1 of 1

BECKHOFF EL4001 EtherCAT Terminal 1-Channel Analog Output 0-10 V

BECKHOFF EL4001 EtherCAT Terminal 1-Channel Analog Output 0-10 V

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: EL4001

  • Country of origin:Germany

  • Product Type: EtherCAT Terminal

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 12 mm x 100 mm x 68 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Product Overview

The EL4001 (EL4001) is a precision 1-channel analog output terminal designed for the EtherCAT I/O system, providing a stable voltage signal from 0 to 10 V. Engineered for high-speed industrial applications such as proportional valve control, setpoint specification for frequency inverters, and climate control in cleanrooms, this module delivers 12-bit resolution for accurate actuator positioning. By utilizing EtherCAT Distributed Clocks (DC) technology, the EL4001 achieves ultra-precise synchronization with a jitter of less than 1 microsecond, making it indispensable for coordinated multi-axis systems and deterministic control loops. Its compact 12 mm form factor and short-circuit proof output ensure high reliability and space efficiency in dense control cabinets.

Technical Configuration

The EL4001 hardware utilizes a 2-wire single-ended connection technology, drawing power directly from the 24 VDC power contacts. The output stage is highly robust, supporting loads greater than 5 kOhm while maintaining an output error of less than 0.1 percent. A key feature of this terminal is the integrated watchdog function; in the event of a fieldbus communication failure, the output can be programmed to transition to a user-defined safety value or follow a specific ramp, protecting mechanical hardware from abrupt stops. The process image is represented by a 1 x 16-bit AO value, allowing for seamless integration within TwinCAT or any standard EtherCAT master.

Technical Specifications

Feature Specification
Model EL4001
Brand BECKHOFF
Origin Germany
Output Type 1-channel analog output, voltage 0-10 V
Resolution 12 bit
Conversion Time approx. 100 microseconds
Output Error < 0.1 percent (relative to end value)
Distributed Clocks Yes, precision << 1 microsecond
Power Supply 24 VDC via power contacts
Current Consumption (E-bus) typ. 140 mA
Electrical Isolation 500 V (E-bus/signal voltage)
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Operating Temperature -25 to +60 Celsius
Weight 0.06 kg

Technical FAQs

Does the EL4001 require external power for the output signal?

Yes, the terminal draws its 24 VDC power via the power contacts of the EtherCAT strand. Ensure that a power feed terminal (like the EK1100 or EL9100) is providing the necessary voltage to the power rail.

How does the 12-bit resolution map to the 16-bit process image?

The 12-bit digital value is left-aligned within the 16-bit integer (1 x 16 bit AO output) in the process image. This allows the system to remain compatible with standard 16-bit data types while providing 4096 distinct voltage steps between 0 and 10 V.

Is the output protected against wiring errors?

The EL4001 is short-circuit proof. If the load resistance drops below 5 kOhm or a direct short occurs, the terminal limits the current to prevent internal damage, although the output voltage will no longer accurately reflect the process value.


Engineering & Installation Guide

  • Signal Integrity and Grounding: To minimize voltage drop and electromagnetic interference, use shielded twisted-pair (STP) cables for the 0-10 V signal. The shield should be grounded at the control cabinet entry point. Since this is a single-ended output, ensure that the reference ground (0 V) is common between the EL4001 and the receiving device to avoid ground loops.

  • Watchdog Configuration: In the TwinCAT System Manager, navigate to the CoE (CanOpen over EtherCAT) parameters to configure the watchdog behavior. For critical valves, set a "Safe Value" that brings the process to a controlled state rather than simply allowing the voltage to drop to 0 V upon communication loss.

  • Load Compliance: Ensure the input impedance of the connected device is at least 5 kOhm. Connecting low-impedance loads will overload the output stage and may lead to non-linear signal behavior or thermal shutdown of the channel.

  • DC Synchronization: To leverage the sub-microsecond precision, the "Distributed Clocks" feature must be enabled in the EtherCAT Master settings. This is particularly vital when synchronizing the analog output with high-speed motion axes or oversampling input terminals.

 

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Greyish White
Country of origin
Germany

Recently Viewed Products

Technical knowledge

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...

Throwback: How Early Electric Motors Changed Underground Mining

From rope-driven DC compressors to battery-powered mine carts, early mining operations marked a turning point in industrial electrification. This article explores how electric motors transformed...

Factory I/O: A Modern PLC Simulation Tool for Industrial Automation Training

Factory I/O is transforming PLC education by delivering immersive 3D industrial simulations for students, engineers, and maintenance teams. The platform bridges the gap between theory and real-world...

Programming Single-Axis Motion Cycles on a CMZ Servo Drive

This tutorial examines how onboard PLC functionality inside a CMZ SBD servo drive can execute standalone motion programs, including homing logic, position control, and cyclic axis movement without an...