The Allen-Bradley 1756-OA8D is a ControlLogix 120V AC diagnostic output module designed for high-reliability industrial automation environments. Operating as an 8-point electronically fused output device, it provides comprehensive point-level diagnostic detection—including open wire, field power loss, blown fuse, no load, and output verification faults—to ensure optimal operational integrity across PLC, DCS, and automated process control systems.
Description
The Allen-Bradley 1756-OA8D ControlLogix output module delivers solid-state switching for 120V AC field devices. Operating within a voltage range of 74 to 132V AC (47 to 63 Hz), the module features 8 diagnostic output points arranged in two groups of 4 points. It utilizes Producer/Consumer technology to share output status and comprehensive diagnostic data seamlessly across the ControlLogix backplane.
Engineered for critical industrial applications, the 1756-OA8D provides advanced diagnostic reporting to identify field wiring issues, short circuits, or power disruptions. Off-state detection identifies no-load conditions, while on-state output verification ensures commanded states match actual field conditions. Individual electronic fusing helps protect each output point against overcurrent and short-circuit events.
Features
8 diagnostic output channels organized into 2 isolated groups of 4 points each.
Point-level diagnostic features including FuseBlown, NoLoad, OutputVerifyFault, and FieldPwrLoss.
Individual electronic fusing per output point.
Configurable output states in Program Mode and Fault Mode (Hold Last State, On, or Off).
Coordinated System Time (CST) timestamping for diagnostic event tracking.
Support for Scheduled Outputs with CST synchronization.
Electronic keying via software configuration to prevent module misplacement.
Applications
Discrete AC actuator and valve control
Motor starter and contactor switching
Industrial process output control
Safety signaling and indicator control
Automated manufacturing systems
Technical Specifications
Parameter
Specification
Manufacturer
Allen-Bradley / Rockwell Automation
Outputs
8 diagnostic, electronic fusing (4 points/group)
Voltage Category
120V AC 50/60 Hz
Operating Voltage Range
74…132V AC, 47…63 Hz
Output Delay Time (Off to On / On to Off)
9.3 ms @ 60 Hz, 11 ms @ 50 Hz
Current Draw @ 5.1V DC
175 mA
Current Draw @ 24V DC
250 mA
Total Backplane Power
6.89 W
Power Dissipation, Max
5.3 W @ 60 degC (140 degF)
Thermal Dissipation
18.0 BTU/hr
Off-State Leakage Current, Max
3 mA per point
On-State Voltage Drop, Max
2.5V peak @ 0.5 A; 3V peak @ 1 A
Current per Point, Max
1 A @ 30 degC (86 degF) linear derating; 0.5 A @ 60 degC (140 degF) linear derating
Current per Module, Max
8 A @ 30 degC (86 degF) linear derating; 4 A @ 60 degC (140 degF) linear derating
Surge Current per Point
8 A for 43 ms per point, repeatable every 2 s @ 30 degC (86 degF); 5 A for 43 ms per point, repeatable every 1 s @ 60 degC (140 degF)
Load Current, Min
10 mA per point
Inhibit Voltage, Max
Zero crossing 25V peak
Isolation Voltage
125V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group. No isolation between individual group inputs
Slot Width
1
Removable Terminal Block (RTB)
1756-TBNH, 1756-TBSH
Operating Temperature
0…60 degC (32…140 degF)
Nonoperating Temperature
-40…+85 degC (-40…+185 degF)
Relative Humidity
5…95% noncondensing
Vibration
2 g @ 10…500 Hz
Operating Shock
30 g
Nonoperating Shock
50 g
Enclosure Type
None (open style)
North American Temp Code
T4A
Installation Guidelines
Chassis Mounting: Install the module into any available slot in a 1756 ControlLogix chassis.
Terminal Block Compatibility: Use designated Removable Terminal Blocks (1756-TBNH or 1756-TBSH) for field wiring connections.
Wiring Specifications: Ensure field wiring uses single wire connections of 0.33…2.1 mm2 (22…14 AWG) or double wire connections of 0.33…1.3 mm2 (22…16 AWG) solid/stranded shielded copper wire rated at 105 degC or higher.
Conductor Category: Follow Wire Category 1 routing recommendations on signal ports according to industrial wiring and grounding guidelines.
System Derating: When operating in extended or harsh environment systems, ensure all paired chassis and power supply components match the required thermal specifications.
Compliance and Certifications
cULus: UL Listed Industrial Control Equipment, certified for US and Canada (UL File E65584); UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations (UL File E194810).
CE: European Union 2014/30/EU EMC Directive (EN 61326-1, EN 61000-6-2, EN 61000-6-4, EN 61131-2) and 2014/35/EU LVD Directive (EN 61131-2).
RCM: Australian Radiocommunications Act, compliant with EN 61000-6-4.
FM: FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations.
KC: Korean Registration of Broadcasting and Communications Equipment.
UKCA: Compliant with UK Statutory Instruments for EMC, Safety, Explosive Atmospheres, and RoHS.
Morocco: Compliant with ministerial order regulations for electrical safety and EMC.
FAQ
What diagnostic conditions can the output module detect?
The module can detect FuseBlown, NoLoad (in Off-state), OutputVerifyFault (in On-state), and FieldPwrLoss diagnostic conditions at the point level.
Does the module require external fuses for output protection?
No, the outputs are electronically fused per point to protect against short circuits and overload conditions.
Which Removable Terminal Blocks are compatible with this device?
This module is compatible with 1756-TBNH and 1756-TBSH Removable Terminal Blocks.
A practical replacement guide for the GE Fanuc IC693CPU313, covering its embedded five-slot architecture, memory backup, firmware-dependent capacity and why it cannot use Series 90-30 expansion racks.
A field-focused comparison of Bently Nevada 3500/40M and 3500/42M monitor inputs, channel-pair configuration, rear I/O options, external termination hardware and firmware checks before replacement.
A field checklist for diagnosing Allen-Bradley 1746-NR4 RTD and resistance inputs, including sensor curves, lead compensation, excitation current, filter timing and channel diagnostics.
A field-focused checklist for replacing an Allen-Bradley 1785-L40B or planning a PLC-5/40 migration, covering backups, 1771 I/O mapping, DH+/RIO channels, revision risks and commissioning.
Replacing an Allen-Bradley 1747-SN scanner? Check SLC 500 logical rack and G-file mapping, link speed, cable termination, COMM/FAULT LEDs and hardware series before blaming the module or changing the...