Description
Processing analog input signals in the 0 to 10 V range, the BECKHOFF KL3062 Bus Terminal features two single-ended channels designed for direct connection to industrial sensors and transmitters. This compact input module converts analog physical values into digital signals with a 12-bit resolution, ensuring reliable signal transmission to the higher-level automation controller via the K-bus. Utilizing a common internal ground connection for both channels, the terminal minimizes wiring complexity in standard control cabinet installations.
The KL3062 provides comprehensive galvanic isolation up to 500 V between the input circuitry and the internal K-bus. Operating without the need for dedicated power contacts, the terminal derives its required operating power directly from the K-bus interface. The robust IP20 design and standard DIN rail mounting compatibility make it suitable for seamless integration in complex PLC and DCS architectures.
Features
- Two independent analog input channels.
- Single-ended measurement technology sharing a common reference ground.
- Standard 0 to 10 V signal voltage range.
- 12-bit analog-to-digital resolution.
- Integrated galvanic electrical isolation up to 500 V (K-bus to signal voltage).
- Fast conversion time of approximately 2 ms.
- Low power consumption directly from the K-bus (typically 60 mA).
- No address or hardware configuration required prior to commissioning.
Applications
- Industrial process control and monitoring systems.
- Pneumatic and hydraulic valve position feedback.
- Integration with pressure transmitters, flow meters, and distance sensors.
- Factory automation and machine building installations.
- Hazardous area applications requiring compliant ATEX/IECEx intrinsically safe parameters.
Technical Specifications
| Manufacturer |
BECKHOFF |
| Part Number / Model |
KL3062 |
| Number of Inputs |
2 |
| Power Supply |
Via the K-bus |
| Signal Voltage Range |
0 to 10 V |
| Technology |
Single-ended |
| Internal Resistance |
typ. > 200 kOhm |
| Conversion Time |
approx. 2 ms |
| Resolution |
12 bit |
| Measurement Error |
< +/-0.3% (relative to full scale value) |
| Electrical Isolation |
500 V (K-bus / signal voltage) |
| Current Consumption K-bus |
typ. 60 mA |
| Bit Width in Process Image |
Input: 2 x 16 bit data (2 x 8 bit control/status optional) |
| Configuration |
No address or configuration setting |
| Weight |
approx. 60 g |
| Operating Temperature |
0 to +55 degC |
| Storage Temperature |
-25 to +85 degC |
| Relative Humidity |
95 %, non-condensing |
| Vibration/Shock Resistance |
Conforms to EN 60068-2-6 / EN 60068-2-27 |
| EMC Immunity/Emission |
Conforms to EN 61000-6-2 / EN 61000-6-4 |
| Protection Rating |
IP20 |
| Installation Position |
Variable |
| Ex Marking |
ATEX: II 3 G Ex ec IIC T4 Gc, IECEx: Ex ec IIC T4 Gc |
Connections and Interfaces
| Terminal Point |
Function Assignment |
| 1 |
Analog Input 1 (+) |
| 5 |
Analog Input 2 (+) |
| 3 |
0 V (Reference ground for Input 1) |
| 7 |
0 V (Reference ground for Input 2) |
| 4 |
Shield connection |
| 8 |
Shield connection |
Installation Guidelines
-
Mounting: Snap the module directly onto a standard 35 mm DIN rail (EN 60715). Ensure the locking mechanism engages securely.
-
Wiring: Use appropriate wire sizes with terminal connectors. For solid or stranded wires, ensure the maximum cross-section conforms to the terminal blocks' limit.
-
Shielding: Connect the analog cable shields to terminal points 4 or 8 to prevent electrostatic and electromagnetic interference from disrupting signal integrity.
-
Grounding: Ensure the DIN rail is grounded to a low-impedance earth system in compliance with standard electrical installation codes.
Compliance and Certifications
- CE
- UL
- ATEX (II 3 G Ex ec IIC T4 Gc)