Bently Nevada

Bently Nevada 3300/16-02-01-01-01-00-00 XY/GAP Dual Vibration Monitor

SKU 3300/16-02-01-01-01-00-00

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Bently Nevada

  • Product No.: 3300/16-02-01-01-01-00-00

  • Country of origin:United States

  • Product Type: XY/GAP Dual Vibration Monitor

  • Payment: T/T, Western Union

  • Weight: 1000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The Bently Nevada 3300/16-02-01-01-01-00-00 is an XY/GAP Dual Vibration Monitor designed for two-channel radial vibration and shaft position monitoring in Bently Nevada 3300 systems.

The monitor accepts two proximity probe and Proximitor Sensor inputs. This configuration uses a 0 to 5 mil peak-to-peak vibration range and is designed for 3300 8 mm, 3300 XL 8 mm, or 7200 5 mm and 8 mm Proximitor Sensors with a 200 mV/mil scale factor.

The unit provides independent vibration measurement for Channel A and Channel B. Probe gap is also monitored to indicate average shaft position relative to the proximity probes.

This configuration includes an epoxy-sealed alarm relay, CSA/NRTL/C agency approval, no safety barriers, and no Trip Multiply option.

Features

  • Two independent radial vibration channels

  • Average shaft position and probe gap monitoring

  • 0 to 5 mil peak-to-peak full-scale vibration range

  • 200 mV/mil transducer sensitivity

  • Compatible with 3300 8 mm Proximitor Sensors

  • Compatible with 3300 XL 8 mm Proximitor Sensors

  • Compatible with 7200 5 mm and 8 mm Proximitor Sensors

  • Independent Alert and Danger alarm functions

  • Gap Alert capability for both channels

  • Epoxy-sealed alarm relay configuration

  • Individual recorder outputs for both channels

  • Front and rear buffered transducer outputs

  • CSA/NRTL/C approval configuration

  • No safety barrier option

  • No Trip Multiply option

Applications

  • Radial shaft vibration monitoring

  • Shaft position and probe gap monitoring

  • Rotating machinery protection

  • Dual-channel proximity probe monitoring

  • Machinery condition monitoring using 3300 proximity systems

  • Replacement of matching 3300/16 XY/GAP monitor configurations

Ordering Information

Option Configuration
Model 3300/16 XY/GAP Dual Vibration Monitor
A: Full-scale Range 02 - 0 to 5 mils peak-to-peak
B: Transducer Input 01 - 3300 8 mm, 3300 XL 8 mm, or 7200 5 mm and 8 mm Proximitor Sensor
Transducer Sensitivity 200 mV/mil
C: Alarm Relay 01 - Epoxy-sealed
D: Agency Approval 01 - CSA/NRTL/C
E: Safety Barrier 00 - None
F: Trip Multiply 00 - None

Technical Specifications

Parameter Specification
Manufacturer Bently Nevada
Model 3300/16-02-01-01-01-00-00
Product Type XY/GAP Dual Vibration Monitor
System 3300
Number of Channels 2
Measurement Functions Radial vibration and average shaft position
Signal Inputs One or two proximity probe signals
Input Impedance 10 kohm
Sensitivity 200 mV/mil
Full-scale Range 0 to 5 mil peak-to-peak
Power Consumption 2 W nominal
Alarm Relay Epoxy-sealed
Agency Approval CSA/NRTL/C
Safety Barrier None
Trip Multiply None
Rack Space 1 rack position
Weight 1 kg (2.2 lb)

Performance

Parameter Specification
Accuracy at +25 degC +/-0.33% of full-scale typical
Maximum Accuracy Error +/-1%
Frequency Response Option 4 to 4,000 Hz or 1 to 600 Hz
Alarm Setpoint Range 0 to 100% of full-scale
Alarm Repeatability Within +/-0.39% of full-scale
Gap Alarm Delay 6 seconds

Recorder Outputs

Parameter Specification
Available Output 1 +4 to +20 mA
Available Output 2 0 to -10 Vdc
Available Output 3 +1 to +5 Vdc
Outputs per Channel 1 individual recorder output
Voltage Output Impedance 100 ohm
Minimum Load Resistance 10 kohm
4-20 mA Load Resistance 0 to 600 ohm

Buffered Outputs

Parameter Specification
Front Output One coaxial connector per channel
Rear Output One terminal connection per channel
Protection Short-circuit protected
Output Impedance 100 ohm

Environmental

Parameter Specification
Operating Temperature 0 to +65 degC
Storage Temperature -40 to +85 degC
Relative Humidity Up to 95%, non-condensing

Installation & Commissioning

  • Verify the complete catalog number before replacing the installed monitor.

  • Confirm the existing proximity system uses a 200 mV/mil transducer configuration.

  • Verify compatibility with the installed 3300 8 mm, 3300 XL 8 mm, or 7200 5 mm and 8 mm system.

  • Record existing Alert, Danger, gap, recorder-output, and bypass settings before removal.

  • Confirm the rack alarm state before removing or installing the monitor.

  • Verify Channel A and Channel B probe signals after installation.

  • Check vibration, gap, Alert, Danger, and recorder outputs before returning the rack to service.

Replacement Notes

  • Match the complete 3300/16-02-01-01-01-00-00 configuration when sourcing a replacement.

  • Do not substitute another 3300/16 solely because the front panel appears identical.

  • Full-scale range, transducer input, relay option, agency approval, safety barrier, and Trip Multiply options must be checked.

FAQ

What does the Bently Nevada 3300/16-02-01-01-01-00-00 monitor?

The Bently Nevada 3300/16-02-01-01-01-00-00 continuously monitors two independent radial vibration channels and average shaft position using proximity probe and Proximitor Sensor systems.

What vibration range does the 3300/16-02-01-01-01-00-00 use?

The Bently Nevada 3300/16-02-01-01-01-00-00 uses full-scale range option 02, corresponding to 0 to 5 mils peak-to-peak.

Which Proximitor Sensors are compatible with this 3300/16 configuration?

The Bently Nevada 3300/16-02-01-01-01-00-00 uses 200 mV/mil inputs for 3300 8 mm, 3300 XL 8 mm, and 7200 5 mm or 8 mm Proximitor Sensors.

Does the 3300/16-02-01-01-01-00-00 include alarm relays?

The Bently Nevada 3300/16-02-01-01-01-00-00 includes option C01, which identifies the epoxy-sealed alarm relay configuration.

Does this 3300/16 monitor use safety barriers?

The Bently Nevada 3300/16-02-01-01-01-00-00 uses safety barrier option E00, meaning no external or internal safety barrier is included in this configuration.

What should be checked before replacing this Bently Nevada 3300/16?

The Bently Nevada 3300/16-02-01-01-01-00-00 replacement should match the vibration range, transducer type, relay configuration, approval option, safety barrier option, and Trip Multiply configuration.

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Bently Nevada 3300/16-02-01-01-01-00-00 XY/GAP Dual Vibration Monitor

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 3
Only 5 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Technical knowledge

1746-OA8 vs 1746-OA16: Output Count and Current Limits

A direct comparison of 1746-OA8 and 1746-OA16 output count, common grouping, backplane current and temperature-derated load limits.

Replacing a 1761-NET-DNI: Capture These Settings First

A field checklist for recording the 1761-NET-DNI hardware series, firmware, EDS file, DF1 settings, DeviceNet address and messaging configuration before replacement.

EL3062 vs EL3062-0030: The Input Range Changes

The EL3062 is a 0–10 V EtherCAT terminal. The EL3062-0030 is a 0–30 V variant. This checklist covers identification, scaling and commissioning.

Replacing a 1769-OW8: Checks Before Moving Relay Loads

A field checklist for replacing Allen-Bradley 1769-OW8 relay output modules without losing load-group, wiring, and commissioning details.

PLC I/O Modules: Wiring, Load, and Isolation Checks

A field checklist for matching PLC digital and analog I/O to sensors, loads, commons, isolation groups, filters, and replacement settings.

Magnetic Flowmeters: Commissioning and Diagnostics

A field-focused checklist for selecting, installing, commissioning, and diagnosing magnetic flowmeters, with emphasis on conductivity, full-pipe conditions, grounding, wiring, zero checks, and PLC...