Product Overview
The EPI2338-0002 (EPI23380002) is an ultra-versatile IO-Link device that provides 8 digital channels, each of which can be independently configured as either an input or an output. Operating as an IO-Link V1.1 Class B device, it is designed for decentralized, cabinet-free installation in demanding industrial environments. The Class B interface is a critical distinction, as it provides an additional, electrically isolated power supply specifically for high-current loads and outputs. This makes the EPI2338-0002 an ideal B2B solution for modular machine building, robotic tooling, and automated production lines where high I/O density and flexible signal direction are required in an IP67-rated footprint.
Hardware Architecture and Class B Integration
The EPI2338-0002 architecture is defined by its "One-Port-Multi-Signal" capability. Each of the 8 channels, accessed via M12 screw-type connectors, can sink or source signals based on the PLC configuration. The module utilizes the high-speed COM3 (230.4 kbaud) data rate to ensure that the process data for all 16 signals (8 inputs + 8 outputs/diagnostics) is updated with minimal latency.
A key technical feature is the IO-Link Class B interface (M12 A-coded). Unlike Class A, which only provides system power, Class B provides a second, isolated power supply ($P24$). This $P24$ supply powers the digital outputs and the sensor supply, ensuring that an electrical fault or short circuit on the output side does not interrupt the IO-Link communication logic ($L+$). Each output can deliver up to 0.5 A, and the module features an adjustable input filter (0 to 20 ms) to accommodate various field sensor types.
Technical Specifications
| Attribute |
Specification Details |
| Model |
EPI2338-0002 |
| Brand |
BECKHOFF |
| Protocol |
IO-Link V1.1 (Class B) |
| Data Rate |
230.4 kbaud (COM 3) |
| Channel Count |
8 (Individually configurable as In/Out) |
| Interface |
1 x M12 plug (A-coded) |
| I/O Connection |
M12, screw type |
| Max Output Current |
0.5 A per channel |
| Input Filter |
3.0 ms (Default), adjustable 0–20 ms |
| Electrical Isolation |
Yes (L+ system / P24 peripheral) |
| Operating Temp |
-25 to +60 Celsius |
| Protection Rating |
IP65 / IP66 / IP67 |
| Dimensions (W x H x D) |
30 mm x 126 mm x 26.5 mm |
Technical FAQs
What is the advantage of a Class B IO-Link port for this module?
The Class B port provides an additional set of pins for auxiliary power ($U_2$ or $P24$). This allows the digital outputs and sensor supply to draw power from an isolated source. If a machine's Emergency Stop cuts the peripheral power ($P24$), the module remains "alive" on the network via the $L+$ system power, allowing it to report the status to the controller.
How is the input/output direction determined?
The direction is determined via the IO-Link parameterization. In the engineering tool (like TwinCAT), the user defines whether a specific pin should act as a Type 3 digital input or a 0.5 A digital output. No hardware jumpers are required.
Does this module support short-circuit diagnostics?
Yes. Every channel is individually short-circuit proof. The module can report short-circuit or overload conditions back to the IO-Link master, enabling precise identification of faulty field wiring or failed actuators.
Engineering & Installation Guide
-
Wiring for IP67: To maintain the environmental seal, M12 connectors should be tightened to a torque of 0.6 Nm. Unused I/O ports must be closed with M12 protective caps. Use high-quality A-coded M12 cables specifically rated for IO-Link Class B to ensure the $P24$ pins are connected.
-
Filter Optimization: For high-speed applications, the input filter can be reduced to 0 ms via IO-Link parameters. However, ensure that the field sensors are high-quality and the cabling is shielded to prevent nuisance triggers from electrical noise.
-
Power Planning: The current consumption from $L+$ (system) is typically 100 mA. Ensure the total load from the 8 outputs does not exceed the capacity of your IO-Link Master's Class B port supply (typically limited by the M12 connector's pin rating).
Engineering Advantages
The EPI2338-0002 represents the pinnacle of I/O flexibility. By allowing each port to be configured on the fly, it significantly simplifies spare parts inventory—one module can replace multiple dedicated input or output boxes. Its Type 3 input characteristics ensure compatibility with low-power sensors, while the 0.5 A outputs are robust enough to drive solenoids, relays, and indicators directly. With its -25 to +60 Celsius operating range and high shock/vibration resistance, the EPI2338-0002 provides a resilient, software-configurable I/O solution for the most modern B2B industrial automation architectures.