulty channel?

    • A: Check the LED status on the front panel of the DSDI 110. If the input signal is present at the terminal block (measured with a multimeter) but the corresponding LED and controller variable do not update, the internal optocoupler for that channel may be failed.

  • Q: Is external fuse protection required?

    • A: While the board has internal protection, it is standard engineering practice to fuse the 24 V DC field power distribution in groups to prevent a single field short from taking down the entire I/O board.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Green
Country of origin
Sweden
Power source
DC Power

Recently Viewed Products

Technical knowledge

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...

Throwback: How Early Electric Motors Changed Underground Mining

From rope-driven DC compressors to battery-powered mine carts, early mining operations marked a turning point in industrial electrification. This article explores how electric motors transformed...

Factory I/O: A Modern PLC Simulation Tool for Industrial Automation Training

Factory I/O is transforming PLC education by delivering immersive 3D industrial simulations for students, engineers, and maintenance teams. The platform bridges the gap between theory and real-world...

Programming Single-Axis Motion Cycles on a CMZ Servo Drive

This tutorial examines how onboard PLC functionality inside a CMZ SBD servo drive can execute standalone motion programs, including homing logic, position control, and cyclic axis movement without an...

Single-Axis Motion Control Setup with CMZ Servo Drives

This tutorial explores the commissioning of a single-axis servo motion system using a CMZ SBD drive, covering hardware setup, axis scaling, homing configuration, and safe motion verification for...

Mitsubishi FX PLC Integration With FR-D700 VFD and HMI Control

This tutorial explains how Mitsubishi FX PLCs integrate with FR-D700 VFDs and HMI panels for forward/reverse motor control. It covers wiring logic, parameter configuration, ladder programming, and...