Description
Designed for integration into the 3500 Machinery Protection System, the 163179-03 is a specialized input/output module that interfaces directly with the 3500/62 Process Monitor. This specific module variant is engineered with internal safety barriers and internal terminations, allowing direct connection to field sensors and transmitters located in hazardous environments without requiring auxiliary external barriers.
The 163179-03 functions by receiving industrial analog signals—such as 4 to 20 mA DC or proportional voltage inputs—and routing them to the main 3500/62 monitor module for digitizing, processing, and alarm setpoint comparison. This setup enables continuous surveillance of key process variables including pressure, temperature, level, flow, and gas concentrations within critical rotating machinery and plant systems.
Features
- Direct compatibility with the Bently Nevada 3500/62 Process Monitor main board.
- Integrated internal safety barriers eliminate the need for external explosion-protection hardware.
- Internal termination blocks support secure, permanent field wiring connections.
- Accepts 6 independent channels of process variable transmitter inputs.
- Robust construction engineered for high-reliability industrial automation environments.
- Fully configurable through standard 3500 rack configuration software.
Applications
- Machinery protection and condition monitoring in petrochemical and oil & gas refining.
- Steam, gas, and hydro turbine process variable oversight in power generation facilities.
- Industrial wastewater treatment plant processing monitoring.
- Continuous monitoring of pressure, flow, and level in chemical manufacturing processes.
Technical Specifications
| Manufacturer |
Bently Nevada |
| Part Number / Model |
163179-03 |
| Series Name |
3500 Series Machinery Protection System |
| Compatible Monitor Module |
3500/62 Process Monitor |
| Termination Type |
Internal Terminations |
| Barrier Configuration |
Internal Safety Barriers (Intrinsically Safe) |
| Number of Channels |
6 differential or single-ended channels |
| Input Signal Formats |
4 to 20 mA DC, +1 to +5 VDC (proportional) |
| Operating Temperature |
-30 degC to +65 degC |
| Storage Temperature |
-40 degC to +85 degC |
| Relative Humidity |
95% non-condensing |
| Country of Origin |
United States |
Connections and Interfaces
| Terminal Connection Group |
Function Description |
| Channels 1 through 6 |
Process transmitter input terminals (Signal, Common, Shield) |
| Internal Barrier Ground |
Dedicated connection for intrinsic safety ground reference |
Installation Guidelines
- Power down the 3500 rack before installing or removing the 163179-03 I/O module to prevent system faults or hardware damage.
- Insert the module into the designated slot on the rear panel of the rack, directly behind the corresponding 3500/62 monitor card.
- Ensure that the chassis ground connection and the internal safety barrier ground are connected to a high-integrity, low-impedance earth ground.
- Follow specified torque guidelines for the terminal screws to prevent loose field wiring connections under vibration conditions.
Compliance and Certifications
- CE Compliant
- UL/CSA Class I, Division 2 / Division 1 (when installed with appropriate barriers)
- ATEX / IECEx Intrinsically Safe for Zone 0/Zone 1 environments