1 of 1

Bently Nevada 3500/25-01-03-CN 3500/25 Enhanced Keyphasor Module

Bently Nevada 3500/25-01-03-CN 3500/25 Enhanced Keyphasor Module

Only 7 item(s) left in stock
  • Manufacturer: Bently Nevada

  • Product No.: 3500/25-01-03-CN

  • Country of origin:United States

  • Product Type: Enhanced Keyphasor Modules

  • Payment: T/T, Western Union

  • Weight: 340g

  • Dimensions: 241.3 mm x 24.4 mm x 103.1 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

The 3500/25-01-03-CN is a high-performance, half-height, two-channel machinery protection component designed to deliver phase reference and speed measurements within the Bently Nevada 3500 Series Machinery Protection System rack framework. This module processes incoming electrical signals from proximity probe transducers or passive magnetic pickups to establish a highly precise, digital once-per-turn or multiple-event-per-turn timing pulse. These generated phase reference pulses (Keyphasor signals) are transmitted directly via the 3500 system backplane to other monitoring modules and interconnected diagnostic software. This real-time processing enables the machinery protection system to compute shaft rotative speed, track synchronous vector tracking variables, and map specific vibration amplitudes alongside physical phase angles across fluid-filmed bearing assets.

The operational setup of the 3500/25 module incorporates a single half-height two-channel Keyphasor card variant mapped alongside an internal barrier I/O module type featuring dedicated internal compression screw terminations. The integrated internal safety barriers provide certified intrinsically safe connections for transducers running straight into hazardous deployment spaces. This configuration is designed to comply with strict international regulatory expectations while providing downward functional compatibility with older 3500 module versions, effectively replacing preceding components such as the PWA 125792-01 assembly.

Features

  • Dual-channel speed and phase monitoring design providing once-per-turn and multi-event pulse conditioning.
  • Integrated intrinsically safe internal barriers supporting direct connection to hazardous location transducers.
  • Provides real-time phase reference mapping, 1X vibration amplitude vectors, and comprehensive speed diagnostics across the system rack backplane.
  • Advanced capabilities including generation of once-per-turn timing pulses from high-density multi-event gear targets.
  • Coaxial buffered front-panel interfaces and rear Euro-style connections providing clean raw transducer waveform telemetry.
  • Built-in system health validation via dedicated front plate OK and communication status (TX/RX) LED arrays.

Applications

  • Real-time phase reference logging and vector vibration tracking on utility steam and gas power turbines.
  • Multi-channel shaft speed monitoring, overspeed trip integration, and zero-speed indexing across critical centrifugal air compressors.
  • Structural phase matching and multi-plane field balancing on high-speed industrial process fans and fluid-filmed bearing gearboxes.

Ordering Information

Part Number Option Breakdown and System Descriptions
3500/25-AA-BB-CC 3500/25 Enhanced Keyphasor Module Assembly 
A: 01 Single half-height 2-channel Keyphasor card (order for 2-channels) 
B: 03 Internal Barrier I/O with Internal Terminations 
C: 03-CN Agency Approval Option with specific localized compliance configurations 

Technical Specifications

Parameter Classification Precise Engineering Values
Manufacturer Bently Nevada (Baker Hughes) 
Main Part Number 3500/25-01-03-CN
Module Type Variant Enhanced Keyphasor Module with Internal Safety Barriers 
Typical Power Consumption 3.2 Watts typical 
Non-Isolated Input Signal Range +0.8 V to -21.0 V 
Isolated Input Signal Range +5.0 V to -11.0 V 
Minimum Transducer Impedance 21.8 kOhm minimum 
Input Speed/Frequency Range 1 to 1,200,000 cpm (0.017 to 20 kHz) 
Output Speed/Frequency Range 1 to 99,999 cpm (0.017 to 1667 Hz) 
Non-Processed Signal Accuracy 0.017 to 100 Hz: +/- 1 cpm; 101 to 500 Hz: +/- 8 cpm; 501 Hz to 20 kHz: +/- 1% of cpm 
Processed Signal Accuracy 0.017 to 60 Hz: +/- 1 cpm; 61 to 150 Hz: +/- 8 cpm; 151 Hz to 20 kHz: +/- 1% of cpm 
Auto-Threshold Pulse Requirements Minimum 2 Volts peak-to-peak amplitude; Minimum frequency of 120 rpm (2 Hz) 
Manual-Threshold Range User-selectable from 0 to -20 Vdc; Minimum 500 millivolts peak-to-peak triggering amplitude 
User-Selectable Hysteresis 0.2 to 2.5 Volts 
Maximum Output Impedance 504 Ohm maximum buffered output impedance 
Transducer Transmit Power Limit -24 Vdc, 40 mA maximum per channel 
Operating Temperature (Barrier I/O) 0 degC to +65 degC (32°F to +150°F) 
Storage Temperature Limits -40 degC to +85 degC (-40°F to +185°F) 
Maximum Relative Humidity 95%, non-condensing 
Main Module Dimensions (H x W x D) 119.9 mm x 24.4 mm x 256.5 mm (4.72 in x 0.96 in x 10.10 in) 
Main Module Net Weight 0.34 kg (0.76 lbs) 
I/O Module Dimensions (H x W x D) 241.3 mm x 24.4 mm x 103.1 mm (9.50 in x 0.96 in x 4.06 in) 
I/O Module Net Weight 0.46 kg (1.01 lbs) 
Chassis Space Allocation (Main) 1 half-height front monitor rack slot 
Chassis Space Allocation (I/O) 1 full-height rear interface rack slot 

Connections/Interfaces

Connector Pin Layout Function Assignment and Loop Configuration
Front Panel Coaxial Port 1 Channel 1 buffered transducer phase/speed voltage raw waveform output 
Front Panel Coaxial Port 2 Channel 2 buffered transducer phase/speed voltage raw waveform output 
Rear Euro Terminal Blocks Independent lines for intrinsically safe probe power, shield grounds, and return path tracking signals 

Installation Guidelines

  • Rack Alignment Rules: Slide the main half-height processing card into any of the 14 available front monitor slots of the 3500 chassis using the dedicated half-height card guide adapter. Mount the corresponding full-height barrier I/O module into the rear slot directly opposing the main card assembly.
  • Safety Intrinsic Wiring: Ensure all external field conductors entering the internal barrier I/O terminal block are installed strictly in accordance with factory document drawing 138547. Route intrinsically safe probe cables through separate, isolated wire trays away from all non-intrinsically safe power or machinery supply feeds.
  • Electrostatic Control Procedures: A single-use conductive electrostatic grounding wrist strap must be worn and correctly terminated to the machinery rack structure when slotting the cards or moving local components to avoid irreversible circuit degradation.
  • Chassis Monitoring Limits: Each single protection rack can support a maximum of two main Keyphasor processing modules, with one module allocated to the top half-slot line and the second located in the bottom half-slot line.

Compliance and Certifications

  • EMC Directives: European Community Directive 2014/30/EU compliant via EN 61000-6-2 (Industrial Immunity) and EN 61000-6-4 (Industrial Emissions) verification.
  • Electrical Safety Rules: European Community Directive 2014/35/EU compliant under standard EN 61010-1 parameters.
  • Maritime Standards: Certified under DNV GL rules for maritime vessels/offshore installations alongside American Bureau of Shipping (ABS) Steel Vessels Rules Part 1 guidelines.
  • RoHS Directive: Fully compliant under European Community RoHS Directive 2011/65/EU and China RoHS regulations maintaining a 15-year environment-friendly use period (EFUP).
  • Hazardous Approvals: Class I, Zone 2 AEx/Ex nA nC ic [ia Ga] IIC T4 Gc and Class I, Division 2, Groups A, B, C, and D boundaries when used with internal safety barrier interfaces.
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Bently Nevada 3500/25-01-03-CN 3500/25 Enhanced Keyphasor Module

What is the minimum rotation speed required when deploying passive magnetic pickups with this card?

Passive magnetic pickups require a minimum shaft rotative speed greater than 200 rpm (3.3 Hz) to provide a valid signal profile.

How many Keyphasor cards can be safely operating inside a single 3500 protection rack?

Each 3500 system rack can contain a maximum of two main Keyphasor modules, with one positioned in a top half-slot and one in a bottom half-slot.

What is the key difference between the Auto Threshold and Manual Threshold tracking configurations?

Auto Threshold requires a minimum signal amplitude of 2 Volts peak-to-peak and a frequency above 2 Hz, whereas Manual Threshold allows manual entry from 0 to -20 Vdc with triggering down to 500 millivolts peak-to-peak.

Does the internal barrier I/O modification change the normal operational temperature scope?

Yes. When used with the internal barrier I/O module version, the operating temperature specification is restricted to a range of 0 degC to +65 degC instead of the non-barrier limit.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Recently Viewed Products

Technical knowledge

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...

Throwback: How Early Electric Motors Changed Underground Mining

From rope-driven DC compressors to battery-powered mine carts, early mining operations marked a turning point in industrial electrification. This article explores how electric motors transformed...

Factory I/O: A Modern PLC Simulation Tool for Industrial Automation Training

Factory I/O is transforming PLC education by delivering immersive 3D industrial simulations for students, engineers, and maintenance teams. The platform bridges the gap between theory and real-world...