BECKHOFF

BECKHOFF KS6021 RS422/RS485 Serial Interface Bus Terminal

SKU KS6021

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: BECKHOFF

  • Product No.: KS6021

  • Country of origin:Germany

  • Product Type: Bus Terminals

  • Payment: T/T, Western Union

  • Weight: 60g

  • Dimensions: 12 mm x 100 mm x 68 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The BECKHOFF KS6021 is a high-performance Bus Terminal with a pluggable wiring level, designed to enable direct connection of devices with RS422 or RS485 interfaces to the K-bus system. It provides an electrically isolated, interference-immune interface for bidirectional data transfer over long distances, making it highly suitable for integrating serial communication devices into standard Beckhoff I/O networks.

Operating in full or half-duplex mode, the BECKHOFF KS6021 transmits and receives differential signals using a dedicated TxD and RxD channel architecture. The serial interface operates independently of the underlying bus system, allowing the controller to transmit data collision-free and receive data with an integrated buffer system. This model features a pluggable wiring design (indicated by the KS prefix), which simplifies terminal installation, replacement, and wiring verification without disconnecting individual field conductors.

Features

  • Pluggable connection level for fast, tool-free terminal replacement and streamlined wiring.
  • Supports RS422 and RS485 serial communication standards for high noise immunity.
  • Full or half-duplex data transfer modes over twisted-pair cabling.
  • Integrated data buffering with a 128-byte receive buffer and a 16-byte transmit buffer.
  • Electrical isolation of 500 V between the internal K-bus and the field signal lines.
  • No manual address setting required; configuration is handled via the Bus Coupler or controller.
  • Clear diagnostics and operation status via K-bus communication.

Applications

  • Integration of serial devices such as barcode scanners, operator terminals, and printers into K-bus I/O systems.
  • Connecting to sensors, controllers, and industrial instruments utilizing RS422 or RS485 physical layer interfaces.
  • Long-distance serial communications up to 1000 meters in noisy industrial environments.

Technical Specifications

General

Manufacturer BECKHOFF
Model KS6021
Product Type Bus Terminal with pluggable wiring level
Communication Interface RS422/RS485
Data Channels TxD and RxD, full or half-duplex

Electrical and Communication

Data Transfer Rates 1200 to 19,200 baud (Default: 9600 baud, 8 data bits, no parity, 1 stop bit)
Bit Transfer Type Differential signal
Line Impedance 120 ohms
Maximum Cable Length Approximately 1000 m (twisted pair)
Data Buffers 128 bytes (receive), 16 bytes (transmit)
Power Supply Via the K-bus
K-bus Current Consumption Typical 65 mA
Power Contacts None (no power contacts)
Electrical Isolation 500 V (K-bus / signal voltage)
Process Image Bit Width Input/output: 3 x 8-bit user data, 1 x 8-bit control/status (up to 5 x 8-bit user data possible)

Mechanical and Environmental

Wiring Technology Pluggable wiring (tension clamp connection)
Connection Cross-section Solid conductor: 0.08 to 1.5 mm²; Flexible: 0.08 to 1.5 mm²; Ferrule: 0.14 to 1.5 mm²
Connection Cross-section AWG AWG 28 to 16 (solid/stranded); AWG 26 to 16 (ferrule)
Stripping Length 9 to 10 mm
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Weight Approx. 60 g
Mounting 35 mm DIN rail (EN 60715) with locking mechanism
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Relative Humidity 95 %, non-condensing
Protection Class IP20

Compliance and Approvals

Certifications CE, UL, ATEX
Ex Marking II 3 G Ex nA IIC T4 Gc

Installation Guidelines

  1. De-energize the System: Ensure the power supply to the entire K-bus network and Bus Coupler is fully switched off before starting terminal installation.
  2. Mount the Terminal: Align the terminal on the 35 mm DIN rail and press down until it securely locks into place, ensuring robust contact with the adjacent terminal using the side tongue-and-groove system.
  3. Wire Connection: Actuate the tension clamp contact using a screwdriver, insert the stripped conductor (or ferrule), and release the clamp. Since this is a KS-series terminal, the complete wiring level block can be plugged or unplugged from the housing as a unit.
  4. Connect Shielding: Properly ground and shield the RS422/RS485 communication line to prevent electromagnetic interference and maintain signal integrity.
  5. Power and Verify: Apply power to the K-bus. Verify that the diagnostics indicate correct K-bus communication and data activity.

Replacement Recommendations

The BECKHOFF KS6021 features a pluggable wiring design that simplifies replacement tasks. When replacing an existing terminal, the wired pluggable block can be removed from the terminal housing without disconnecting the individual signal wires. Ensure the system is powered down, disconnect the plug block, swap the terminal housing on the DIN rail, and securely snap the plug block back into the new unit to minimize downtime and prevent wiring errors.

FAQ

What is the main difference between the BECKHOFF KS6021 and the KL6021?

The BECKHOFF KS6021 features a pluggable wiring level, allowing the entire block of connection terminals to be plugged or unplugged as a single unit, whereas the KL6021 has a fixed terminal level. Both terminals share identical RS422/RS485 communication specifications and K-bus compatibility.

What transmission protocols and baud rates does the BECKHOFF KS6021 support?

The BECKHOFF KS6021 operates with RS422 and RS485 standards, supporting data transfer rates from 1200 to 19,200 baud, with a default configuration of 9600 baud, 8 data bits, no parity, and 1 stop bit.

Does the BECKHOFF KS6021 require power contacts on the adjacent terminals?

No, the BECKHOFF KS6021 does not use power contacts for field-side supply and is powered entirely via the internal K-bus, consuming a typical current of 65 mA.

What are the integrated buffer capacities of the BECKHOFF KS6021 serial interface?

The BECKHOFF KS6021 is equipped with an integrated 128-byte receive buffer and a 16-byte transmit buffer to handle serial data communication without data loss.

Is electrical isolation provided on the BECKHOFF KS6021?

Yes, the BECKHOFF KS6021 provides electrical isolation of 500 V between the internal K-bus and the RS422/RS485 field-side signals to ensure high noise immunity.

View all FAQs →

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Technical knowledge

Replacing a Beckhoff EL4032: Wiring and Output Checks

A field checklist for replacing a Beckhoff EL4032, covering the ±10 V load, terminal map, power contacts, EtherCAT state, and watchdog behavior.

Replacing Yokogawa AAI835: Wiring and Barrier Checks Before Swap

Before replacing a Yokogawa AAI835, verify the 4-in/4-out channel map, power-loss loop behavior, barrier type, output load, cable, and redundancy.

ABB PM891K01 Replacement: Check Redundancy Before Ordering

ABB PM891K01 article 3BSE053241R1 is the non-redundant AC 800M processor kit. Use this field checklist before replacement.

ABB TP853 Replacement Checks for CI853/CI855/CI857/CI861

Replacement checks for ABB TP853 3BSE018126R1: identify the installed CI853, CI855, CI857, or CI861 interface, record wiring, and verify communication after installation.

5069-L330ERMS2 Startup Checks: RTBs, I/O, and Motion Limits

Engineering checks for the Allen-Bradley 5069-L330ERMS2: controller capacity, separate RTB kits, local I/O limits, network-node limits, and motion-axis count.

Replacing ABB DSQC 351: Controller and Network Checks

Checks to record before replacing ABB 3HNE 00006-1 DSQC 351: controller generation, X3/X5/X20/X21 wiring, DeviceNet settings, INTERBUS mapping, and LED states.