Description
The BECKHOFF ERI2809-0021 is an IP67-rated digital output module built in a heavy-duty zinc die-cast housing. Operating as an IO-Link device under the Class B specification, this module enables the connection of up to 16 digital outputs directly in the field, eliminating the need for protective control cabinets in demanding industrial environments.
This module processes output signals with a nominal voltage of 24 V DC and is designed to actuate ohmic, inductive, and lamp loads. Each output channel on the BECKHOFF ERI2809-0021 is individually protected against short circuits, preventing localized faults from disrupting the entire system. System data and control logic are transmitted via a high-speed IO-Link interface using COM 3 data transfer rates.
The zinc die-cast construction provides excellent mechanical resistance to impact, vibration, and moisture. Electrical isolation between the control logic power supply and the auxiliary load supply ensures stable operation and outstanding noise immunity during high-load switching operations.
Features
- 16 digital outputs with individual short-circuit protection
- IO-Link Class B communication interface supporting COM 3 (230.4 kbaud)
- Zinc die-cast housing offering IP65, IP66, and IP67 protection ratings
- Electrical isolation between L+ (control logic) and P24 (auxiliary/load supply)
- Diagnostic capabilities for detecting short-circuit and overload conditions
- Standard M8 screw-type connectors for secure field output wiring
Applications
- Decentralized control of actuators, solenoid valves, and indicator lamps
- On-machine installation in metalworking, assembly, and packaging plants
- Fieldbus systems requiring high mechanical protection and ingress prevention
- Decentralized I/O systems linked to IO-Link masters
Technical Specifications
General
| Manufacturer |
BECKHOFF |
| Model |
ERI2809-0021 |
| Product Type |
IO-Link Box Digital Output Module |
| Housing Material |
Zinc die-cast |
| Protection Class |
IP65, IP66, IP67 (conforms to EN 60529) |
Electrical
| Nominal Output Voltage |
24 V DC (-15% / +20%) |
| Max. Output Current |
0.5 A per channel (individually short-circuit proof, total sum max. 4 A) |
| Short-Circuit Current |
typ. 1.5 A |
| Current Consumption (L+) |
typ. 100 mA |
| Auxiliary Power Current |
typ. 20 mA + load |
| Electrical Isolation |
L+ / P24: Yes |
| Load Type |
Ohmic, inductive, lamp load |
IO-Link and Communication
| Interface Type |
IO-Link Class B |
| Specification Version |
IO-Link V1.1 |
| Data Transfer Rate |
230.4 kbaud (COM 3) |
| Connection Type |
1 x M12 plug, A-coded |
Mechanical and Environmental
| Dimensions (W x H x D) |
60 mm x 126 mm x 26.5 mm |
| Weight |
approx. 450 g |
Operating Temperature
-25 to +60 degC |
| Storage Temperature |
-40 to +85 degC |
| Vibration / Shock Resistance |
Conforms to EN 60068-2-6 / EN 60068-2-27 |
| EMC Immunity / Emission |
Conforms to EN 61000-6-2 / EN 61000-6-4 |
Connections / Interfaces
| Interface / Connection |
Function |
| M12 Plug (A-coded) |
IO-Link Class B interface and power supply (L+) |
| 16 x M8 Sockets |
Digital output channel connections (screw-type) |
Installation Guidelines
- Ensure the system power supply is completely de-energized before mounting or modifying the connections.
- Secure the zinc die-cast housing to a flat mounting surface using the integrated fixing holes (suitable for M3 or M4 screws).
- Connect the Class B IO-Link master line to the A-coded M12 plug interface. Use shielded cabling to prevent electromagnetic interference.
- Wire the 16 output devices to the designated M8 sockets. Tighten all connectors to the recommended torque to preserve the IP65/66/67 ratings.
- Perform control power checks on L+ and P24 prior to initial commissioning within your configuration software.