Description
Decentralized automation processes in harsh machine environments require robust, cabinet-free I/O interfaces. The IP2000-B318 Fieldbus Box serves as a reliable distributed interface, linking up to eight binary actuator control signals directly to a PROFIBUS network. Engineered with an IP67 rating, this module facilitates direct machine mounting, drastically reducing field wiring complexity and cabling costs.
Operating with a standard 24 V DC control voltage, the module distributes power and signal logic to eight independent digital outputs, each capable of delivering up to 0.5 A of load current. Standardized Ø8 mm snap-on connectors ensure fast, secure connection of field cables, while the integrated T-connector design facilitates straightforward loop-through of the PROFIBUS network lines directly on the module body.
Features
-
Direct Fieldbus Coupling: Native support for PROFIBUS DP protocol networks with integrated T-connector topology.
-
High-Density Outputs: 8 digital outputs rated at 24 V DC, 0.5 A per channel with integrated short-circuit protection.
-
Rugged Enclosure: Fully encapsulated IP67-rated housing designed for direct machine installation without protective enclosures.
-
Quick Installation: Standardized Ø8 mm snap-on connections minimize installation downtime and wiring errors.
-
Status Indicators: High-visibility LED diagnostic displays for network status and channel-specific logical output states.
Applications
- Automotive assembly lines and robotic cell integration
- Packaging, sorting, and material handling systems
- Pneumatic valve terminal control and decentralized actuator block management
- Conveyor systems and general machinery engineering
Technical Specifications
| Manufacturer |
Beckhoff Automation GmbH & Co. KG |
| Part Number / Model |
IP2000-B318 |
| Product Series |
Fieldbus Box (IPxxxx Series) |
| Fieldbus Interface |
PROFIBUS DP |
| Number of Outputs |
8 digital outputs |
| Nominal Output Voltage |
24 V DC (-15% / +20%) |
| Load Current per Channel |
0.5 A (short-circuit proof) |
| Signal Connection |
8 x Ø8 mm snap-on connectors |
| Bus Connection |
Integrated T-connector (PROFIBUS IN/OUT) |
| Protection Rating |
IP67 |
| Operating Temperature |
0 degC to +55 degC |
| Storage Temperature |
-25 degC to +85 degC |
| Approximate Weight |
2.0 kg (shipping weight weight-adjusted) |
Installation Guidelines
-
Mechanical Mounting: Fasten the unit securely to a flat surface using the integrated mounting holes. Ensure that no mechanical stresses are applied to the housing structure.
-
Functional Grounding: Establish a low-impedance connection between the module ground and the machine ground plane to ensure electromagnetic compatibility (EMC).
-
Cabling and Shielding: Utilize shielded PROFIBUS cables. Route fieldbus lines away from high-voltage cables or motor drive leads to prevent signal distortion.
-
Unused Interfaces: Seal any unused Ø8 mm signal sockets or PROFIBUS connectors with appropriate protective IP67 sealing caps to maintain the ingress protection rating.