Description
The BECKHOFF CX5130-0150 is a high-performance Embedded PC designed for DIN rail mounting in medium-scale industrial automation applications. Driven by a dual-core Intel Atom E3827 processor running at 1.75 GHz, this fanless controller provides reliable processing power with low power consumption. It is equipped with 4 GB of non-expandable DDR3 RAM, a slot for a CFast storage card, and an independent microSD card slot, providing versatile storage options for system configuration and logging.
To ensure system stability in industrial environment power fluctuations, the BECKHOFF CX5130-0150 features an integrated 1-second UPS. This backup unit provides sufficient power to write up to 1 MB of persistent data safely onto the CFast card during an unexpected power interruption. The CPU module is compatible with multiple operating systems, including Windows Embedded Compact 7, Windows Embedded Standard 7 P, Windows 10 IoT Enterprise, and TwinCAT/BSD, and fully supports TwinCAT 2 or TwinCAT 3 (XAR) runtime environments.
A key capability of this controller is its integrated, automatic I/O recognition interface, allowing direct connection to either E-bus (EtherCAT) or K-bus (Bus Terminal) systems. This flexibility allows users to integrate various signal types and connection technologies directly onto a single controller head station, simplifying the engineering workflow and reducing control cabinet space requirements.
Features
- Dual-core Intel Atom E3827 processor (1.75 GHz clock frequency) for high-performance processing.
- 4 GB of integrated DDR3 RAM for high-speed application execution.
- Integrated 1-second UPS for secure saving of persistent data (up to 1 MB on CFast card).
- Automatic recognition and direct interface support for both K-bus (Bus Terminals) and E-bus (EtherCAT Terminals).
- Dual independent Gigabit Ethernet interfaces (RJ45, 10/100/1000 Mbit/s) for network segmentation or daisy-chaining.
- DVI-I visual interface and four high-speed USB 2.0 ports for peripheral and display integration.
- Fanless design with no moving parts for enhanced reliability and maintenance-free operation.
Applications
- Industrial machine control and decentralized processing stations.
- Control cabinet installations with high-density terminal setups.
- Material handling and conveyor synchronization using integrated EtherCAT execution.
- Utility and environmental control systems requiring persistent data backup on power loss.
Technical Specifications
| Parameter |
Specification |
| Manufacturer |
BECKHOFF |
| Model |
CX5130-0150 |
| Processor Type |
Intel Atom E3827 (Dual-Core, 1.75 GHz) |
| System Memory |
4 GB DDR3 RAM (not expandable) |
| Storage Slots |
1 x CFast slot, 1 x microSD slot (cards not included) |
| Persistent Memory |
Integrated 1-second UPS (up to 1 MB on CFast card) |
| TwinCAT 3 Platform Level |
Performance (40) |
| Control Software |
TwinCAT 2 runtime, TwinCAT 3 runtime (XAR) |
| I/O Connection Type |
Direct E-bus (EtherCAT) or K-bus (Bus Terminals) with auto-recognition |
| Supply Voltage |
24 V DC (-15% / +20%) |
| E-bus/K-bus Current Supply |
2 A maximum |
| Max. Power Consumption |
14 W (standard), 20 W (with UPS charging active) |
| Standard Interfaces |
2 x RJ45 (10/100/1000 Mbit/s), 1 x DVI-I, 4 x USB 2.0, 1 x optional interface slot |
| Protection Class |
IP20 |
| Operating Temperature |
-25 to +60 Celsius |
| Storage Temperature |
-40 to +85 Celsius |
| Relative Humidity |
95%, non-condensing |
| Dimensions (W x H x D) |
142 mm x 100 mm x 92 mm |
| Weight |
approx. 1095 g |
Connections / Interfaces
| Interface |
Function |
| LAN 1 / LAN 2 |
2 x RJ45 ports (10/100/1000 Mbit/s), independent controller ports |
| DVI-I |
Connection for DVI/VGA visualization monitor |
| USB |
4 x USB 2.0 connection points for keyboard, mouse, or flash drives |
| Optional Slot |
Interface slot for optional expansion (e.g. fieldbus master/slave, serial) |
| E-bus/K-bus Side |
Direct connection terminal plane for EtherCAT or standard I/O Bus Terminals |
| LED Diagnostics |
1 x power, 1 x TC status, 1 x flash access, 2 x bus status indicators |
Installation Guidelines
- Ensure the system is completely de-energized before mounting, wiring, or modifying the system configuration.
- Mount the unit on a standard 35 mm DIN rail (EN 60715) in a horizontal position to guarantee proper convection cooling.
- Ensure proper clearance distances are maintained above and below the device for ventilation.
- Connect a clean, nominal 24 V DC power source to the supply terminals, checking polarity carefully.
- Attach the required E-bus (EtherCAT) or K-bus terminals to the right-hand side of the CPU module, ensuring the terminal block guides lock securely into place.
- Insert a CFast storage card pre-loaded with an appropriate operating system and TwinCAT configuration prior to powering the unit.
Replacement Recommendations
When replacing an existing unit, make sure to back up or transfer the system's CFast card and any persistent data settings. Ensure that the replacement unit is ordered with matching options (such as optional interfaces or Ex approvals) to maintain exact software compatibility and electrical matching. Ensure the system is powered down fully before swapping storage media or terminal connections.
Compliance and Certifications
The unit complies with CE, UL, and DNV GL marine requirements in standard configuration. Hazardous area certifications, such as ATEX (Ex nA IIC T4 Gc / Ex tc IIIC T135 degC Dc), IECEx, or cFMus, are valid only when combined with the CX2900-0107 ordering option. Verify your unit's markings to ensure compatibility with your localized plant safety regulations.