Bently Nevada 330780-90-05 3300 XL 11 mm Proximitor Sensor
SKU 330780-90-05
In stock
No reviews
12-month warranty
Free returns within 30 days
Manufacturer:
Bently Nevada
Product No.:
330780-90-05
Country of origin:United States
Product Type:
3300 XL 8mm Proximity Sensor
Barcode:
8537101190
Payment:
T/T, Western Union
Weight:
220g
Dimensions:
8cm x 6cm x 6.5cm
Shipping port:
Xiamen
Warranty:
12 months
Description
The Bently Nevada 330780-90-05 is an advanced eddy current measurement device within the 3300 XL 11 mm Proximitor Sensor series, designed to process signals from a proximity probe and extension cable combination. It delivers a continuous, linear voltage output directly proportional to the static distance (gap) or dynamic vibration between the probe tip and the observed target. This sensor is explicitly engineered for high-performance fluid-film bearing machinery monitoring and vibration analysis within critical machinery protection systems, including the Bently Nevada 3500 System.
The hardware offers reliable input-output capabilities by converting target movement into standard industrial electrical signals, allowing direct interfacing with machinery protection monitors, distributed control systems (DCS), and plant asset management networks. This module features robust physical protection and EMI/RFI immunity, enabling deployment across severe industrial applications such as oil and gas processing, petrochemical production, power generation facilities, and mining installations.
Features
Linearized Voltage Output: Delivers exceptional accuracy and repeatable calibration for vibration, gap, and speed measurements.
System Compatibility: Fully compatible with standard 3300 XL 11 mm proximity probes and extension cables, integrating with monitoring architectures.
Enhanced RFI/EMI Immunity: Provides robust resistance against electromagnetic interference without requiring specialized external conduit housing.
DIN Rail Mounting Option: Features a flexible physical design supporting convenient standard DIN rail mounting or traditional panel installation.
Integral Coaxial Connector Protectors: Prevents moisture ingress and external contamination, maintaining signal integrity at the physical interface.
Applications
Steam and gas turbines
Centrifugal and axial compressors
Industrial pumps and electric motors
Hydroelectric generators
Cooling tower fans and gearboxes
Technical Specifications
Parameter
Specification
Manufacturer
Bently Nevada
Model
330780-90-05
Series
3300 XL 11 mm
Sensor Type
Proximitor Sensor
System Length
9.0 metres (29.5 feet)
Mounting Option
Panel Mount
Agency Approval Option
Multiple Approvals (ATEX, IECEx, CSA, TR CU)
Output Scale Factor
3.94 V/mm (100 mV/mil) nominal
Operating Temperature
-51 degC to +100 degC
Storage Temperature
-51 degC to +100 degC
Power Requirements
-17.5 Vdc to -26 Vdc
Relative Humidity
100% condensing, non-submerged
Connections/Interfaces
Connector Pin
Function
VT / -24 Vdc
Power Supply Input (-17.5 Vdc to -26 Vdc)
OUT / SIG
Linear Voltage Output Signal
COM / GND
Common / Ground Reference
PROBE
Coaxial Interface to Extension Cable / Probe
Installation Guidelines
Grounding and Shielding
Ensure the sensor housing is insulated from the underlying structure or connected to the designated system ground to eliminate potential ground loop interference.
Maintain the continuous shield from the probe connection back to the monitor panel, grounding the shield only at the monitor common point.
Probe Gap Adjustment
Adjust the initial physical gap between the target material and the probe tip until the output voltage reads approximately -10.0 Vdc, corresponding to the midpoint of the linear operating range.
Cable Routing and Physical Protection
Route all interconnecting coaxial cables away from high-voltage machinery lines or structural paths prone to extreme mechanical vibration.
Install physical connector protectors over the coaxial junctions to maintain proper signal protection against fluids, grease, and ambient moisture.
Compliance and Certifications
ATEX / IECEx Zone 0, Zone 2
CSA Class I, Division 1 and 2
TR CU (EAC) Hazardous Area Approvals
FAQ
What is the primary function of the device?
The device processes input from an 11 mm proximity probe and extension cable to deliver a linear voltage output proportional to target distance, enabling vibration and position monitoring.
What are the power requirements for this sensor?
The sensor operates on a nominal supply voltage ranging from -17.5 Vdc to -26 Vdc.
What is the operating temperature range for the device?
The device is specified to operate reliably in ambient temperatures ranging from -51 degC to +100 degC.
How should the sensor shield be connected during installation?
The shield should maintain continuity throughout the cable run and be grounded exclusively at the monitor instrument side to avoid ground loop current.
A field replacement guide for GE Fanuc IC200MDL650 covering revision-dependent negative logic, four common groups, 24 VDC thresholds, input filtering, carrier checks and commissioning records.