The Allen-Bradley 1746-NR4 is a four-channel RTD and direct-resistance input module for the SLC 500 1746 I/O platform. Each channel is configured independently for its sensor type, excitation current, data format, and digital filter. The module reports converted values through the SLC image table and provides channel diagnostics for open-circuit, short-circuit, configuration, and out-of-range conditions.

Technical Specifications

Catalog number 1746-NR4
Module type RTD/resistance input module
Input channels 4, individually configurable
Supported RTDs Platinum 385 and 3916 (100, 200, 500, and 1000 ohm); Copper 426 (10 ohm); Nickel 618 and 672 (120 ohm); Nickel-Iron 518 (604 ohm)
Direct-resistance ranges 0–150, 0–500, 0–1000, and 0–3000 ohm ranges; the 3000-ohm range is limited to 1900 ohm when 2.0 mA excitation is selected
Excitation current 0.5 mA or 2.0 mA, selected per channel; the 10-ohm copper RTD requires 2.0 mA
Filter selections 10, 50, 60, or 250 Hz
Step response 300 ms at 10 Hz; 60 ms at 50 Hz; 50 ms at 60 Hz; 12 ms at 250 Hz
Backplane current 50 mA at 5 V DC and 50 mA at 24 V DC
Input-to-backplane isolation 500 V AC for 1 minute
Channel-to-channel isolation None
Common-mode separation ±1 V maximum

Wiring and Configuration

The 1746-NR4 accepts two-wire and three-wire RTDs. A four-wire sensor is connected as a three-wire device; one compensation lead is not used. For two-wire or three-wire circuits, use cable with consistent conductor impedance. Record the existing terminal assignment, sensor coefficient, excitation current, filter, temperature units, and data format before replacing a module.

The filter setting is an engineering trade-off. A 10 Hz filter gives stronger 50/60 Hz rejection but a 300 ms step response. The 250 Hz setting responds in 12 ms with less noise rejection. Changing this setting can alter both update time and measurement stability without any wiring change.

Installation and Replacement Notes

  • Install the module in any modular SLC 500 chassis slot except slot 0.
  • Check the chassis power budget for both the 5 V and 24 V backplane rails.
  • Verify compatibility before using the module in a 1746-A2 fixed I/O expansion chassis.
  • Do not substitute 1746-NR8 settings or terminal assumptions for the 1746-NR4.
  • Confirm the channel status word before replacing hardware; recoverable sensor and configuration faults differ from non-recoverable module faults.

Documentation

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Allen-Bradley 1746-NR4 SLC 500 RTD/Resistance Input Module

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details
Loading product navigation…

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Technical knowledge

Allen-Bradley 1746-NR4 RTD Faults: Wiring, Excitation, and Filter Checks

A field checklist for diagnosing Allen-Bradley 1746-NR4 RTD and resistance inputs, including sensor curves, lead compensation, excitation current, filter timing and channel diagnostics.

Replacing an Allen-Bradley 1785-L40B: PLC-5/40 Checks Before Migration

A field-focused checklist for replacing an Allen-Bradley 1785-L40B or planning a PLC-5/40 migration, covering backups, 1771 I/O mapping, DH+/RIO channels, revision risks and commissioning.

Allen-Bradley 1747-SN: RIO Mapping and Link Fault Checks

Replacing an Allen-Bradley 1747-SN scanner? Check SLC 500 logical rack and G-file mapping, link speed, cable termination, COMM/FAULT LEDs and hardware series before blaming the module or changing the...

Allen-Bradley 1771-IG: TTL Logic and 5 V Wiring Checks

Check 1771-IG TTL HIGH/LOW logic thresholds, field supply ripple and 1771-WC wiring before replacing an input module.

AKS 33 vs AKS 3000: Checks Before Replacing a Pressure Transmitter

A field checklist for distinguishing Danfoss 060G2105, 060G1323 and 060G2109 by pressure range, fitting, loop signal and controller scaling.

Diagnosing DeltaV SE5009 Power Problems Before Replacement